background image

Rotar Plus 20-25 Easytronic - Cod.197AA2702 - Edition 00 01/2004

GB

10

9

MAINTENANCE

8

BEFORE MAINTAINING THE MACHINE ALWAYS PERFORM THE FOLLOWING

•

Switch off the motor by means of the switch on the control panel.

•

Power the machine off by means of the wall outer switch (do not press the emergency stop button).

•

Close the line cock.

•

Make sure that no compressed air is inside the oil separator tank by turning the cock anticlockwise and bleed all air off.

•

Before removing any protections, double check that wall-mounted switch has been turned to 0.

 AFTER THE FIRST 100 HOURS

1) 

Check the oil level 

(see next paragraph): top up with the same type of oil if

necessary.

2) 

Check for proper screw tightening

: in particular the power electric connection

screws.

3) 

Visually check

 that all fittings seal properly.

4) 

Check 

room temperature

EVERY 500 HOURS

Check the oil level (fig.7)

Always blow off air from the oil separator tank before topping up. Slowly unscrew

the cock A until all air comes out and then screw it again.

The max. level is reached when the oil touches the filler.

Check level at oil light (B).

The  amount  of  oil  necessary  for  topping  up  from  the  minimum  level  to  the

maximum level is about 1.5 lt.

EVERY 1000 HOURS

Clean  the  air  filter

  thoroughly  (fig.8).  Blow  filter  with  compressed  air  from

inside out.

Hold the filter against the light and look for any tears. Always replace a torn

filter. Install filter cartridge and cover accurately. If badly positioned, they would let

dust into the compression unit.

Replace the air filter when you have cleaned it four times.

Clean the radiators

The radiator is highly efficient with a limited clogging degree. However, in case

of abnormal overheating or at least once a year, a check for filter clogging  is recommended.

To clean the radiators, proceed as follows:

•

remove the rear and upper panels of the pressurized chamber;

•

position a protection plastic sheet under the radiator unit;

•

spray (spray gun + solvent) from the outside towards the inside;

•

check for proper air flow through the radiators.

AFTER THE FIRST 1000 HOURS, EVERY 3000 HOURS AFTERWARDS

Change oil (fig.7)

Change oil every 3000 working hours  when compressor is hot – over 70 °C.

Drain pressure from the oil separator tank through cock (A).

• Connect the supplied hose to cock (C).

• Unscrew filler cap, open ball cock (C) and drain all oil into a container. When finished,

close the cock and remove the hose.

• Fill fresh oil through filler plug (D)  (a full charge is 6 liters).

• Close the plug.

• Power on machine.

• Start machine and let is run for 5 minutes, then stop it.

• Drain all air.

• Allow 3 minutes and check oil level. Top up if needed.

When you change oil, you can change to a different type of lubricant (see table).

SHELL CORENA D

AGIP  DICREA 46

IP VERETUM OIL 46

BP ENERGOL HLP 46

MOBIL  D.T.E. MEDIUM

CASTROL  AIRCOL MR46

ESSO UNIVIS 46

FINA EOLAN R046

Remember to use the same oil for future top-ups - 

Never mix 

different  types of oil

Change oil filter (fig.9)

Change oil filter  EVERY TIME YOU CHANGE OIL; depressurize tank before proceeding.

Always smear filter edge and filter seal lightly with oil before screwing filter into place by hand.

7

Summary of Contents for ROTAR PLUS 20

Page 1: ...facturers f Products can be delivered to the Manufacturer for servicing purposes only after prior authorization by the very Manufacturer The Manufacturer shall decide at their discretion whether authorization can be granted or require an Authorized Service Center to take on servicing In any case products shall be delivered free of any charge and will be returned to the Customer on ex factory basis...

Page 2: ...and maintenance carried out so far SYMBOLS USED IN THE MANUAL Some symbols are used to highlight danger situations give recommendations or information These symbols are usually positioned next to the text a figure or at the top of a page in this case they refer to all subjects dealt with in that page Carefully read symbol meaning below CAUTION Important description on service dangerous situation s...

Page 3: ...the maintenance schedule specified in the user s guide WHAT NOT TO DO Do not touch inner parts and pipes as they are very hot during compressor operation and stay hot for a certain time after compressor stop Do not position inflammable or nylon objects or cloths close to and onto the compressor Do not move the compressor when the tank is under pressure Do not operate the compressor if the power ca...

Page 4: ...llection centres for disposal PLACEMENT AND INSTALLATION fig 2 Upon installation make sure that the chosen place is in compliance with all prevailing national safety standards and meets the following requirements low percentage of dust suspended in air shop must be suitably sized and well ventilated so that room tem perature never exceeds 40 C when the compressor is working If this is not the case...

Page 5: ...24 50 60 Electrical box protection class IP 54 54 54 54 54 54 Motor insulation class F F F F F F Full load current A 31 31 31 36 36 36 Starting load A 70 75 73 98 104 107 Max Start up per hour n 10 10 10 10 10 10 Ambient limit temperature C 50 50 50 50 50 50 Noise level at 1 m Cagi pneurop dB A 70 70 70 71 71 70 3URWHFWLRQ GHYLFHV Max compressor temperature C 110 110 110 110 110 110 Min oil temper...

Page 6: ...led loadless cycle starts blinking LOADLESS message is displayed once loadless cycle is over compressor stops and off message is displayed 8 Emergency stop switch to stop compressor only in case of actual need 9 Functioning diagram maintenance operations WORKING TIMES Automatic mode The compressor operation is controlled by the pressure transducer which stops the machine when the max pressure valu...

Page 7: ...ission using RS485 and automatically disable transmission on RS232 12 Pressure sensor service password enables the 4 20 mA input to which the pressure sensor is connected With this parameter activated the pressure measurement is displayed To display machine operation time press the key the display will revert to the pressure measurement automatically after 20 seconds Enabling this parameter the ex...

Page 8: ...t be silenced by the service technician who when carrying out maintenance operations will select the item Pre alarm hours from the menu and reset the value as described under the heading Modifiable parameters point 1 9 Separator pressure switch Alarm trips in the event of the separator pressure switch contact opening The compressor locks up To silence the alarm first reset the separator pressure s...

Page 9: ...l mixture which ensures the seal and the lubrication of the moving parts of the compressor The air oil mixture returns to the tank 6 where the air is pre separated through spinning and is finally separated from the oil by the oil separator filter 13 From the tank 6 only air comes out which reaches the radiator 11 through the tube 15 and the mains through the cut off cock 16 FIRST START UP Before s...

Page 10: ...ey would let dust into the compression unit Replace the air filter when you have cleaned it four times Clean the radiators The radiator is highly efficient with a limited clogging degree However in case of abnormal overheating or at least once a year a check for filter clogging is recommended To clean the radiators proceed as follows remove the rear and upper panels of the pressurized chamber posi...

Page 11: ...ion rules in force EVERY 2000 OPERATING HOURS Check drive belt tension Fig 12 Use a frequency tester to carry out this check Proceed as follows Move tester microphone closer to the belt about at mid length and hit the belt with a wrench Read value on tester Stretch or slacken the belt if the value is different from values indicated in the table Higher value slacken Lower value stretch To adjust pr...

Page 12: ... Change the drive belt as follows fig 12 2 Tighten the screw 1 turning it clockwise with a hexagon head wrench until you feel that the belt is slackening and comes off easily 3 Install the new belt and set the screw 1 back to its original position turn clockwise Leave belt slightly slack Check frequency value as described on page 11 1 Test 12 ...

Page 13: ...ignal Oil separator filter clogged Min pressure valve does not clo se perfectly Voltage too low Shop too cold Leakage from tubes Leakage from front compressor flange Remedy Check voltage press Reset and start once again Check motor absorption and check relay settings If absorption is OK press Reset and start once again Check oil drainage tube and non return valve Check oil level and drain some if ...

Page 14: ... 500 mA 500V KM1 Line contactor 18 5 kW 11 kW 18 5 kW 11 kW KM2 Delta contactor 18 5 kW 11 kW 18 5 kW 11 kW KM3 Star contactor 15 kW 7 5 kW 15 kW 7 5 kW FR Thermal relay 28 40 17 22 28 40 20 25 YV Solenoid valve SP1 Minimum pressure switch SP2 Pressure switch for oil separator filter SP3 Pressure switch for air filter BP Pressure transducer 0 16 bar D Electronic controller ST Thermal feeler for el...

Reviews: