FS-8700-48 Fike Cheetah Manual
Page 31 of 36
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
The event codes are defined in the table below.
# Description
Notes
0 no record
-
1 aux power unconfig auxiliary power module present but unconfigured.
2 aux power corrected auxiliary power module replaced after being missing.
3 aux power missing auxiliary power module not present but configured.
4 ac1 power restored ac for main board input restored.
5 ac1 power trouble
ac for main board input missing/brownout.
6 ac2 power restored ac for power module input restored.
7 ac2 power trouble
ac for power module input missing/brownout.
8 batttery1 restored
battery for main board input restored.
9 batttery1 trouble
battery for main board input missing.
10 battery2 restored
battery for power module input restored.
11 battery2 trouble
battery for power module input missing.
12 aud1 trb restored
audible #1 restored.
13 aud1 open trouble audible #1 open circuit.
14 aud1 short trouble
audible #1 short circuit.
15 aud2 trb restored
audible #2 restored.
16 aud2 open trouble audible #2 open circuit.
17 aud2 short trouble
audible #2 short circuit.
18 gnd fault restored
ground fault trouble restored to normal.
19 gnd fault present
ground fault present.
20 device present
addr device trouble: device returns canceling missing trouble
21 device missing
addr device trouble: device was polled but not found
22 commun restored addr device trouble: communication to device has returned to normal
23 bad communication addr device trouble: communication to device has errors (parity checksum etc.)
24 restored multiple
addr device trouble: multiple devices trouble has cleared
25 multiple devices
addr device trouble: multiple devices detected at this address
26 restored device kind addr device trouble: correct kind of device has been restored to this address
27 wrong device kind
addr device trouble: wrong kind of devices has been found
28 contaminated device addr device trouble: analog device is contaminated
29 loop module restored loop mod missing trouble has cleared
30 loop module missing loop module not in place but there are configured devices on the loops.
31 config menu accessed trouble stored when the configuration menu has been entered
32 factory initialized
history stored when a factory initialization has been invoked
33 uart failure
history stored when the uart has been corrupted by esd and then re-initialized.
34 uart restored
history stored when preceding trouble has cleared.
35 system reset
complete reset including power-down of loops for ten seconds.
36 trouble restored
trouble function input restore.
37 trouble input active
trouble function input present.
38 process restored
process control function input restored.
39 process input active
process control function input present.
40 supervisory restored supervisory function input restore.
41 supervisory active
supervisory function input present.