 Quadnet Power Supply Unit Installation Manual 

  

 

 

 

 

9

Topology & Cabling 

 

All system wiring should be installed to comply with BS 5839: Pt 1: 2002: Amendment 2: 2008 and BS 7671 
(wiring regulations) and any other standards relevant to the area or type of installation. A cable complying 
with  the  BS  5839:  Pt  1:  2002  Category  1  (cables  required  to  operate  for  prolonged  periods  during  fire 
conditions)  is  required.  This  must  be  a  2-core  1.5mm

2

  screened  fire  resistant  cable  (ie.  MICC,  FP200, 

Firetuff,  Firecell,  Lifeline  or  equivalent).    Ventcroft  No-Burn  multicore  cable  was  utilised  during  the  LPCB 
approval testing. 
 
If connected to the Quadnet control panel, the Power Supply Unit requires both a data connection and dual 
power connections. Thus, one x 2 core 1.5 mm

2

 screened fire resistant cable must be installed between the 

PSU  and  the  control  panel  for  data  connection,  and  2  x  1.5  mm

2

  screened  fire  resistant  cable  must  be 

installed between the PSU and the control panel for 24V DC power connections if each cable is no longer 
than 6.3m (use 2.5 mm

2

 for 24V DC power cables up to a maximum of 9.5m). 

 
In order to protect against possible data corruption it is important to ensure the following points are adhered 
to: 
 

1.  The data and power cables must have the 

screen/earth connected at the control panel and 

at the Power Supply Unit

 using the terminals provided. 

 
2. 

Do  not  use  a  4-core  cable

  to  save  the  installation  of  two  2-core  cables.  It  is  essential  that 

individual 2-core cables are used. 

 

When fitting the mains, power and signal cables to the Power Supply Unit equipment

 

and before attaching 

the connectors, slide the ferrite sleeve over the cable so that it butts up against the Power Supply Unit case. 
Fit the tywrap around the cable under the ferrite sleeve to lock the ferrite into position on the cable. 

 

 
Cable Specification 
 

 

For DC Power and Communications between PSU and Control Panel: 

 
 

Max Capacitance Core to Screen ................................................... 180pF / m 

 
 

Max Capacitance Core to Core....................................................... 100pF / m 

 
 

Max Inductance ............................................................................... 1.0mH / km 

 
 

Max Resistance Two Core Screened 1.5mm² ................................ 12.1

 / km 

 
 

Fire Proof ........................................................................................ BS5839: Pt1: 2002 Category 1 

 

 

 

Example .......................................................................................... Datwyler 8700  

Summary of Contents for Quadnet PSU V3

Page 1: ...26 0853 Issue 5 Fire Detection Alarm System Power Supply Unit V3 Power Supply Unit Installation Manual TO BE RETAINED BY THE COMMISSIONING ENGINEER...

Page 2: ...of such contents Due to the complexity and inherent importance of a life risk type system training on this equipment is essential and commissioning should only be carried out by competent persons Fike...

Page 3: ...tallation 7 Physical Dimensions 8 Power Supply Assembly 8 Topology and Cabling 9 Cable Specification 9 Mains Supply Batteries 10 PSU Termination Schematic 11 PSU Terminals 12 Address Select Links 15 E...

Page 4: ...ganisation Anti Static Handling Guidelines Immediately prior to handling any PCBs or other static sensitive devices it is essential to ensure that a personal connection to earth is made with an anti s...

Page 5: ...ed intelligence signifies that the signal processing is spread throughout the system in order that the decisions about fires and faults are taken within the detector itself The detector is capable of...

Page 6: ...PSU Earlier models differ slightly The power supply is normally supplied disassembled to make first fix easier If the panel is already assembled it must be disassembled in order to fix the backbox to...

Page 7: ...ting At least four of the five mounting holes should be used to secure the cabinet to a solid wall using suitable screws of at least 50mm in length A gap of at least 50mm should be left between this e...

Page 8: ...Quadnet Power Supply Unit Installation Manual 8 Physical Dimensions Power Supply Assembly This is the reverse of the disassembly process above 50mm 50mm 420mm 420mm FLUSH MOUNT HOLE IN WALL...

Page 9: ...ontrol panel for 24V DC power connections if each cable is no longer than 6 3m use 2 5 mm 2 for 24V DC power cables up to a maximum of 9 5m In order to protect against possible data corruption it is i...

Page 10: ...acity batteries on this system larger batteries will not fully charge in the time allowed and smaller ones will be overcharged and the service life will be reduced Using different capacity or type of...

Page 11: ...Quadnet Power Supply Unit Installation Manual 11 PSU Termination Schematic NOTE The diagram above shows a V3 PSU Earlier models differ slightly...

Page 12: ...elay NO NC COM The Fault relay is a single pole change over volt free relay contact The relay contacts are rated at 30V DC 1A max All inductive loads should be diode protected to prevent back EMF Howe...

Page 13: ...r to V3 backplane PCB Issue 3 do not have twin power connections for an external PSU or the facility for monitoring comms with an external PSU so it is recommended that no external PSU is used with th...

Page 14: ...Description A Serial Data connection A B Serial Data connection B SCRN Cable Screen connection PSE COMMS A B SCRN The Secondary PSU must be installed adjacent to the main Power Supply unit The PSE CO...

Page 15: ...RS For normal Quadnet systems where only one PSU is used with the panel the PSU s address must be set to 0 or 1 If connecting secondary PSUs to the Quadnet system the main PSU should be address 1 and...

Page 16: ...cated on the Charge Controller Unit Fuse No Label Fuse Type Breaking Capacity Max Rated Voltage FUSE1 Input from SMPS 10A T Glass 100A 250VAC FUSE2 Battery 10A T Glass 100A 250VAC FUSE3 Mains Input Li...

Page 17: ...e installer needs to provide a set of As Wired drawings and proof of cable continuity and insulation test readings etc to enable commissioning to proceed This information is essential for commissionin...

Page 18: ...ot followed Battery Data Make a clear note by labelling of the batteries of the installation date and the battery voltage The battery voltage should be taken for each battery with the 230V AC mains su...

Page 19: ...Charging Voltage Current Details Ripple and noise 2 x 17Ah 12V sealed lead acid batteries 230V AC nominal 31V 19V 0 5R max internal resistance 350mA min output current 5 5A max output current 27 3V 2...

Page 20: ...a Power 1 Power 2 ve to ve with temp short circuit applied ve to Earth with temp short circuit applied ve to Earth with temp short circuit applied A reading of approximately 1 ohm per 100 metres of 1...

Page 21: ...Quadnet Power Supply Unit Installation Manual 21 Your Notes...

Page 22: ...Quadnet Power Supply Unit Installation Manual 22 Your Notes...

Page 23: ...Quadnet Power Supply Unit Installation Manual 23 Your Notes...

Page 24: ...to the appropriate terminals at both ends For PSU connections to control panels install two power connection cables and one data connection cable Leave a copy of the User Instructions by the control p...

Reviews: