FCPS-24F(E) Connections
46
Document #50580 Rev.C 8/12/97 P/N 50580:C
Appendix C
FCPS-24F(E) Connections
Notes:
•
Maximum FIRE•COMMAND•25/50 amplifier output is 38 watts when two amplifiers are installed due to 3.0
amps current limitation of FCPS-24F(E) output (single amplifier panel will supply 25 watts).
•
NAC 2 on the FCPS-24F(E), in addition to triggering the FIRE•COMMAND•25/50 by reverse polarity, can
support notification appliances.
•
On FIRE•COMMAND•25/50, do not jumper P10, but leave factory installed jumper in place on P7
•
This configuration must not be used when background music is selected.
FIGURE C-1:
FCPS-24F(E) Connections to FIRE•COMMAND•25/50
Trouble Relay transfer on loss of power
Command Input
(alarm polarities)
4.7K ELR
No jumper
on P10
FIRE•COMMAND•25/50
Regulated, filtered, power-limited output, 3 amps maxi-
mum- wiring is supervised by the FIRE•COMMAND•25/50
(loss of power results in transfer of Trouble Relay)
FACP ELR
Control
Input #1
FACP NAC activation causes
FCPS-24F(E) NACs 1 & 2 to activate.
FCPS-24F(E) NAC 2 triggers the
FIRE•COMMAND•25/50. Power from the
FCPS-24F(E) TB4 Terminals 7 & 8 power
the FIRE•COMMAND•25/50.
24 VDC
Common
FCPS-24F(E)
Factory installed
jumper must be in
place on P7