background image

Operating instructions 

Flow monitors

SI5002 

SI5003 

SI0521

704318 / 03

 

08 / 2012

UK

Summary of Contents for Efector 300 SI5002

Page 1: ...Operating instructions Flow monitors SI5002 SI5003 SI0521 704318 03 08 2012 UK...

Page 2: ...trical connection 7 5 Operating and display elements 7 6 Set up and settings for water 8 6 1 High flow adjustment optional 8 6 2 Change switch point SP1 9 6 3 Change switch point SP2 9 7 Additional se...

Page 3: ...tended use may lead to malfunctions of the unit or to un wanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit must only be ca...

Page 4: ...to normally closed 7 2 It then applies output open if flow SP1 SP2 If the flow speed increases the switching status changes when the switch point is reached If the flow speed falls again the switching...

Page 5: ...ation location General The sensor tip is to be completely sur rounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Page 6: ...ces of interference 3 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the threads...

Page 7: ...unit as follows A SI5002 SI0521 positive switching B SI5003 negative switching Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black 5 Operating and display elements 1 Operation disp...

Page 8: ...nts to your application if necessary 6 2 6 3 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 1 Adapt the switch points to your applica...

Page 9: ...e with the newly set value 7 Additional settings optional 7 1 Low flow adjustment If the unit is used in media other than water you should additionally adapt the unit to the minimum flow Note The foll...

Page 10: ...locked electronically to prevent unintentional settings Press both setting pushbuttons simultaneously for at least 10 s in the operating mode The indication goes out the unit locks or unlocks On deli...

Page 11: ...tching output S1 The operating indicator and 5 red LEDs on the left hand light alternately If the short circuit has been rectified the unit im mediately passes into the normal operating state The curr...

Page 12: ...12 11 Scale drawing and technical data www ifm com More information at www ifm com...

Page 13: ...13 UK...

Reviews: