Addressable Module Connections
Appendix D
Addressable Module Connections
When configured with an addressable FACP such as the MS-9200(E), the FIRE•COMMAND•25/50 may be trig-
gered either by the FACP main NAC output or from addressable control modules. Figure D-1 illustrates CMD1 trig-
gered by an addressable control module. The addressable control module may trigger the FIRE•COMMAND•25/50
via reverse polarity (shown) or relay contact. The FACP monitors the FIRE•COMMAND•25/50 for faults while in
the standby or alarm state by wiring a monitor module to the trouble contacts as shown in Figure D-1. Activation of
the addressable control module is controlled by the FACP. Refer to the MS-9200(E) manual for additional
information.
Notes:
1.
Auxiliary Power terminals for special application power only. Wiring must remain in the room.
2.
Supervise the wiring between the FIRE•COMMAND•25/50 Auxiliary Power output and the control module
with an EOL relay (A77-716B)
3.
EOL resistor supplied with modules.
FIGURE D-1:
Addressable Module Connections