64
Emergency Command Center Manual —
P/N LS10001-000FL-E:D 9/3/2014
Programming
Main Menu - User Programming
Mic Gain is the microphone's transmitting “volume control”. The gain number is automatically
entered when a remote console is programmed.
Speaker Circuit Address Assignment
Primary Operator Console - Circuit Expander
If the ECC-CE6 has been installed on P1 of
the main circuit board, select
CE6 - Installed
from the drop down box. The ECC-50/100 comes
with one (1) integrated speaker circuit. Adding the CE6 gives the system three (3) more speaker
circuits for a total option of four (4) from the drop-down box. If the optional amplifier (ECC-50W-
25/70V) has been installed and programmed as a
secondary
speaker circuit on the General / NAC
Options page, then the total available speaker circuits allowed for the POC will be eight (8). Refer
to application examples on pages 53–54.
Remote Amplifiers
Identify which, if any, remote amplifiers are
Installed
on the system in
addresses 20-27. The remote amplifiers must be installed sequentially. If, for example, remote
amplifiers are installed on addresses 20 and 21, address 22 must be
Disabled
if address 23 is to be
used. If no remote amplifiers are installed at a given address, select
Not Installed
.
Circuit Expander Option
For any installed remote amplifier, select whether any circuit
expanders (ECC-CE4) have been
Installed
.
Speaker Circuit Assignments
Select how many speaker circuits will be used for each ampli-
fier. Each amplifier offers four (4) speaker circuits standard. If the CE4 has been installed, eight
(8) speaker circuits will be available. Note the the ECC allows a maximum of 24 speaker circuits
in the system.
70VAC Option
For every programmed 50W remote amplifier, select whether a 70V transformer
has been
Installed
or
Not Installed
. 70V operation is not available on the 125W model.
Figure 3.7 Remote Amplifier Address Assignments