FS-8700-41 Simplex 4100 Driver Manual
Page 27 of 48
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Appendix A.4.9.
Read Anal og Psuedo Point s
Use the Sim4100_func = 'value' to read the values from the analog pseudo points. Refer to Appendix C.4.2 for a list of the analog pseudo points.
// Analog Psuedo points
// Map Descriptor
Map_Descriptor_Name
, Data_Array_Name
, Data_Array_Offset
, Function
, Node_Name
, Sim4100_Func
, Sim4100_Card
, Sim4100_Point
, Sim4100_Sub
, Protocol
, Length
# Fire Alarms
, DA_C_144
, 0
, Rdbc
, Simplex_01
, value
, 144
, 0
, 0
, sim4100 , 1
# Supervisory Alarms
, DA_C_144
, 1
, Rdbc
, Simplex_01
, value
, 144
, 1
, 0
, sim4100 , 1
# Troubles
, DA_C_144
, 2
, Rdbc
, Simplex_01
, value
, 144
, 2
, 0
, sim4100 , 1
Excessively Dirty Sensors , DA_C_144
, 3
, Rdbc
, Simplex_01
, value
, 144
, 115
, 0
, sim4100 , 1
Dirty Sensors
, DA_C_144
, 4
, Rdbc
, Simplex_01
, value
, 144
, 116
, 0
, sim4100 , 1
Almost Dirty Sensors
, DA_C_144
, 5
, Rdbc
, Simplex_01
, value
, 144
, 117
, 0
, sim4100 , 1