background image

411UDAC                                    

Fire Alarm Communicator

Installation, Programming, Troubleshooting 

and Operating Instruction Manual

One Fire-Lite Place
Northford, CT  06472 
Phone (203) 484-7161        
FAX: (203) 484-7118

P/N 51073:D         ECN 08-870

D

Document  #51073          
12/09/2008         Rev.

Summary of Contents for FIRE-LITE 411UDAC

Page 1: ...m Communicator Installation Programming Troubleshooting and Operating Instruction Manual One Fire Lite Place Northford CT 06472 Phone 203 484 7161 FAX 203 484 7118 P N 51073 D ECN 08 870 D Document 51073 12 09 2008 Rev ...

Page 2: ...s especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper stor age of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise...

Page 3: ...d Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board locatio...

Page 4: ...4 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...

Page 5: ...Alarm Communicator 16 Telephone Company Rights and Warnings 16 For Canadian Applications 17 CHAPTER 2 Installation 18 Mounting Options 18 Mounting 18 Transformer Mounting 18 Cabinet Dimensions and Knockout Locations 19 411UDAC Backbox 20 Operating Power 21 Operating Power Connections 21 Battery Cable Connections 22 Input Channels 23 Wiring Initiating Device Circuits 24 Typical Addressable FACP Con...

Page 6: ...ations 65 411UDAC Power Supply 66 Load in Standby 66 Load in Alarm 66 Programming Sheets 67 Digital Communicator Options Program Sheets 67 Digital Communicator Options Program Sheet Factory Defaults 69 Event Codes Transmission Format Programming Sheets 71 4 2 Standard 4 2 Express Formats Primary Central Station 71 4 2 Standard 4 2 Express Formats Secondary Central Station 71 4 2 Standard 4 2 Expre...

Page 7: ...ower Supplies for Fire Protective Signaling Systems UL 1635 Digital Alarm Communicator System Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN ULC S524 01 Standard for Installation of Fire Alarm Systems CAN ULC S527 99 Standard for Control Units for Fire Alarm Systems CAN ULC S559 04 Equipment for Fire Signal Receiving Centers and Systems This Class A di...

Page 8: ...Zone 2 B Zone 2 B Zone 3 B Zone 3 A Zone 3 A Zone 3 B Zone 4 B Zone 4 B Phone Line 1 Phone Line 2 Relay K5 and K6 PRO 411 DACT Programmer Battery Connector supervised nonpower limited AC Power Connector supervised nonpower limited Earth AC Neutral AC Hot 411UDABD CDR 411ANAC CDR 411AREL CDR HIGH VOLTAGE CAUTION Transformer Jumper J8 must be installed for proper panel operation All Circuits on TB2 ...

Page 9: ...11 Series DACT Programmer Model PRO 411 as well as the PK 411UD Windows 95 based remote site programming software The 411UDAC is supplied with a compact metal cabinet The digital communicator can be programmed or interrogated off site via the public switched telephone network Any IBM compatible personal computer with Windows 3 1 or greater with a 1200 baud Hayes compatible modem and Upload Downloa...

Page 10: ...tion number communication fault Secondary Central Station number communication fault system off normal local Program Mode entered 24 Hour normal test 24 Hour abnormal test 24 hour test message with previously reported alarm or trouble still active Individual LEDs for AC Power System Trouble Input Active Supervisory Communication Fail Battery Trouble Earth Fault Local piezo sounder with separate an...

Page 11: ... a minimum of one alarmed detector per zone Standby Current 5 17 mA including End of Line Resistor Channel Input 2 and Channel Input 4 Style B Class B contact closure input Short Circuit Current 4 46 mA maximum Maximum Loop Resistance 100 ohms Standby Current 2 66 mA Refer to Device Compatibility Document for listed compatible devices Notification Appliance Circuit TB4 Terminals 1 2 The 411UDAC No...

Page 12: ... activation fire supervisory activation 1 3 2 Notification Appliance Circuit One Style B NAC Notification Appliance Circuit requiring a 2 2K ohm End of Line resistor This NAC can only be used to supplement host panel NACs 1 3 3 Output Circuits Modular jacks are used to interface the primary and secondary phone lines to the public telephone network Phone lines are fully supervised at all times if c...

Page 13: ...sed to locally annunciate DACT alarms and troubles DACT troubles include input channel open circuit NAC fault phone line 1 or 2 voltage fault phone number 1 or 2 communication fault and total communication failure Separate and distinct sounds are provided for the following conditions alarm steady On trouble 1 second On and 1 second Off supervisory second On and second Off Front Panel Indicator AC ...

Page 14: ...be used to troubleshoot and program the 411UDAC as well as access the various modes of operation The PRO 411 must be ordered separately PK 411UD Upload Download Software Kit The optional PK 411UD Kit consists of the PK 411UD Upload Download software on 3 disk and the PK 411UD Program Manual The PK 411UD enables a user to program the 411UDAC off site via the public switched telephone network using ...

Page 15: ...med to do so Transmitted data includes fire alarm fire alarm trouble supervisory alarm and AC loss information Specific digital communicator troubles are also transmitted 1 8 2 Real Time Clock Mode Real Time Clock Mode allows the user to change the digital alarm communicator s internal 24 hour clock Connect ing an external Programmer allows access to the various Modes of operation While the 411UDA...

Page 16: ...tant The DACT must not be used to dial a phone number that is call forwarded per requirements of UL 864 9th Edition 1 9 3 Telephone Company Rights and Warnings The telephone company under certain circumstances may temporarily discontinue services and or make changes in its facilities services equipment or procedures which may affect the operation of this digital communicator How ever the telephone...

Page 17: ...made by an authorized Canadian maintenance facility designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metal...

Page 18: ...he lower two holes remove the backbox from the wall and drill the lower two holes in the wall Before mounting the backbox to the wall install the supplied transformer in the backbox by sliding the bot tom transformer flange into the lower transformer mounting slot Position the hole in the top transformer flange over the transformer mounting stud Refer to Figure 2 1 for the location of the slot and...

Page 19: ...5 36 83 cm 3 25 8 255 cm 1 75 4 445 cm 3 5 8 89 cm 12 5 31 75 cm 4 12 10 47 cm 6 12 15 55 cm 8 12 20 63 cm 10 12 25 75 cm 1 1 2 794 cm 6 5 16 51 cm 7 62 cm 3 0 FIGURE 2 2 Cabinet Dimensions and Knockout Locations 5024JRBB CDR Main Circuit Board Mounting Studs Transformer Mounting Stud Ground Stud Single Transformer Mounting Slot Double Transformer Mounting Slot Knockouts Top back Top front TR 3 R ...

Page 20: ...ment 51073 Rev D 12 09 2008 P N 51073 D Top Bottom Right Side Door 12 714 32 294 cm Backbox 12 5 31 75 cm Door 14 714 37 374 cm Backbox 14 5 36 83 cm Depth 2 875 7 303 cm Depth 3 7 62 cm FIGURE 2 3 411UDAC Backbox 411ACABB CDR ...

Page 21: ...ises main breaker box to TB3 of the main circuit board As per the National Electric Code use 14 AWG 2 00 mm2 or heavier gauge wire with 600V insula tion No other equipment may be connected to this circuit In addition this circuit must be provided with overcurrent protection and may not contain any power disconnect devices A separate earth ground connection must be made to ensure proper panel opera...

Page 22: ...ry terminal of the second battery When the panel is ready to have power applied connect the battery cable plug to connector J3 on the 411UDAC main circuit board The battery charger is current limited and capable of recharging sealed lead acid type batteries The charger shuts off when the system is in alarm Refer to the battery calculations table to determine the correct battery rating CAUTION Batt...

Page 23: ...ire smoke detectors Refer to Figure 2 6 Wiring Initiating Device Circuits on page 24 for information on wiring Style B and Style D circuits The channel inputs may be programmed as shown below A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72 It is allowable to mix an assortment of device types i e smoke detectors heat detectors pull stations ...

Page 24: ...detectors Channel 2 connected to manual pull stations Channel 3 connected to 2 wire smoke detectors and Channel 4 connected to waterflow devices In this example the factory default programming for Channel 4 must be changed from pull station to waterflow device 2 Wire Smoke Detectors Class B 2 Wire Smoke Detectors Class A Manual Pull Stations Class B Waterflow Devices Class B 411UDAC Main Circuit B...

Page 25: ...must be UL listed for Central Station Service and Remote Signaling Service 411UDAC Relay 2 Output DACT Trouble Channel 2 Zone 2 Channel 1 Zone 1 Channel 3 Zone 3 2 2K EOL Channel 4 2 2K EOL Monitor Circuit Input SLC Loop Trouble Relay Alarm Relay Supervisory Relay UL listed 2 2K EOLs P N 27070 Program the 411UDAC as follows Channel 1 Normally Open Contact Device alarm Channel 2 Host Panel Trouble ...

Page 26: ... supplement host panel NACs 2 Do not connect strobes to the 411UDAC Notification Appliance Circuit The NAC may be programmed as follows Silenceable Nonsilenceable waterflow Silence Inhibited one minute Autosilence 5 to 30 minutes TB4 B NAC 12V POWER B FIGURE 2 8 Notification Appliance Circuit Connections Style Y Class B Notification Appliance Circuit supervised and power limited 2 2K ohms watt P N...

Page 27: ...y Note Relay connections may be power limited or nonpower limited provided that 0 25 spacing is maintained between conductors of power limited and nonpower limited circuits Relays automatically change to energized condition when programmed for Trouble 411ARELE CDR Relay 1 Shown Programmed for Alarm Supervisory or any other function except DACT Trouble and Host Panel Trouble relay contacts shown in...

Page 28: ...ION It is critical that the 411UDAC be located as the first device on the incoming telephone circuit to properly function FIGURE 2 11 Wiring Phone Jacks To Premises Phone Green Wire Red Wire Red Wire Tip Ring Ring Tip Ring Tip Ring Tip To Premises Phone Primary Lines Incoming Telco Phone Lines Secondary Lines Incoming Telco Phone Lines Note Shorting bars inside RJ31X Jack removed during male plug ...

Page 29: ...ogrammer 1 Remove all power from the 411UDAC 2 Unlock and open the 411UDAC door 3 Connect the Programmer cable to connector J2 located in the lower right corner of the 411UDAC Note that the key on the connector must align with the slot in the J2 connector 4 Reapply power to the 411UDAC 5 Operate the Programmer by pressing the MODE key Enter the appropriate four digit code and then press the ENTER ...

Page 30: ...ed circuit wiring Furthermore all power limited and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the 411UDAC is shown below FIGURE 2 12 Typical UL Power limited Wiring Diagram AC Power Nonpower limited Circuits Power limited Circuits 411AULPW CDR Note Relay connections may be power limited or nonpower limit...

Page 31: ...s operating free of internal troubles the unit will dis play the following conditions All LEDs are off except the AC Power LED NAC output is off Onboard piezo sounder is off The relays are in their normal deactivated state Communicator is not transmitting to the Central Station The 411UDAC transmits system status reports to a central station if programmed to do so via the public switched telephone...

Page 32: ...y Functions MODE KEY Pressing the MODE key followed by a valid 4 digit numerical code and the ENTER STORE key selects one of the five modes of operation To enter Normal Mode from any other mode press the MODE key followed by 6676 and then ENTER STORE 6676 spells NORM on a Touch Tone phone If an incorrect key is entered reenter the proper 4 digit code before pressing the ENTER STORE key Note that a...

Page 33: ...digits of the desired address For example to view the contents of address 86 press the 8 key on the keypad 8 will appear as the first digit in the display a blank will appear in the position of the second digit and the decimal point will move one position to the right indicating that the next digit can now be entered Press the 6 key on the keypad 6 will appear as the second digit on the display an...

Page 34: ...Time Clock Mode 0 001 will appear on the Programmer display The time is displayed in military time Note the position of the decimal point in the display This indicates that the first digit to be programmed is the one to the left of the decimal point To program the first hour digit press the cor responding number on the Programmer keypad and then press the ENTER STORE key For example to program 2 0...

Page 35: ...mmed if desired If all factory default set tings are acceptable programming is complete Program Mode is entered by pressing the MODE key followed by the 4 digit program mode entry code 7764 and pressing the ENTER STORE key 7764 spells PROG on a Touch Tone phone If an incorrect key is entered reenter the proper 4 digit code before pressing the ENTER STORE key Note that as information is entered int...

Page 36: ...dress to 0 When desired changes have been completed exit Programming Mode by pressing the MODE key followed by the 4 digit code for an alternate mode and then the ENTER STORE key During Program Mode if no key is pressed within 10 minutes the unit will revert to Normal Mode The Programmer cable should not be removed from the 411UDAC unless the unit is in Normal Mode If the Pro grammer cable is remo...

Page 37: ...tandard 1800 Hz Carrier 2300 Hz ACK 3 3 1 Expanded 1800 Hz Carrier 2300 Hz ACK 4 3 1 Standard 1900 Hz Carrier 1400 Hz ACK 5 3 1 Expanded 1900 Hz Carrier 1400 Hz ACK 6 4 1 Standard 1800 Hz Carrier 2300 Hz ACK 7 4 1 Expanded 1800 Hz Carrier 2300 Hz ACK 8 4 1 Standard 1900 Hz Carrier 1400 Hz ACK 9 4 1 Expanded 1900 Hz Carrier 1400 Hz ACK A 4 2 Standard 1800 Hz Carrier 2300 Hz ACK B 4 2 Expanded 1800 ...

Page 38: ...elected in address 20 The last location 1 farthest right represents the contents of memory address 145 which is the first digit of the event code The following Tables list the data which is automatically programmed for each Format that can be selected in address 20 The addresses shown in each Table contain the Setting data which is automatically programmed by the 411UDAC To change the value key in...

Page 39: ...Input Channel 3 Fault Event Code 380 003 166 168 Primary Input Channel 4 Fault Event Code 380 004 169 171 Primary AC Voltage Fault Event Code 301 000 172 174 Primary Earth Fault Event Code 310 000 175 177 Primary Low Battery Fault Event Code 302 000 178 180 Primary No Battery Fault Event Code 311 000 181 183 Primary Phone Line 1 Voltage Fault Event Code 351 000 184 186 Primary Phone Line 2 Voltage...

Page 40: ...ne Number 1 Communication Fault Event Code 6A 179 180 Primary Phone Number 2 Communication Fault Event Code 6B 181 182 Primary System Off Normal Fault Event Code 6F 183 184 Primary Input Channel 1 Active Restore Code E1 185 186 Primary Input Channel 2 Active Restore Code E2 187 188 Primary Input Channel 3 Active Restore Code E3 189 190 Primary Input Channel 4 Active Restore Code E4 191 192 Primary...

Page 41: ...C Fault Event Code 6 160 Primary Charger Fault Event Code 4 161 Primary Phone Number 1 Communication Fault Event Code 6 162 Primary Phone Number 2 Communication Fault Event Code 6 163 Primary System Off Normal Fault Code 6 164 Primary Input Channel 1 Active Restore Code E 165 Primary Input Channel 2 Active Restore Code E 166 Primary Input Channel 3 Active Restore Code E 167 Primary Input Channel 4...

Page 42: ...the factory default entry of 0 If other test report times are needed enter 1 12 hour 2 8 hour or 3 6 hour Secondary Central Station Phone Number 30 49 Addresses 30 49 are factory set to F 30_F to 49_F Programming is typically done as follows If your phone number is 484 7161 press 4 The display will read 30_4 Press ENTER STORE to save the entry to memory and increment to the next address 31_F Enter...

Page 43: ...addresses 229 312 with the factory default settings Any of the Event Code settings may be altered Consult your Central Station prior to alter ing the event code settings An entry of all zeros for any event code will cause the communicator to NOT transmit the report Transmission of reports to either or both Central Station phone numbers may be disabled Refer to Central Station Communications on pag...

Page 44: ...ent Code 380 003 254 256 Secondary Input Channel 4 Fault Event Code 380 004 257 259 Secondary AC Voltage Fault Event Code 301 000 260 262 Secondary Earth Fault Event Code 310 000 263 265 Secondary Low Battery Fault Event Code 302 000 266 268 Secondary No Battery Fault Event Code 311 000 269 271 Secondary Phone Line 1 Voltage Fault Event Code 351 000 272 274 Secondary Phone Line 2 Voltage Fault Eve...

Page 45: ...ber 1 Communication Fault Event Code 6A 267 268 Secondary Phone Number 2 Communication Fault Event Code 6B 269 270 Secondary System Off Normal Fault Event Code 6F 271 272 Secondary Input Channel 1 Active Restore Code E1 273 274 Secondary Input Channel 2 Active Restore Code E2 275 276 Secondary Input Channel 3 Active Restore Code E3 277 278 Secondary Input Channel 4 Active Restore Code E4 279 280 S...

Page 46: ...t Code 6 248 Secondary Charger Fault Event Code 4 249 Secondary Phone Number 1 Communication Fault Event Code 6 250 Secondary Phone Number 2 Communication Fault Event Code 6 251 Secondary System Off Normal Fault Code 6 252 Secondary Input Channel 1 Active Restore Code E 253 Secondary Input Channel 2 Active Restore Code E 254 Secondary Input Channel 3 Active Restore Code E 255 Secondary Input Chann...

Page 47: ...6 hours E 17 hours F 18 hours Note UL requires a minimum of 2 hours delay Backup Reporting 61 Leaving address 61 at 0 means that reports will be transmitted to the secondary Central Station phone number only if attempts to communicate to the primary Central Station phone number are unsuccessful Programming a 1 causes all reports to be transmitted to both the primary and secondary Central Station p...

Page 48: ...trouble and fire supervisory must not be delayed A delay therefore cannot be selected for inputs programmed for these fire applications If the input is set for a waterflow function the delay timer will also delay activation of the relay piezo sounder and LEDs Input Channel 2 Delay Timer 72 74 2 The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input C...

Page 49: ...ry phone line Select 1 for rotary dialing Make Break Ratio for Secondary Phone 84 This address is used only if a 1 has been programmed for address 83 The Make Break ratio is factory set to 0 which is 67 33 ratio but may be changed to 1 which is 62 38 ratio Output Relay 1 Enable 85 The factory default setting for Output Relay 1 is 0 for disabled Enter 1 to enable the relay Output Relay 1 Function S...

Page 50: ...d time interval between 5 and 30 minutes Enter 1 for 5 minute autosilence 2 for 10 minutes 3 for 15 minutes 4 for 20 minutes 5 for 25 minutes 6 for 30 minutes The factory default is 0 for no autosilence Restoral Method 94 Note Restoral Method refers to the communication of Restoral Events to a Central Station It has no effect on the actual input circuit restoral itself Typical Restoral Method 0 en...

Page 51: ...s will never restore in Stand alone Mode until the Reset Switch is pressed If both an Autoresettable input circuit and a Latching input circuit are activated and subsequently cleared only the Autoresettable input circuit will restore but no transmission will occur to the Central Station since there is still an input circuit active the Latching input circuit TABLE 3 8 Restoral Methods Input Circuit...

Page 52: ...r from answering incoming calls FAX Answer Machine Primary Phone Line 123 This entry is used when the primary phone line is being shared with a FAX answering machine or other device Factory default is 0 for no sharing of the primary phone line An entry of 1 indicates that another device is shar ing the primary phone line The communicator will wait for three consecutive calls from the Service Termi...

Page 53: ...rd activity for a period of 20 minutes will cause the panel to return to Normal Mode To access the Troubleshoot Mode press the MODE key followed by the digits 8768 and then the ENTER STORE key 8768 spells TROU on a Touch Tone phone Once in this mode the 411UDAC will continue to communicate any events not yet acknowledged at a central station prior to entering Troubleshoot Mode The UP arrow DOWN ar...

Page 54: ...Circuit status n S O voltage 1 0V 0V 5 5V Where n normal S shorted and O open Telephone Line Testing Pressing C for touchtone dialing or D for rotary dialing followed by ENTER STORE causes seizure of the Primary phone line After a delay of three seconds the 411UDAC goes off hook to acquire a dial tone The Programmer keypad may be used as a telephone touchpad for number dialing Once the first digit...

Page 55: ...l be reported to a central station over the remaining good phone line The digital communicator comes with line seizure capability provided for both the primary and secondary telephone line interfaces Any time that the DACT needs to make a call to a central station line seizure will disconnect any local premises phones sharing the same telephone line All transmissions to central stations will be se...

Page 56: ...3 5 7 9 Format 1 A C Format B D Report 3 1 4 1 Standard 4 1 Express 3 1 4 1 Expanded 4 2 Standard 4 2 Express 4 2 Expanded Fire Alarm SSS S FA SSS S FA FAFAFA FA 2 SSSS FAFA2 SSSS FAZ Fire Alarm Restore SSS S RFA SSS S RFA RFARFARFA RFA 2 SSSS RFARFA2 SSSS RFAZ Channel Input Trouble Channel Input Open SSS S TZ SSS S TZ TZTZTZ TZ Z SSSS TZTZ2 SSSS TZZ Channel Input Trouble Restore SSS S RTZ SSS S R...

Page 57: ...re Supervisory Condition 2nd digit RV Fire Supervisory Condition Restore 1st digit RV2 Fire Supervisory Condition Restore 2nd digit X Test Report 1st digit X2 Test Report 2nd digit Y Trouble corresponding to the following 1 Not Used 2 Not Used 3 Not Used 4 Telco Primary Line Fault 5 Telco Secondary Line Fault 6 Not Used 7 Not Used 8 Not Used 9 Not Used A Communication Failure Primary Number B Comm...

Page 58: ...ending order 1 Fire Alarm highest priority level 2 Fire Supervisory 3 System Troubles Host Panel Trouble active input programmed for trouble AC Fail after delay Channel Input faults Telephone line fault Communication trouble System Off Normal 4 Restoral Reports Fire Alarm Fire Supervisory Host Panel Trouble AC Channel Input fault Telephone line Communication System Off Normal 5 System Test 6 Uploa...

Page 59: ...re is printed out in the report as an E for New Event or R for New Restore 3 GG Group Number is fixed at 00 and cannot be changed 4 CCC Channel Input Number is transmitted as 001 for Channel Input 1 002 for Channel Input 2 003 for Channel Input 3 004 for Channel Input 4 Ademco Contact ID Reporting Structure A typical printout from a Central Station receiver such as the Ademco 685 of alarm and trou...

Page 60: ...g service prior to installation The Compatibility Table provides a list of compatible receivers and associated software versions for the receivers Changes in the hard ware and or software by the receiver manufacturers may affect the receiver compatibility with the DACT After com pleting the installation communication between the DACT and Central Station Receiver must be tested and verified TABLE 4...

Page 61: ...ode is not verified the communicator will terminate the request immediately In order to contact the communicator the following must be true The digital communicator may be in any mode of operation including Normal Program Real Time Clock Troubleshoot or Lamp Test Downloading is not possible if the communicator is active during Central Station communications or while testing the phone lines while i...

Page 62: ...nicator immediately terminates down loading processes the trouble or alarm locally and transmits the information to the Central Station s 5 1 1 Security Features Remote site upload and download with the 411UDAC have been carefully designed to include key security features to ensure proper functionality The key features are listed and explained below Secret Code Verification A secret code is stored...

Page 63: ...eps 4 through 10 if no callback is requested perform steps 9 and 10 only 4 Verify product type 5 Identify the Service Terminal location 6 Hang up disconnect call 7 Call the Central Station s and transmit a request for upload download message if programmed to do so If this message is accepted the communicator will proceed to the next step 8 Return call to the Service Terminal 9 Verify secret code 1...

Page 64: ...eturn call to the Service Terminal 9 Verify secret code 10 Verify product type 11 Begin downloading 12 Upon completion of download call the Central Station s back and report a successful download or failed upload download status if programmed to do so Unlike most competitive products during the uploading process the 411UDAC fire protection remains active Should a system trouble or alarm condition ...

Page 65: ...ndby NFPA 72 for Auxiliary and Remote Station systems require 60 hours of standby 14 Amp Hours 2 Two 12 VDC 7 Amp Hour batteries wired in parallel can be located in the backbox to provide 14 Amp Hours of backup refer to Figure 2 5 on page 22 for battery cable connections TABLE 6 1 Battery Calculations Standby Load Current in amps from Table 6 2 X Required Standby Time in Hours 24 or 60 Hours _____...

Page 66: ...ment 2 Refer to the Device Compatibility Document for 4 wire smoke detector current 3 Maximum available current for notification appliances is 1 0 amp 4 Maximum available current from resettable output is 0 200 amps 5 Total system current cannot exceed 1 6 amps 6 For Remote Station applications total standby current must not exceed 193 mA TABLE 6 2 Load in Standby Device Type of Devices Current am...

Page 67: ... hours 61 Backup Reporting Enter 0 to report to Secondary phone number as backup only 1 to report to both Primary and Secondary phone number for all reports messages 2 reports go to first available receiver 62 Reserved for Future Use 63 DACT Trouble Reminder Enter 0 to disable 1 to enable 64 Operational Mode Selection Enter 0 for stand alone communicator disabled 1 for stand alone communica tor en...

Page 68: ...fication 1 for verification of all 2 wire smoke zones 92 Silence inhibit Enter 0 for no silence inhibit 1 to inhibit silencing of NAC for one minute 93 Autosilence Enter 0 for no autosilence 1 for 5 minute autosilence 2 for 10 minutes 3 for 15 minutes 4 for 20 minutes 5 for 25 minutes 6 for 30 minutes 94 Restoral method Enter 0 for Typical restoral method 1 for Conditional Restoral Method 1 2 for ...

Page 69: ...condary Number Test Time Interval 0 for 24 hours 60 AC Loss Reporting Delay 2 for 2 hour delay 61 Backup Reporting 0 to report to Secondary Central Station phone number as backup only 62 Reserved for Future Use 63 Trouble Reminder 0 disables Trouble Reminder 64 Operational Mode Select 0 enables stand alone mode disables communication to Central Station 65 Input Channel 1 Function Selection 0 for f...

Page 70: ...6 Trouble Call Limit Dialer Runaway Prevention Feature 0 for disabled feature 97 98 99 100 Future Use 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 Addresses 101 to 120 store the Service Terminal 1 Phone Number Valid entries are 0 9 and A E F designates the end of the phone number 121 122 Ring Count on Primary Phone Line 03 for number of rings before answering cal...

Page 71: ...177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 B 2 4 2 Standard 4 2 Express Formats Secondary Central Station 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 2...

Page 72: ... 229 230 231 232 B 4 4 2 Standard 4 2 Express Formats Secondary Central Station 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 ...

Page 73: ... 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 B 7 All 3 1 All 4 1 and 4 2 Expanded Formats for Primary Central Station Factory Defaults 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 B 8 All 3 1 All 4 1 and 4 2 Expanded Formats ...

Page 74: ...172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 B 10 Ademco Contact ID Format Secondary Central Station 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 ...

Page 75: ...19 B 12 Ademco Contact ID Format Secondary Central Station Factory Defaults 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 1 1 1 1 1 5 1 1 1 1 1 5 ...

Page 76: ...118 Near Alarm FIRE Near Alarm Panic Alarms 120 120 Panic Alarm PANIC Panic 121 Duress PANIC Duress 122 Silent PANIC Silent Panic 123 Audible PANIC Audible Panic Burglar Alarms 130 130 Burglary BURG Burglary 131 Perimeter BURG Perimeter 132 Interior BURG Interior 133 24 Hour BURG 24 Hour 134 Entry Exit BURG Entry Exit 135 Day Night BURG Day Night 136 Outdoor BURG Outdoor 137 Tamper BURG Tamper 138...

Page 77: ...Low Water Pressure 202 Lox CO2 SUPER Low CO2 203 Gate valve sensor SUPER Gate Valve 204 Low water level SUPER Low Water Level 205 Pump activated SUPER Pump Activation 206 Pump failure SUPER Pump Failure System Troubles 300 and 310 300 System trouble TROUBLE System Trouble 301 AC loss TROUBLE AC Power 302 Low system battery TROUBLE System Low Battery 303 RAM checksum bad TROUBLE Bad RAM Checksum Re...

Page 78: ...trouble TROUBLE Sensor Trouble 381 Loss of supervision RF TROUBLE RF Sensor Supervision 382 Loss of supervision RPM TROUBLE RPM Sensor Supervision 383 Sensor tamper TROUBLE Sensor Tamper 384 RF transmitter low battery TROUBLE RF Sensor Batt Open Close 400 400 Open Close OPENINGCLOSING 401 Open Close by user OPENING User CLOSING User 402 Group Open Close OPENING Group User CLOSING Group User 403 Au...

Page 79: ...isabled DISABLE Dialer Disable 552 Radio transmitter disabled DISABLE Radio Disable Bypasses 570 570 Zone bypass BYPASS Zone Bypass 571 Fire bypass BYPASS Fire Bypass 572 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 Manual trigger test TEST Manually TriggeredRestore not applicable 602 Periodic test report TES...

Page 80: ...anged 411UDAC Events Format Group 1 Format Group 2 Ademco Contact ID Input Circuit Functions Active Restore Active Restore Active and Restore Sensor 2 Wire Smoke 1x Ex 1 E 111 00x Pull Station 1x Ex 1 E 115 00x Contact Closure 1x Ex 1 E 110 00x Host Control Panel Trouble FF Ex F E 373 00x Latching Supervisory 8x Ex 8 E 200 00x Autoresettable Supervisory 8x Ex 8 E 200 00x Silenceable Waterflow 1x E...

Page 81: ...ters Real Time Clock Mode Program digital communicator time Fire protection is off 7764 PROG Enters Program Mode Allows programming of digital communicator Fire protection is off 3337 DEFP Returns digital communicator to factory default program settings Fire protection is off during Default Mode 8768 TROU Allows display of status for all circuits Fire protection is off during Troubleshoot Mode ...

Page 82: ...ines must exit the building in separate directions 3 The 411UDAC DACT relay 1 must be enabled refer to Output Relay 1 Enable 85 on page 49 and must be programmed to activate on DACT trouble refer to Output Relay 1 Function Selections 86 on page 49 4 The Auxiliary Trouble Input wiring from the 411UDAC DACT must be in conduit and in the same room as the FACP and DACT 411UDAC FACP Auxiliary Trouble I...

Page 83: ...stor 11 Operating Voltage 11 Style Y 11 O Operating Power connections 21 Primary 21 Secondary 22 see also Battery Operational Modes Default Mode 15 53 Normal Mode 15 31 Program Mode 15 35 Real Time Clock Mode 15 34 Troubleshoot Mode 15 53 Output Circuits 26 battery charger 12 resettable power 12 telephone circuits 12 see also Telephone Circuits P Panel Configuration Nonlatching Slave Panel Communi...

Page 84: ...84 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...

Page 85: ...411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D 85 Notes ...

Page 86: ...86 411UDAC Document 51073 Rev D 12 09 2008 P N 51073 D Notes ...

Page 87: ...n Material Authorization form from our Return Authorization Department This writing constitutes the only warranty made by Honeywell International Inc with respect to its products Honeywell International Inc does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer ackn...

Page 88: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...

Reviews: