background image

16

 15586 Rev E      5/14/93   P/N 15586:E

General Alarm and Trouble Module (40xxAT)- This module provides one Form-C general alarm contact
and a system trouble contact. An Auxiliary Disable switch disables the alarm contact and creates a system
trouble condition. A yellow LED indicates when the switch is in the disable position. This module is supervised
for insertion (once jumper JP4 on the main board is cut). If the 40xxAT is then removed, the  system trouble
LED will light and the panel's audible trouble device will sound.

Contacts are rated for 2.0 amps at 30 VDC and 0.5 amp at 120 VAC. For applications requiring ULC listing,
these contacts shall be derated to 2 amps at 30 VDC and 0.5 amps at 30 VAC.

To install, remove jumper JP4 on the main board. Plug the module into connector P4 through the standoff.
Secure the board to the main board using two screws provided. Note that either this module or a Transmitter
Module (40xxTM) may be plugged into P4, but not both.

Alarm

Trouble

Figure 3I:  40xxAT General Alarm and Trouble Module Connections

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for CMS-4012

Page 1: ...234567890123456789012123456789012 1234567890123456789012345678901212345678901234567890123456789012123456789012 1234567890123456789012345678901212345678901234567890123456789012123456789012 1234567890123456789012345678901212345678901234567890123456789012123456789012 1234567890123456789012345678901212345678901234567890123456789012123456789012 1234567890123456789012345678901212345678901234567890123456...

Page 2: ...p before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper instal...

Page 3: ...ional Features 7 2 0 Controls and Indicators 8 2 1 Control Switches 8 2 2 Status Indicators 9 3 0 Installation Instructions 10 3 1 General 10 3 2 Initiating Circuits 10 3 3 Output Circuits 11 3 4 Power 12 3 5 Optional Modules 13 4 0 Periodic Testing 20 4 1 Notification 20 4 2 System Test 20 4 3 Zone Test 20 4 4 Initiating Device Test 20 4 5 Supervisory Test 20 4 6 Trouble Test 21 4 7 Battery Test ...

Page 4: ...3E AC Connections 12 3F Battery and Meter Connections 13 3G Remote Zone Annunciator Installation 14 3H Zone Relay Module Connections 15 3I General Alarm and Trouble Module Connections 16 3J Transmitter Module Connections 17 3K McCulloh Type Transmitter Connection 18 3L Basic System Wiring Diagram 19 3M Battery Charger Check Procedure 24 Technical Manuals Online http www tech man com firealarmresou...

Page 5: ... Standard 864 Underwriter s Laboratories of Canada ULC listed Standard CAN ULC S527 M87 California State Fire Marshall CSFM listed CSFM File Number 7165 075 130 Bureau of Standards and Appeals listed MEA Resolution Number 578 81 SA MEA MEA MEA MEA MEA The MS 4012 4024 and CMS 4012 4024 Fire Alarm Control Panels are suitable for service under the following standards For Compatible Notification Appl...

Page 6: ...TM for Transmitter Module When received the actual module boards will be marked as MS4000 40xx followed by a one letter abbreviation and the letter B for board For instance To order a 24 volt General Alarm and Trouble Module order a 4024AT The module received will be marked MS4000 40xxAB The voltage of a particular module is inked on the bottom side of the PC board A Packaging Note Technical Manua...

Page 7: ...urrent limited float type charger for sealed batteries Battery supervision Ground fault indicator Extensive transient protection Single Form C general alarm contact Supervision of option boards Conversion of Zone 4 to a N O sprinkler supervisory Waterflow Alarm Service including two zone waterflow plates 4000 WF that mechanically lock the disable switch on waterflow zones 1 2 Optional features inc...

Page 8: ...ory condition If the LED lights it is good Walk Test switch allows one person to test all initiating an indicating devices The function of this switch is to automatically reset the panel After receiving an alarm signal the panel will sound all signaling devices for two seconds and then will reset the panel The procedure repeats every two to three seconds until the alarm condition is cleared Disabl...

Page 9: ...ights in response to a fault in the main bell circuits including an open or a short in the field wiring or connection of a non polarized indicating appliance Battery Trouble A yellow LED that annunciates fault in the battery circuit Ground Fault A yellow LED that lights when either side of the power source is shorted to the chassis Walk Test A yellow LED that lights when the Walk Test feature is a...

Page 10: ...es NOTE To employ coded manual pull stations inhibit the latching circuit for a particular zone by removing the associ ated diode in the zone circuit on the main board see Figure 3L Observe polarity when connecting polarized devices Con nect first device to the panel second device to the first device third to the second and so on Remove the End of Line resistor ELR from the terminals and install o...

Page 11: ...bility Document for compatible UL listed detectors available from Fire Lite 3 3 Output Circuits Indicating Bell Circuits Two Class B Indicating Appliance Circuits are provided as a standard feature on this panel Each circuit is capable of 1 5 amperes of signaling current Total current drawn from both circuits cannot exceed 2 5 amperes Indicating appliances must be polarized Remove ELR from each ci...

Page 12: ...pical End of Line Relay Connection Figure 3D Typical End of Line Relay Connection Smoke Detector Power Resettable power for 4 wire photoelectric and ionization smoke detectors can be obtained from terminals 19 negative and 20 positive Up to 200mA of current is available depending on the number of optional modules in the system see Appendix B Table B 2 Non resettable Power Non resettable power can ...

Page 13: ...ger output voltage use a voltmeter with a range of 0 50 VDC Connect the meter to plug P5 see Figure 3F CAUTION Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics If contact is made with sulfuric acid immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention The 4012 4024 has two module connectors P3 and P4 Fo...

Page 14: ...ncludes an audible trouble device with a trouble silence switch To make use of this remote function an LED interface board 40xxLI must be used The 40xxLI module is supervised for insertion once JP3 is removed from the main board If the 40xxLI is then removed all four zone trouble LEDs and the system trouble LED will come on and the panel s audible trouble device sounds All wiring except audible tr...

Page 15: ...JP3 on the main board Zone Alarm relays will NOT operate with JP3 installed Plug the module into connector P3 on the main board Note that either this module or the LED Interface Board 40xxLI can be plugged into P3 but not both Screw terminal connections are provided with each contact see Figure 3H The Zone Disable and Trouble Silence switches will not affect operation of the relays on the 40xxZR m...

Page 16: ... LED will light and the panel s audible trouble device will sound Contacts are rated for 2 0 amps at 30 VDC and 0 5 amp at 120 VAC For applications requiring ULC listing these contacts shall be derated to 2 amps at 30 VDC and 0 5 amps at 30 VAC To install remove jumper JP4 on the main board Plug the module into connector P4 through the standoff Secure the board to the main board using two screws p...

Page 17: ...n Trouble OUTPUT in Normal in Trouble Figure 3J 40xxTM Transmitter Module Connections Local Energy Municipal Box supervised circuit Remove jumper JP1 If box is equipped with a reset supervisory switch remove jumper between main board terminals 9 and 10 see Figure 3B Wire the switch common to terminal 9 and the N C contact to terminal 10 Remote Station Connection non supervised Terminals 3 and 4 pr...

Page 18: ...rvice under classification UUTV Potter Electric Signal Company model ATTE B The central station receiving unit must be UL listed and compatible with the transmitter The transmitter must be installed according to its installation instructions The transmitter cabinet must be mounted adjacent to the control unit with interconnecting wiring enclosed in conduit The fire alarm control unit transmitter a...

Page 19: ...vices Power limited see Section 3 4 Unfiltered unregulated 1 amp max subtract from indicating circuit power Non resettable Power up to 50 mA max Subtract from Four wire detector power Refer to Appendix D Heat Detector ManualStation SmokeDetector Plug TM or AT module in P4 and cut JP4 Plug LI or ZR module in P3 and cut JP3 Cut JP2 when ammeter is employed Cut JP4 when TM or AT module is employed Re...

Page 20: ... are activated and that the zone and system alarm LEDs light Reset the panel and repeat for each zone To check all initiating devices slide the Walk Test switch down The Walk Test LED will light and the system trouble devices will be activated In this mode the panel will reset automatically Activate an alarm initiating device and ensure that the indicating devices function Check each initiating de...

Page 21: ...d repeat the test procedure outlined in Section 4 2 Measure battery voltage while the indicating appliances are activated Reapply AC power and reset the panel Replace any battery with terminal voltage less than 85 of rating Attheconclusionoftesting returnallswitchestotheirnormal up positions Notifythefiredepartment central station and facility personnel that the test is complete 4 7 Battery Test 4...

Page 22: ...ion on Zone 4 JP5 JP6 must be installed and JP7 JP8 removed For coded output inhibit the alarm latching circuit on an initiating zone by cutting its respective diode D31 Zone 1 D33 Zone 2 D35 Zone 3 D37 Zone 4 Reset Disconnect the batteries Remove AC power from the panel Wait 30 seconds and reconnect AC power first followed by the batteries This resets the panel s built in fuses Isolate To disting...

Page 23: ...s are not the source of the problem If the batteries and transformer are known to be good have the panel repaired or replaced Problems concerning the AC power supply or the batteries are covered in Section 5 2 5 2 Component Troubleshooting Battery Test Battery Trouble Indication The batteries may be tested by conducting the procedure in Section 4 7 Transformer Test AC Power LED off Ensure that cir...

Page 24: ...determine if the panel is operating properly To read the charger output see Figure 3M Battery Charger Check Procedure If the charger output voltage does not meet specifications and the transformer is known to be good the control panel will have to be repaired or replaced Newer 4012s and 4024s contain TB3 Non resettablePowerOutput Step 1 Remove and save JP12 from the controlpanel Step 3 Using a vol...

Page 25: ... VDC 4024 perform the following calibration procedure Step 1 Adjust R5 until the voltage across the 1K resistor is 30 VDC MS 4024 or 15 VDC MS 4012 Step 2 Adjust R108 until the the Battery Trouble LED just turns on threshold point Step 3 Adjust R5 until the voltage across the resistor is 27 6 VDC MS 4024 or 13 2 VDC MS 4012 Step 4 Remove the meter and resistor and reconnect the batteries to Plug P...

Page 26: ... 1 VDC 4024 2 VDC Indicating device operating range 4012 9 15 VDC 4024 18 31 VDC Total current to all external devices 2 5 amps Maximum signaling current per circuit 1 5 amps End of line resistor 10k 1 4 watt A 3 Alarm Relay Dry Form C contacts rated for 2 0 amps 30 VDC resistive 0 5 amps 30 VAC resistive A 4 AC Power 120 VAC 60 Hz 1 2 amps Wire size 14 AWG with 600V insulation A 5 Transmitter Mod...

Page 27: ...s 30 VAC resistive A 8 Four wire Smoke Detector Power Up to 200mA of current can be provided to four wire smoke detectors Note If using Non Resettable power Terminal Block 3 the combined current shall be limited to 50 mA A 9 Unregulated Unfiltered Power Total DC current available for powering external devices is 1 0 amp subtracted from indicating appliance power A 10 Non resettable Power DC curren...

Page 28: ...ne Relays d Add lines a b c for subtotal Basic Control Panel 79 2 mA If using a Zone Relay Module 4012ZR add 8 mA or 4024ZR add 16 mA If using a Transmitter Module 40xxTM add 5 mA If using the Reverse Polarity Alarm output add 10 mA If using the Reverse Polarity Trouble output add 10 mA If using a Remote Zone Annunciator RZA 4 add 8 mA Unregulated Auxiliary power draw from Terminals 18 19 AC Power...

Page 29: ...ere amps X hours Enter 0 3 for 5 minutes in alarm or 0 6 for 10 minutes in alarm Add Standby and Alarm amp hours Select a battery with a greater amp hour rating Table 3 Ampere Hour Calculations Standby amp hours Alarm amp hours Total amp hours needed 340 mA 340 mA 340 mA 340 mA 340 mA Notes NFPA 72 Local and 72 Proprietary Protected Premises systems require 24 hours of standby NFPA 72 Auxiliary an...

Page 30: ...de by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that Fire Lite is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience transportation damage misuse abuse ac...

Page 31: ...ne at a time light Audible trouble device sounds Remove AC power and conduct SYSTEM Battery terminal voltage should be at nominal rating TEST again Measure battery voltage Notify fire department central station and facility personnel that test is complete O p e r a t i o n Local Service Representative Name Address Telephone 1 The system alarm and zone alarm indicators will light 2 Indicating appli...

Page 32: ...e at a time light Audible trouble device sounds Remove AC power and conduct SYSTEM Battery terminal voltage should be at nominal rating TEST again Measure battery voltage Notify fire department central station and facility personnel that test is complete Action Result O p e r a t i o n Local Service Representative Name Address Telephone 1 The system alarm and zone alarm indicators will light 2 Ind...

Reviews: