LL Pressure
(liquid line pressure): Connect the
ASX14 to the liquid line service port. Set the acces-
sory head to measure pressure and ensure the read-
ing stabilizes before locking in the reading. Enter
data manually if you want to get pressure from your
gauges. The analysis is only as good as the measure-
ments. The Fieldpiece ASX14 has better resolution
than most gauge sets.
LL Temp
(liquid line temperature): Measure near the
same location that the LL Pressure was taken. Use
the ATC1, ATC2 or ATC3 to get a good pipe tem-
perature. The clamp should be perpendicular to the
pipe and should be securely seated with the sensor
in contact with the liquid line.
OD Dry Bulb
(outdoor dry bulb temperature): Clip a
calibrated ATA1 to the inlet of the condenser (typi-
cally on the side of the condenser), in the shade if
possible. Note that the temperature of the air enter-
ing the outdoor coil can be considerably different
than the ambient temperature due to recirculation
of air exiting the unit. Determine the average tem-
perature of the air entering the condenser.
Cond Amps Draw
(actual condensing unit amp
draw): For a package system this is the total amp
draw of the unit. With a factory HG2, use an ACH4
amp clamp and take measurement automatically.
To use another amp clamp (such as the SC77) and
for HG1s upgraded to an HG2, input this measure-
ment manually.
TrueFlow®
7
The TrueFlow® meter measures the airflow directly
via a grid installed in place of the filter (or other location
that has all the indoor unit airflow through it). For more
information please visit www.energyconservatory.com.
TrueFlow®:
Default: NO. If NO, skip ahead to the
Customer ID. Answering YES unlocks the inputs
for this section.
Nom Ton:
Nominal tonnage of the A/C system.
Grid Size:
Default: 14 inches. Other selection: 20 inches.
Choose the grid size you are using.
7 TrueFlow® is the registered trademark of The Energy Conservatory.
Sup Plen Pres:
TrueFlow® system operating pressure
with the filter installed and no TrueFlow® grid. This
is the normal supply operating pressure (NSOP)
and is measured using the static pressure probe in-
cluded with the TrueFlow® plate.
Flow Pressure:
This is the TFSOP and is measured
using the TrueFlow® plate.
Sup Plen Pressure with Grid:
TrueFlow® system
operating pressure with the filter and the TrueFlow®
grid installed. This is the TF SOP and is measured
using the static pressure probe included with the
TrueFlow® plate.
GRANT FORM
If you are working under a grant you are typical-
ly required to track additional information about the
system in order to qualify for the tax rebates or other
incentives. In parts of the Unites States, CheckMe!® is
used to verify that a system is tuned to the highest stan-
dards and qualify the work for grants.
Air conditioning comprises a significant portion of
power consumption in the United States but more im-
portantly is often the cause of peak power usage peri-
ods. Grants are often funded by utilities or government
agencies in order to reduce the peak electrical power
consumption and power infrastructure needed to sup-
port that.
In order to participate in these grants, a technician
will usually have to work through a third party verifier.
Contact your local utility to learn on how to become a
grant participant.
After you have selected "New" or a pre-existing grant
from the list of grants you will be taken to the GRANT
FORM. The Grant form allows you to create new grants
in accordance with particular specifications.
Grant and Sys Info:
Use alpha-numeric characters
to manually input and name this grant. Once cre-
ated you can access this grant for future tests.
Optional Inputs:
Optional inputs are inputs that
you want to be present on the INPUT FORM for the