Model 2314/2316 SNMP Alarm Encoder
Fial Incorporated
2314/2316-042315
15
The Alarm Inputs Page
To provision or modify an Alarm point, click the Alarm Inputs link in the left pane. The Alarm Inputs page
will appear, as shown in Figure 14.
Figure 14. Alarm Inputs Page Via The Web
The Alarm Inputs page (as shown in Figure 14), displays the provisioning table for the 8 external alarm
points in this unit. You may have to use the thumb bar to view all alarm points. Alarm information includes
Alarm Point number, Name, current State, Severity, Service Affecting, Delay period and Inverted condition.
You need not provision points that are unused, but all 8 points are always present in the table as viewed by
an SNMP manager. Use the dialog table at the bottom of this screen to provision each alarm point. The
dialog table does not appear if the user is not logged in with administrator privileges. To provision an alarm
point, edit the following fields found at the bottom of the screen:
Edit Alarm Point: Use this drop-down box to select the alarm point you wish to edit.
Name: Enter a name for the selected alarm. Any characters are allowed in this field. Alarm names
can be the same as other alarms; however, this is not recommended for obvious reasons.
Names may be up to 29 characters long. The column width adjusts to fit the name.
Severity: Select the Severity level for the selected alarm point. The possible Severity levels are:
CR, MJ, MN, and ST. Only CR, MJ and MN generate notifications when asserted. To make
Summary of Contents for 2314