Document #50580 Rev. C 8/12/97 P/N 50580:C
7
Product Features
•
Integral digital message repeater with 'primary' and 'secondary' dual-message capability
•
Standard, prerecorded message:
“May I have your attention please. May I have your attention please. The signal you have just heard
indicates a report of a fire in this building. Please proceed to the nearest exit and leave the building.
Do not reenter the building unless directed to do so by the proper authorities.”
•
Field-selectable message capability and custom message field recording capability using local microphone or
compatible audio input jack
•
Two 30 second or one 60 second custom message
•
Integral tone generators field selectable for steady, slow-whoop, high-low or chime tones
•
Multiple Master configurations allow higher wattage capability
•
Powered by:
✓
optional internal power supply and battery charger (up to 17 AH) module FC-PSM(E)
✓
host FACP
✓
external UL listed power supply such as the Fire•Lite FCPS-24F(E)
•
Optional 70.7 V
RMS
conversion module available for each amplifier
•
Piezo sounder for local trouble
•
Independent Form-C trouble relay
•
35 mA auxiliary power output for addressable control modules (when interfaced with the Fire•Lite
MS-9200(E) FACP or equivalent) and End-of-Line power supervision relays
•
Integral Dress Panel
•
Optional local playback speaker and record control functions
•
Auxiliary Audio Input for recording custom message from compatible source or playing music over the sys-
tem with prior approval of Local Authority Having Jurisdiction (LAHJ)
•
Manual Evacuate/Message Override two position switch for transmission of stored voice messages or micro-
phone interrupt
•
System LEDs (visible with cabinet door closed):
✓
Power ON (green)
✓
System Trouble (yellow)
✓
Alarm (red)
✓
Microphone Trouble (yellow)
✓
Tone Generator Trouble (yellow)
✓
Message Generator Trouble (yellow)
✓
Record (green)
•
Other System LEDs (located on modules)
✓
Ground Fault (yellow) - optional FC-PSM(E) Power Supply Module
✓
Battery Trouble (yellow) - optional FC-PSM(E) Power Supply Module
✓
AC On (green) - optional FC-PSM(E) Power Supply Module
✓
Amplifier Supervision (green) - Amplifier Module
✓
Wiring Fault/Amplifier Fail (yellow) - Amplifier Module
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com