FS-8700-41 Simplex 4100 Driver Manual
Page 18 of 48
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Appendix A.2.1.
Table of Attribut es recognised by the D river
The following table reports the attributes recognized by the driver. This list may be extended by changing the configuration.
Refer to Appendix A.3 for more information. If, for example, the attribute ‘ENABLED STATE’ is recognized then the state of
this attribute will be stored at array location 6.
Attribute
Array
Position
Method
Not Defined
0
1
PRIMARY STATUS
1
1
PHYSICAL STATE
2
1
RAW STATE
3
1
ACTIVE STATE
4
1
ARMED STATE
5
1
ENABLED STATE
6
1
UNVERIFIED
7
2
CURRENT DEVICE
8
1
DEVICE
9
1
TEST STATE
10
1
PRESENT SENSITIVITY SELECTED= 11
2
PRESENT SENSITIVITY SELECTED = 11
2
AVERAGE VALUE =
14
3
AVERAGE VALUE=
14
3
AVERAGE =
14
2
AVERAGE=
14
2
AVERAGE
14
2
VALUE =
17
2
VALUE=
17
2
PEAK=
20
2
PEAK =
20
2
TROUBLE THRESHOLD
23
1
OUTPUT STATE
24
1
OUTPUT STATUS
25
1
DETECTOR SOUNDER
26
1
Attribute
Array
Position
Method
ALARM TEMPERATURE SELECTED=
27
2
DETECTOR RELAY
30
1
TOTAL NUMBER OF TROUBLES 31
2
NODE MISSING
32
1
VERSION CONTROL
33
1
NODE INITIALIZATION IN PROGRESS 34
1
SIMPLEX SERVICE MODE
35
1
EARTH GROUND
36
1
AC POWER
37
1
BATTERY LOW/DISCHARGED 38
1
BATTERY CHARGE
39
1
SYSTEM PSEUDO STATUS
40
1
NETWORK CARD STATUS
41
1
CARD TROUBLE STATUS
42
1
MISCELLANEOUS STATUS
43
1
RELAY STATUS
44
1
PRIORITY
45
2
CONTROL STATUS
46
1
CURRENT (AMPS)
47
2
CARD MISSING/FAILED
48
1
CORRECT CARD
49
1
RS-232 Interface PORT A
40
1
RS-232 Interface PORT B
41
1
2120/RS-232 PORT Broadcast Fail 42
1
CARD MISSING/FAILED
43
1