64
WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM
WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM
Air Conditioning Basics
The Evaporator, Condenser, Restrictor (Throttling
valve) and Compressor are the four basic components
of an air conditioner. Following one pound of refriger-
ant through the system shows the function of each com-
ponent.
Subcooled liquid refrigerant at high pressure enters
the restrictor and is throttled to saturated refrigerant at
a lower pressure. The restrictor can be of either a fixed
or TXV/EXV type. The fixed type must be charged to
a target superheat that varies with indoor and outdoor
conditions. The evaporator capacity varies with the in-
door heat load on a fixed restrictor. The TXV/EXV regu-
lates the size of the restriction to maintain a constant
superheat. This essentially adjusts the capacity of the
evaporator responding to the indoor heat load. TXV/
EXV systems must be charged to subcooling.
After the restrictor, refrigerant enters the evaporator
at a low temperature and pressure and boils (evaporates)
into a gas by absorbing heat from the indoor air. The re-
frigerant stays at the same temperature and pressure un-
til all the refrigerant evaporates into a gas. After the re-
frigerant becomes a gas, it will become superheated and
the temperature will change. The superheat measure-
ment is the best indication of refrigerant charge level in
a fixed restrictor system and a TXV/EXV system will
keep the superheat constant. There must be superheat
present to ensure liquid does not flood the compressor.
Superheat measurements are taken on the suction line
between the evaporator and compressor.
The compressor takes this low temperature, low
pressure, and slightly superheated refrigerant and com-
presses it into a much higher temperature and pressure.
The highly superheated gas enters the condenser
and rejects heat into the outside air. The refrigerant
condenses back into a liquid. Once all of the gas is con-
densed into a liquid then additional removal of heat
causes a temperature drop known as subcooling. TXV/
EXV systems are charged to subcooling since superheat
is controlled by the throttle valve. Subcooling measure-
ments are taken on the liquid line between the condens-
er and TXV/EXV (fig. 33). Then the subcooled liquid
enters the restrictor, and the cycle starts again.
Figure 33. The Refrigeration Diamond.