Notify fire department, central station, and facility personnel of test.
Slide SYSTEM TEST switch down. ------------------ All LEDs (except zone alarm) light and
indicating appliances are activated.
Release SYSTEM TEST switch. ---------------------- All zone alarm LEDs will light.
Short out each zone, one at a time. ---------------- Zone and system LEDs light. All indicating
appliances are activated.
Slide WALK TEST switch down. --------------------- Walk Test LED and system trouble activated.
Activate alarm initiating ------------------------------- Zone alarm and system LEDs light. Indicating
devices, one at a time
appliances are briefly activated then reset.
Slide WALK TEST switch up. ------------------------- Panel exits test mode and returns to normal.
Short out Zone 4 (if monitoring ---------------------- Supervisory and zone alarm LEDs light. Audible device
N.O. supervisory devices).
continues to sound until trouble condition is corrected.
Open Zone 4 (if monitoring -------------------------- Zone and system trouble LEDs light and
N.O. supervisory devices).
audible trouble device sounds.
Momentarily open all circuits, ----------------------- System and respective circuit trouble LEDs
one at a time.
light. Audible trouble device sounds.
Remove AC power and conduct SYSTEM ------ Battery terminal voltage should be at nominal rating.
TEST again. Measure battery voltage.
Notify fire department, central station, and facility personnel that test is complete.
Action
Result
O
p
e
r
a
t
i
o
n
Local Service Representative
Name:
Address:
Telephone:
1) The system alarm and zone alarm indicators will light.
2) Indicating appliances will be activated.
3) Supplementary output will be activated.
Locate alarmed zone and slide zone disable switch downward.
After correcting the alarm condition, reset the control panel by
depressing the SYSTEM RESET switch.
A trouble signal under normal operation indicates a condition
that requires immediate correction. Contact your local service
representative. The panel's audible trouble buzzer that sounds
in response to a trouble condition may be silenced by depressing
the TROUBLE SILENCE switch (the trouble LED will remain on).
Alarm Condition:
Alarm Silence:
Alarm Reset:
Trouble Condition:
CMS-4012/4024 Quick Reference Sheet
✄
✄
✄
✄
✄