REV. A
Jan/14/22

MODELS

Fire Protection Air Compressor

LL BP MANUAL

S244B

S910B

S600B

S244P

Summary of Contents for S244B

Page 1: ...REV A Jan 14 22 MODELS Fire Protection Air Compressor LL BP MANUAL S244B S910B S600B S244P...

Page 2: ......

Page 3: ...MAINTENANCE 8 VALVES AND SWITCHES 8 S244 PARTS DIAGRAM 9 S600 PARTS DIAGRAM 10 S910 PARTS DIAGRAM 11 TROUBLESHOOTING 12 5 DIGITAL AMD 3 PUMP 2 AIR FILTER 4 DISCHARGE TUBE S600 S910 HOSE S244 1 ELECTRI...

Page 4: ...tion and testing purposes WARNING Refer to the authority having jurisdiction regarding hard wiring requirements AVAILABLE ACCESSORIES ACCESSORY PART NUMBER FLOOR MOUNTING KIT INSTALL S28 1 2 X 30 STAI...

Page 5: ...t direct the air stream at body Drain tank air weekly to decrease risk of bursting NOTE Per UL 1450 46 17 C Aire recommends a maximum of 70 duty cycle for its compressors INSTALLATION SELECTING A LOCA...

Page 6: ...it u 1 5 Install air lter assembly INLET AND DISCHARGE PIPING CAUTION Do not operate unit without inlet air ltration If the air is dirty pipe the lter to a source of clean air Do not install piping w...

Page 7: ...nal The insulated wire with a green outer surface and yellow stripes is the grounding wire NOTE The installation electric motor wiring and all electrical controls must be in accordance with NFPA 70 19...

Page 8: ...the arrow buttons can perform a 1 1 change to the set value The compressor will not run in this mode If the compressor remains in this mode for 60 seconds with no adjustments it will automatically re...

Page 9: ...TTTINGS LOCKED C P M C To lock the settings hold the M and the P simultaneously for 3 seconds until the SETTINGS LOCKED light is illuminated RUN MAX MIN PSI kPa BAR 24HRS 7 DAYS STARTS SETTTINGS LOCKE...

Page 10: ...STALLATION DIAGRAMS NOTE Baseplate units are factory set to 10 20PSI No AMD Permitted Digital AMD eliminates the need for air pressure maintenance device Check valve required between compressor and sy...

Page 11: ...d on all units Pressure relief valves aid in preventing system failures by relieving system pressure when compressed air reaches a determined level Pressure relief valves are PRESET by the manufacture...

Page 12: ...Motor MR C168A 3 Belt Guard BG 03 4 Belt BT A 51 5 Solenoid 115V EL SV3V1 06 230V EL SV3V1 06 220 6 Safety Relief Valve BR SV 25 70 7 Digital AMD EL D0911 8 Pump PM F 65A 9 Discharge Hose DT 0504 10...

Page 13: ...Motor MR C182A 3 Belt Guard BG 03 4 Belt BT A 59 5 Solenoid 115V EL SV3V1 06 230V EL SV3V1 06 220 6 Discharge Tube DT 5050 REF 7 Digital AMD EL D0911 8 Pump PM F25A 9 Check Valve BR VCV33U 10 Manifold...

Page 14: ...Belt Guard BG 03 4 Belt BT A 59 5 Solenoid EL SV3V1 06 220 6 Discharge Tube DT 5050 REF 7 Digital AMD EL D0911 8 Pump PM F36A 9 Check Valve BR VCV33U 10 Manifold BP 3M 11 Safety Relief Valve BR SV 25...

Page 15: ...r room Install compressor above system valve Leaks Find and repair leaks Overheating Compressor System too large Decrease system pressure Upsize compressor Wrong size fuse or breaker Check fuse breake...

Page 16: ...back of this Owner s Manual Keep Installation Checklist for future reference 2 Ensure the compressor is sized properly for the application the compressor should run no more than 6 out of 10 minutes on...

Page 17: ...380 West 1st Street Dresser WI 54009 800 762 2247 651 462 3440 www cairecompressors com...

Reviews: