23
MRP-4424 Document 15180 Rev D 03/12/97 15180:D
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
}
}
}
}
no connection
Relay #1
Relay #2
Relay #3
Relay #4
}
}
}
}
Zone Relay Module -- 4XZMF
Non-power limited and power limited wiring must have a minimum distance of 0.25" wire to wire. If this
module is used to drive non-power limited and power limited circuits, please follow the instructions below:
}
}
}
}
}
}
Relay #1
Relay #2
Relay #3
Relay #4
Alarm
Trouble
NO
NC
C
NO
NC
C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Relay #1 through #4 will activate with Output #1 through #4
and remain latched unless jumper "LATCH" is cut.
Use Disable switch to
disconnect the relays
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
Cut jumper for non-latching
(silenceable) relay operation
power limited
circuit
power limited
circuit
non-power
limited circuit
non-power
limited circuit
Note:
Refer to the Protected Premises Unit label, located on the door of the control panel, to indicate if any dry contacts are
to be used as non-power limited dry contacts.
1) Skip a set of dry contacts to maintain the 0.25" required space between power limited and non-power
limited circuits. The wiring of this module must follow the requirements as specified in the
"General" sec-
tion,
"UL Power Limited Wiring Requirements."
OR
2) If this module is needed to drive power limited and non-power limited relays that are next to each other,
refer to the figure below showing a typical connection: