background image

24

 MRP-4424     Document  15180     Rev D     03/12/97     15180:D

Side View

Front View

Single-gang Box

Connect to corresponding terminals of
RZA-4XF Remote Annunciator.

+24V
Out #1
Out #2
Out #3
Out #4
System Trouble
Sound
Resound

1
2
3
4
5
6
7
8

The wiring of this module must follow the requirements as specified in the 

"General" section, "UL

Power Limited Wiring Requirements."

LED Interface Module -- 4XLMF

Figure 3.6-3:  LED Interface Module -- 4XLMF

Note:  Make wiring connections with system
power off.  Maximum wire impedance is 50
ohm per wiring connection.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for MRP-4424

Page 1: ...The MRP 4424 Agent Release Control Panel DOCUMENT 15180 ECN96 433 03 12 97 Rev D 12 Clintonville Road Northford CT 06472 Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Page 3: ...2 2 Control Switches 12 2 3 Zone Status LEDs 12 2 4 Supervisory 13 2 5 Zone Disable 13 2 6 Last Event Recall 13 3 0 Installation Procedure 14 3 1 General 14 3 2 Initiating Device Circuits 15 3 3 4 Wire Smoke Detector Connections 16 3 4 Output Circuits 17 3 5 Power 18 3 6 Optional Modules 20 3 7 Setting MRP 4424 Mode of Operation 25 Appendix A Battery Calculations 27 Appendix B NFPA Standard Specif...

Page 4: ...le Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Noti Fire 911A Manual Document 74 06200 005 MS 5012 Manual Document 15465 Fire Lite Device Compatibility Document 15384 ADA Americans with Disabilities Act I NFPA Standards The MRP 4424 complies with the following NFPA standards NFPA 12 CO2 Extinguishing Systems High Pressure Only NFPA 12A Halon 1301 Extingui...

Page 5: ...all Notification Release Circuits RMS regulated output power 2 25 amps 7 amp hour to 15 amp hour battery options up to 90 hours standby Resettable and non resettable regulated power outputs Extensive transient protection Watchdog timer to supervise microprocessor in cludes MICRO FAIL LED Output circuits protected against false activations Slide in zone identification labels Steel cabinet 14 5 wide...

Page 6: ...6 MRP 4424 Document 15180 Rev D 03 12 97 15180 D Figure 1 0 1 MRP 4424 Installation Diagram Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...alarm exists Zone Relay Module 4XZMF The Zone Relay module provides Form C contacts for the following As a jumper option the first four relays described below can be made silenceable LED Interface Module 4XLMF The LED Interface Module supports the RZA 4XF Remote Annunciator module Annunciator wiring is supervised for open conditions by this module The Annunciator Driver Module mounts to the main b...

Page 8: ...istive 0 5 amps 30 VAC resistive 1 4 Remote Annunciator NotifierRemoteAnnunciator RZA 4XF The Remote Annunciator mounts on a standard single gang box and provides LED indication of the same functions as the zone relay module For example with DIP 1 ON and DIP 2 OFF One Zone in Alarm red Two Zones in Alarm red Releasing Circuit 1 red Releasing Circuit 2 red System Trouble yellow A Local Trouble Soun...

Page 9: ...o Style Y Z NACs two Style Y Releasing Circuits Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to all external devices 2 25 amps Maximum signaling current per circuit 1 5 amps End of line resistor 4 7K 1 2 Watt part 71252UL listed Alarm and Trouble Relays Dry Form C contacts rated 2 0 amps 30 VDC resistive 0 5 amps 30 VAC resistive All re...

Page 10: ... Rev D 03 12 97 15180 D Figure 1 6 1 Cabinet Dimensions Cabinet 5 375 Backbox 4 750 Door 16 125 Backbox 16 Door 14 625 Backbox 14 5 Optional Trim Ring TR 4XRF Technical Manuals Online http www tech man com firealarmresources com ...

Page 11: ... flashes for any trouble condi tion including those associated with option boards CIRCUITTROUBLE Yellow LED that flashes for trouble conditions on output circuits notification and releasing circuits ALARMSILENCED Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm POWERTROUBLE YellowLEDthatflashesforlowordisconnected batteries and earth fault condition...

Page 12: ...ing circuits The ALARM SILENCED LED will illuminate Alarm silence is a latching function and requires a RESET to clear ALARMACTIVATE The ALARM ACTIVATE switch may be used to activate Notification ApplianceCircuits ALARMACTIVATEalsoactivatestheSystemAlarm relay ALARM ACTIVATE is a latching function Pressing ALARM SILENCE silences the notification appliance circuits and System Alarm Relay and lights...

Page 13: ...switch 2 With the TONE SILENCE switch held in press in sequence the ALARM SILENCE switch the ALARM ACTIVATE switch and then the RESET switch 3 The Zone 1 Alarm LED will flash 4 To disable Zone 1 press the RESET switch The Zone 1 yellow LED will light to show that the zone is disabled Note The RESET switch toggles disable status for the selected zone 5 To select the next zone press the ALARM SILENC...

Page 14: ...dance with the National and or Local codes for fire alarm systems UL Power Limited Wiring Requirements Power limited and non power limited circuit wiring must remain separated in the cabinet All power limited circuit wiring must remain at least 0 25 away from any non power limited circuit wiring Furthermore all power limited circuit wiring and non power limited circuit wiring must enter and exit t...

Page 15: ...ual Pull Station HeatDetector Two wire SmokeDetector Abort Switch Manual Release IDC 1 IDC 2 IDC 3 IDC 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 4 7K 1 2 Watt part 71252 UL listed 4 7K 1 2 Watt part 71252 UL listed Notes 1 Observe polarity when connecting polarized devices 2 All circuits are supervised and power limited 3 Leave Dummy Load provided on all unused circuits Style B Initiating Device Ci...

Page 16: ...elay current RMAX 20 6 VOM N x IS NA x IA IR 3 3 4 Wire Smoke Detector Connections Refer to the Device Compatibility Chart for suitable 4 wire smoke detectors 24 VDC Common IDC IDC Red Black 24 VDC Common IDC IDC UL listed24VDC Four WireSmokeDetectors UL Listed 4 7K 1 2 Watt ELR TB1 1 2 3 4 TB4 1 2 3 4 B A A B 24VR A maximum of 200mA is available from the 24VDC 4 wire smoke detector power circuit ...

Page 17: ...n of maximum allowable resistance RMAX 20 6V 20 4V IS Where RMAX maximum allowable resistance of wiring IS solenoid current Dummy Load all unused Notifi cationApplianceCircuits 4 7K 1 4 Watt UL ListedEnd of Linedevice 4 7K 1 4 Watt UL listedEnd of Linedevice Dummy Load all unused Releasing Circuits OUT 1 OUT 2 OUT 3 OUT 4 Figure 3 4 1 Notification Appliance Circuits B A A B B A A B B B B Polarized...

Page 18: ...tedtothispanel Disconnect allsourcesofpowerbeforeservicing Thepanelandassociatedequipmentmaybedamaged by removing and or inserting cards modules or interconnecting cables while this unit is energized This output is not suitable for power ing devices requiring filtered regu lated DC power ThecombinedcurrentdrawsfromtheResettableandNon Resettableoutputscannot exceed 200 mA RMS Regulated Power 24 VDC...

Page 19: ...ger wire with 600 volt rating Battery Power Observe polarity when connecting battery Connect battery cable to J9 on the main board using the plug in connector provided See Appendix A for calculation of correct battery rating Voltmeter Ammeter To monitor battery voltage and battery charging current a 4XMMF is required To install the power meter module remove the jumper labeled AMP and connect cable...

Page 20: ...duplicatemodules seenotesbelow Thecorresponding option jumper must be cut before installation of an optional module Notes 1 Optional 4XLMF module for an RZA 4XF Annunciator must be installed on J7 and J8 only 2 4XTMF and 4XZMF modules can be installed in either location Figure 3 6 1 Option Panel Modules Cut for Ring by Zone J4 J7 J8 J5 Technical Manuals Online http www tech man com firealarmresour...

Page 21: ...gn the pins on the main board with J1 and or J2 on the option board Insert screws provided into the holes on the top of the stand offs Affix the terminal identification labels provided with the option modules as shown below Stand offs Option Board 4XZMF shown Main Board Figure 3 6 2 Installing Option Modules Part 42050 Technical Manuals Online http www tech man com firealarmresources com ...

Page 22: ...witch down to prevent unwanted activation of the Municipal Box during testing of the control panel The Disconnect LED will remain illuminated while the Municipal Box is disconnected The System Trouble LED will indicate disconnected and or Open Circuit conditions on the Municipal Box Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble if no alarm exists Dummy loa...

Page 23: ... NC C NO NC C NO NC C Cut jumper for non latching silenceable relay operation powerlimited circuit powerlimited circuit non power limited circuit non power limited circuit Note Refer to the Protected Premises Unit label located on the door of the control panel to indicate if any dry contacts are to be used as non power limited dry contacts 1 Skip a set of dry contacts to maintain the 0 25 required...

Page 24: ...und Resound 1 2 3 4 5 6 7 8 The wiring of this module must follow the requirements as specified in the General section UL Power Limited Wiring Requirements LED Interface Module 4XLMF Figure 3 6 3 LED Interface Module 4XLMF Note Make wiring connections with system power off Maximum wire impedance is 50 ohm per wiring connection Technical Manuals Online http www tech man com firealarmresources com ...

Page 25: ... i r e d m o d e o f o p e r a t i o n a n d s e t S W 1 D I P s w i t c h 1 1 2 3 4 5 6 O N D I P S w i t c h e s S w i t c h 1 C R O S S Z O N E S w i t c h 2 S U P E R V I S O R Y T h e T i m e rw i l l s t a r t w h e n e v e r a n a l a r m o c c u r s o n e i t h e r Z o n e 1o r Z o n e 2 T h e T i m e rw i l l s t a r tw h e n a l a r m s o c c u r o n b o t h Z o n e 1 a n d Z o n e 2 O u...

Page 26: ... S w i t c h e s 3 a n d 4 p l u s 9 0 s e c o n d s T h e t i m e r w i l l n o t s t a r t a s l o n g a s t h eA B O R T s w i t c h i s h e l d S Y S T E M R E S E T r e s t o r e s t i m e r t o o r i g i n a l t i m e s s e l e c t e d v i a D I P S w i t c h e s 3 a n d 4 S u c c e s s i v e A B O R T S w i l l a d d 9 0 s e c o n d s t o s e l e c t e d t i m e r v a l u e O NO N L o c a l...

Page 27: ... C o n t r o l P a n e l 8 8 m A C o n t r o l p a n e l w i t h A C p o w e r o f f S y s t e m T r o u b l e L E D a n d a u d i b l e t r o u b l e s o u n d e r o n I f u s i n g a 4 X Z M F Z o n e R e l a y M o d u l e1 X 8 m A I f u s i n g a 4 X T M F T r a n s m i t t e r M o d u l e a d d 1 1 m A I f u s i n g t h e R e v e r s e P o l a r i t y A l a r m o u t p u t a d d 5 m A I f u s ...

Page 28: ... y s t e m d r a w o f 3 a m p s i n a l a r m f o r 5 m i n u t e s 0 2 5 a m p h o u r o r f o r 1 0 m i n u t e s 0 5 a m p h o u r 2 N F P A 7 2 1 9 9 3 C e n t r a l S t a t i o n a n d N F P A 7 2 1 9 9 3 L o c a l a n d P r o p r i e t a r y F i r e A l a r m S y s t e m s r e q u i r e 2 4 h o u r s o f s t a n d b y 3 N F P A 7 2 1 9 9 3 A u x i l i a r y a n d R e m o t e S t a t i o n F...

Page 29: ...c e w i t h t h e N F P A s t a n d a r d s l i s t e d b e l o w N F P A 7 2 1 9 9 3 S i g n a l i n g S y s t e m s f o r C e n t r a l S t a t i o n S e r v i c e P r o t e c t e d P r e m i s e s U n i t N O T I F I R E 9 1 1 A 9 1 1 A C D A C T o r M S 5 0 1 2 f o r c o n n e c t i o n t o a c o m p a t i b l e l i s t e d C e n t r a l S t a t i o n D A C R o r P r o t e c t e d P r e m i s ...

Page 30: ... i s n o t F M a p p r o v e d N o t e s 1 T h e M a x i m u m s t a n d b y l o a d s h a l l b e 1 2 5 m A 2 T h e S t a n d b y B a t t e r y R e q u i r e m e n t 2 4 V D C 7 A m p H o u r M a x 3 T h e 9 1 1 A w a s d i s c o n t i n u e dE f f e c t i v e 1 0 9 6 t h i s d i a g r a m i s f o r r e f e r e n c e o n l y S T D D A C T N O T E o n S T D D A C T P l a c e j u m p e r o v e r p ...

Page 31: ...han 20 in length in the same room This application using the NOTI FIRE 911AC is not FM approved NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employing a DACT This directs the control panel to transmit all trouble conditions except AC LOSS d r a o b r e h t o M C A 1 1 9 m r a l A 1 3 B T 7 d n a 6 y l l a m r o n n e p o s t c a t n o c 3 3 B T 9 d n a 8 e l b u o r T 4 3 B T 0 1 y...

Page 32: ...utral Ground Black White Green yellow yellow 1 2 TB2 TB3 TB1 RESET SILENCE MODE ALARM AC POWER TROUBLE SUPERVISORY Primary Active Secondary Active Kissoff J2 J3 Modular Cable P N MCBL 6 Secondary Phone Line Primary Phone Line 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TB TB4 TB3 d r a o b r e h t o M 2 1 0 5 S M m r a l A 1 3 B T 2 2 B T 3 3 B T 1 2 B T e l b u o r T 4 3 B T 4 2 B T 6 3 B T 3 2 B T y r o s ...

Page 33: ...ission of sprinkler supervisory or trouble conditions Note Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms 4XTMF Transmitter Module activated polarities shown Municipal Box Circuit Gamewell ModelM34 56 Local Energy Municipal Box 6 7 Note Municipal Box wiring can leave the building Technical Manuals Online http www tech man com firealarmresources com ...

Page 34: ...onnections are power limited and supervised with the exception of the reverse polarity loop Supervision of the loop is the responsibility of the receiver Fire Lite RS82 9 Remote Station Receiver UL listed Remote Trouble Remote Alarm 1 2 3 4 4XTMF Transmitter Module activated polarities shown Note Remote Alarm and Remote Trouble wiring can leave the building Technical Manuals Online http www tech m...

Page 35: ...er 2 Use transformer model ULT STK NO 1000391 listed Class 2 12 V 10 VA See Potter Electric Signal Company Bulletin 748 3 This control panel transmitter arrangement can be employed for NFPA 72 1993 Proprietary Fire Alarm Systems Notes 1 Form C Alarm contact programmed to activate on General Alarm 2 Form C Trouble contact which will automatically activate on any Trouble condition MRP 4424 Technical...

Page 36: ...n I d e l l a t s n i f i s e l u d o m l a n o i t p o V 2 1 r o f K 2 2 V 4 2 r o f K 7 4 R L E y m m u d 2 s d a e l y r e t t a b h t o b e v o m e R 3 e h t t a t i u c r i c e n o t c e n n o c s r a e l c e l b u o r t f I m e l b o r p e h t t n i o p n i p o t e m i t 4 t i u c r i c e c a l p e r r a e l c t n s e o d e l b u o r t f I d r a o b M T X 4 n o D E L w o l l e Y n o M T X 4 ...

Page 37: ...37 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 38: ...38 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 39: ...39 MRP 4424 Document 15180 Rev D 03 12 97 15180 D NOTES Technical Manuals Online http www tech man com firealarmresources com ...

Page 40: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Reviews: