User’s Manual 7M
47
Address
Contents
Data
Ind
Values / Dependencies
Input Registers
AVERAGE MEASUREMENTS
35772
Power Angle Total (atan2(Pt,Qt))
T17
35773
j1 (angle between U1 and I1)
T17
35774
j2 (angle between U2 and I2)
T17
35775
j3 (angle between U3 and I3)
T17
35781
Internal Temperature
T17
THD HARMONIC DATA
35782
U1 THD%
T16
35783
U2 THD%
T16
35784
U3 THD%
T16
35785
U12 THD%
T16
35786
U23 THD%
T16
35787
U31 THD%
T16
35788
I1 THD%
T16
35789
I2 THD%
T16
35790
I3 THD%
T16
RAM logger
36000
Measurement parameter
T1
See OutTypes
36001
Time interval
T1
minuteas
36002
Number of valid results
T1
36003
Time stamp of last result
T2
minutes since midnight (<0 if no time)
36004
36131
Logger table (newest to oldest)
T17
Normalised values
SETTINGS
SYSTEM COMMANDS
40001
40002
User Password (L1, L2)
T_Str4
A…Z
Password to attempt user
access level upgrade
0
40003
40005
Factory Password (FAC)
T_Str6
A…Z
Password to attempt factory
access level upgrade
0
40006
40007
Lavel 1 - User password
T_Str4
A…Z
1
40008
40009
Lavel 2 - User password
T_Str4
A…Z
2
40010
Active Acces Level
T1
0
Full protection
0 0 0
1
Access up to level 1 user password
2
Access up to level 2 user password
3
Access up to level 2 (backup pass.)
4
Factory access level
40011
Manual password activation
T1
1
Lock instrument
0
40012
Operator Command Register
T1
1
Save Settings
1 5 1
2
Abort Settings
3
Restart Instrument
40014
Reset command register 2
T1
Bit-0
Reset alarm ouptut relay 1
1
Bit-1
Reset alarm ouptut relay 2
Bit-8
Reset alarm ouptut IR
40015
IR external relay command action
0
Off
0 1 0