User’s Manual 7M
51
Address
Contents
Data
Ind
Values
min
max
P. Level
ENERGY
40401
Active Tariff
T1
0
Tariff input
0
6
1
1..4
Tariff 1..4
5..6
Tariff 5..6
40402
Common Energy Counter
Exponent
T2
–3
4
2
40403 40418 Reserved
40419
Total Energy Calculation
T1
0
Evaluation of the sum
of phases
0
1
2
1
Evaluation of individual
phases
40420
Reactive power calculation
T1
0
Standard calculation
(Q^2=S^2-P^2)
0
1
2
1
Delayed Current method
NON-RESETABLE COUNTERS
40421
Energy Counter n1 Parameter
T1
0
No Parameter
0
95
2
1
Active Power
2
Reactive pover
3
Apparent Power
5
Active Power Phase 1
6
Reactive pover Phase 1
7
Apparent Power Phase 1
9
Active Power Phase 2
10
Reactive pover Phase 2
11
Apparent Power Phase 2
13
Active Power Phase 3
14
Reactive pover Phase 3
15
Apparent Power Phase 3
33
Active Power
individual phases
34
Reactive Power
individual phases
35
Apparent Power
individual phases
40422
Energy Counter n1 Configuration
T1
Bit-0
Quadrant I Enabled
0
63
2
Bit-1
Quadrant II Enabled
Bit-2
Quadrant III Enabled
Bit-3
Quadrant IIII Enabled
Bit-4
Absolute Value
Bit-5
Invert Value
40423
Energy Counter n1 Exponent
T2
–3
6
2
40424
Energy Counter n1 Tarif Selector
T1
Bit-0
Tarif 1 Enabled
0
63
2
Bit-1
Tarif 2 Enabled
Bit-2
Tarif 3 Enabled
Bit-3
Tarif 4 Enabled
Bit-4
Tarif 5 Enabled
Bit-5
Tarif 6 Enabled
40425
Energy Counter n2 Parameter
T1
see Energy Counter
n1 Parameter
0
95
2