20
WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM
WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM WWW.FIELDPIECE.COM
2.3 Superheat OUTPUT FORM
Figure 10. Superheat Test OUTPUT FORM.
Press OUTPUT for the Superheat OUTPUT FORM.
Target SH
(Superheat): Indicates what the superheat
should be as calculated from outdoor dry bulb and
indoor wet bulb
Actual SH
(Superheat): Shows the superheat calculated
from the measured suction line temperature and suc-
tion line pressure.
Vapor Sat:
This is the saturation temperature of the re-
frigerant in the evaporator coil. This is the temperature
a refrigerant will boil at a given pressure. It is one of
the temperatures from which superheat is calculated.
The
Actual SH
(superheat) should be within ±5°F of
the Target SH to ensure optimum performance. If the
ac-
tual SH
is outside this range, modifications to the charge
or adjustments to the restrictor (TXV) are necessary.
Adding refrigerant lowers your Actual SH. Recover-
ing refrigerant increases your Actual SH. The amount of
refrigerant necessary to add or recover will vary based on
the size of the system and the difference between the Ac-
tual and Target SH.
Because everything within the system is interdepen-
dent, one adjustment can affect other parts of the system.
For example, increasing airflow increases the superheat,
which may require adding refrigerant. After modifica-
tions, allow 15 minutes to stabilize and then retest.
Superheat and Subcooling FAQ
Q: How do superheat/subcooling tools work?
A:
Superheat tools measure suction line pressure and
suction line temperature, and calculate the actual su-
perheat. Subcooling tools measure the liquid line pres-
sure and liquid line temperature and calculate actual
subcooling. The refrigerant charts for calculations are
incorporated into the software of the HVAC Guide
analyzer.
Q: When should I take my actual and target
superheat/subcooling?
A:
Superheat and subcooling readings must be taken
when the system is in a steady state. Typically a resi-
dential system will be in a steady state after 10-15 min
-
utes. Turn the system on and set the thermostat low to
ensure that the system doesn’t turn off during your
testing. Once the system’s temperatures and pressures
are not fluctuating, the system is in a steady state.
Wet bulb temperature, outdoor dry bulb, suction line
pressure and suction line temperature must be taken
within a short time period to ensure valid results.
Conditions that affect your target superheat and tar-
get subcooling can change by the minute.
Q: What do I do with my ACTUAL superheat
or ACTUAL subcooling measurements?
A:
Compare actual readings against the target superheat/
subcooling. As a general rule, if superheat is too high,
add refrigerant. If too low, remove refrigerant. If sub-
cooling is too low, remove refrigerant. If subcooling is
too high, add refrigerant. Consult the manufacturer’s
specifications before adding or recovering refrigerant
as further diagnostic tests may be needed
Continued on page 27
Diagnostic text and sections of manual
with more information about this test.
If Target SH and Actual SH are more than
5°F apart, as in this example, you need to
make adjustments to the system.
Boiling point is used to calculate Superheat.