Quadnet Power Supply Unit Installation Manual
15
Address Select Links
Each PSU connected to the same control panel must be given a unique address.
Addresses are set using the address select links on the Quadnet PSU Charge Controller Unit, fitting link
jumpers in the appropriate positions as follows:
ADDRESS
0
1
2
3
4
LINK JUMPERS
For normal Quadnet systems where only one PSU is used with the panel, the PSU’s address must
be set to 0 or 1.
If connecting secondary PSUs
to the Quadnet system the main PSU should be address 1 and up to 3
more PSUs may be connected (addressed in sequence).
Note that if the Quadnet PSU is used as an additional external PSU for a Duonet control panel, the
internal PSU within Duonet already has address 1. Therefore the external PSU addresses should
start at 2 and continue in sequence up to address 4.