5.0
BATTERY LIFE
The device is shipped with only a partial charge; therefore, you’ll need to fully
charge the battery before you begin testing. One full charge typically takes about
1.5 hours to complete and will provide roughly 22 hours of use.
IMPORANT: The device will notify you when the battery is at 20%, at which time you’ll want to plug it in to charge
and preserve battery life. While you will be able to continue testing even when the battery falls to 20%, low battery
notifications will persist every 10 seconds until the unit is plugged in, which means it will interrupt your work.
The battery warning message can be cleared by turning the unit off, but the message will remain if you turn the unit
on again without charging. Remember that battery charge is displayed on initial power up, and you can check it
periodically by using Option 7 (Chk Batt Chrg) to keep track of usage.
6.0
CONTROLS/INTERFACE
On initial power up, the battery charge will display for three (3) seconds; this will help you gauge whether you can
complete all tests on the current charge. Next, the panel will display “Fike Analyzer Select Tool Use.” Once you see
this message, press and release the SELECT button to view the main menu.
Figure 6.0-1 Output Analyzer Controls and Interface
Jumper Port
-
75 Ω resistor = Supervisory current test (EPC only).
-
10 Ω resistor = Simulates max field wiring resistance (EPC only).
-
0 Ω shunt = Max current test (EPC, IRM, ARM).
USB C Port
- Battery charging
EPC or IRM/ARM Cable Port
-
Connect EPC test cable or IRM/ARM test
cable.
Enter Button
- Activates displayed option.
Select Button
- Scrolls through menu options
Activate Button
- Simulates 4-20mA sensor activation.
- Used for EPC testing only.
1 2 3 4
1
6
5
Jumper
Cable
Charge
Battery @ 20%
Pwr off and CHRG