3.4
Connecting the FieldServer to the MIM (Multi -Interface Module)
The RS-232 port of the FieldServer connects to the P5 (RJ11) RS-232 port of the MIM board.
3.4.1
Connection Notes
The Peripherals menu of the Fike Panel needs to be updated:
Hit ‘ESC’ until “Top Level Menu” is on the screen
Hit ‘F1’ for “Config”
Hit ‘F6’ for “Menu 2”
Hit ‘F6’ for “Menu 3”
Hit ‘F1’ for “Periph”
Hit ‘F1’ for “Device”
Choose address of MIM
Set “Type” to “Computer”
Set “Supervise” to “No”