46
1.5 Generator Monitor / Protect
1.5.1 enhanced generator monitor
Setpoints > Generator Monitor / Protect > enhanced Generator Monitor
Setpoint name
Min
Value
Max
Value
Units
factory
Default
Description
Generator Winding Temperature Sensor
Installation Status
Value List
Set to “Installed” when a
temperature module is installed
on the accessory data link
Number of Generator Bearing Temperature
Sensors
Value List
1.5.2 Generator aC monitor
Setpoints > Generator Monitor/Protect > Generator aC Monitor
Setpoint name
Min
Value
Max
Value
Units
Description
Generator Connection Configuration
Value List
Configurations can be: “Star/Wye”
“Delta/3 Wire”
“Delta/4 Wire”
“Single Phase 2 Wire” “Single Phase 3 Wire”
Generator Potential Transformer Primary
Winding Rating
1
50000
V
For direct sensing leave at default value.
For an application requiring a potential
transformer set to transformer primary
winding value.
Generator Potential Transformer Secondary
Winding Rating
1
240
V
For direct sensing leave at default value.
For an application requiring a potential
transformer set to transformer secondary
winding value
Generator Current Transformer Primary Winding
Rating
1
7000
A
Set to current transformer primary winding
value
Generator Current Transformer Secondary
Winding Rating
1
5
A
Can only be set to 1 or 5
Number of Generator Poles
0
200
N/A
Generator Rated Frequency
Value List
Generator Rated Voltage
100
50000
V
Generator Rated Power
1
50000
kW
Generator Rated Apparent Power
1
50000
kVA
1.5.3 Generator aC power monitor
The generator AC power monitor measures all generator power quantities, such as kW, kWh, kVAr, kVArh, kVA etc.
Setpoints > Gen Monitor/Protect > Gen aC Power Mon
Setpoint name
Min Value
Max Value
Units
factory Default
Customer Password Security Level to Reset
Generator Energy Meters
0
3
N/A
3