Ademco Contact ID Format Event Code Description
78
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
EVENT
MESSAGE
System Peripheral Troubles - 330 and 340
330 System peripheral
TROUBLE - Sys. Peripheral - #
331 Polling loop open
TROUBLE - Polling Loop Open
332 Polling loop short
TROUBLE - Polling Loop Short
333 Expansion module failure
TROUBLE - Exp. Module Fail - #
334 Repeater failure
TROUBLE - Repeater Failure - #
335 Local printer paper out
TROUBLE - Printer Paper Out
336 Local printer failure
TROUBLE - Local Printer
Communication Troubles - 350 and 360
350 Communication
TROUBLE - Communication Trouble
351 Telco 1 fault
TROUBLE - Phone Line #1
352 Telco 2 fault
TROUBLE - Phone Line #2
353 Long range radio xmitter fault
TROUBLE - Radio Transmitter
354 Fail to communicate
TROUBLE - Fail to Communicate
355 Loss of radio supervision
TROUBLE - Radio Supervision
356 Loss of central polling
TROUBLE - Central Radio Polling
Protection Loop Troubles - 370
370 Protection loop
TROUBLE - Protection Loop - #
371 Protection loop open
TROUBLE - Protection Loop Open - #
372 Protection loop short
TROUBLE - Protection Loop Short - #
373 Fire Trouble
TROUBLE - Fire Loop - #
Sensor Troubles - 380
380 Sensor trouble
TROUBLE - Sensor Trouble - #
381 Loss of supervision - RF
TROUBLE - RF Sensor Supervision - #
382 Loss of supervision - RPM
TROUBLE - RPM Sensor Supervision - #
383 Sensor tamper
TROUBLE - Sensor Tamper - #
384 RF transmitter low battery
TROUBLE - RF Sensor Batt. - #
Open/Close - 400
400 Open/Close
OPENINGCLOSING
401 Open/Close by user
OPENING - User #CLOSING - User #
402 Group Open/Close
OPENING - Group User #CLOSING - Group User #
403 Automatic Open/Close
OPENING - AutomaticCLOSING - Automatic
404 Late Open/Close
OPENING - LateCLOSING - Late
405 Deferred Open/Close
Opening not usedClosing not used
406 Cancel
OPENING - CancelClosing not used
407 Remote arm/disarm
OPENING - RemoteCLOSING - Remote
408 Quick arm
Opening not applicableCLOSING - Quick arm
409 Keyswitch Open/Close
OPENING - KeyswitchCLOSING - Keyswitch
Remote Access - 410
411 Callback request made
REMOTE - Callback RequestedRestore not applicable
412 Success - download/access
REMOTE - Successful Access
Restore not applicable
413 Unsuccessful access
REMOTE - Unsuccessful AccessRestore not applicable
414 System shutdown
REMOTE - System Shutdown
415 Dialer shutdown
REMOTE - Dialer Shutdown
416 Success - upload/access
REMOTE - Successful AccessRestore not applicable
Access Control - 420
421 Access denied
ACCESS - Access Denied - User #Restore not used
422 Access report by user
ACCESS - Access Gained - User #Restore not used
System Disables - 500 and 510
Summary of Contents for FIRE-LITE 411UDAC
Page 4: ...4 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...
Page 84: ...84 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...
Page 85: ...411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D 85 Notes ...
Page 86: ...86 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...