13
DroP To MIn leVel
– used to return the current security level to the lowest level setup. Highlight and press OK to drop to
minimum level security. If no Levels 1 or 2 passwords are setup the minimum level will be 2. If a Level 2 password is setup, the
minimum level will be 1 and if a Level 1 password is setup the minimum level will be 0.
enTer leVel 1 or 2
– used to enter Level 1 or 2 passwords. Highlight and press OK to proceed to the password entry screen.
Passwords can be entered using the cursor keys. In PowerWizard Level 1 and 2 passwords must be different. An entered
password is compared against the stored Levels 1 and 2 passwords, if the password is correct the PowerWizard will go to the
corresponding security level.
enTer leVel 3
– used to obtain Level 3 access. The Level 3 security password is reserved for critical setpoints that should only be
changed by a skilled operative. The Level 3 password is a prompt and response password.
Highlight and press OK to proceed to the phone in prompt display. The Level 3 password can be obtained by contacting the
generating set manufacturer and providing the 16 digit phone in prompt. The manufacturer will then provide the relevant
response. To enter the 16 digit response press OK again. Passwords can be entered using the cursor keys. The Level 3 password
will expire 10 minutes after the last key pressed.
The Level 3 password can be obtained from the After Sales Helpdesk. Refer to the contact list at the back of the manual.
CHanGe leVel 1 PaSSWorD
– used to setup, change or disable a Level 1 password. In order to use this feature the control
must be at current security Level 1 or higher. Highlight and press OK to proceed to the password entry screen. To setup or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the Level 1
security password, set the password to ‘0’. Press the OK key to save.
CHanGe leVel 2 PaSSWorD
– used to setup, change or disable a Level 2 password. In order to use this feature the control
must be at current security Level 2 or higher. Highlight and press OK to proceed to the password entry screen. To setup or
change the password, enter the new password using the cursor keys. Passwords may be 16 digits long. To disable the level 2
security password set, the password to ‘0’. Press the OK key to save.
CHanGe SCaDa PaSSWorD
(PowerWizard 2.1 only) – used to setup, change or disable a SCADA password. Highlight and press
OK to proceed to the password entry screen. To setup or change the password, enter the new password using the cursor keys.
Passwords may be 16 digits long. To disable the SCADA security password, set the password to ‘0’. Press the OK key to save.
3.4 real Time Clock Programming (PowerWizard 2.1)
The real time clock provides information for the time and date of an automatic time based start / stop control. It also provides a
mechanism for time stamps in the event log. The real time clock is not calibrated and is for information only. The date and time
are set by the user.
In order to set the time or date format:
1.
MAIN MENU > CONFIGURE > TIME/DATE
To set the time, highlight the time then press the OK key twice.
2.
Use the cursor keys to set the time and press the OK key to save. Press the Escape key to return.
3.
To set the date, highlight the date then press the OK key twice.
4.
Use the cursor keys to set the date and press the OK key to save. Press the OK key to return.
5.
To set the date format, highlight either the ‘FORMAT DD/MM/YY’ or ‘FORMAT MM/DD/YY’ and press the OK key.
6.
Use the cursor keys to select the required date format and press the OK key to save.
7.
3.5 fuel Priming – engines with electronic fuel lift Pump
Certain engines fitted with an electronic fuel pump do not have a manual-priming feature on the engine. In these circumstances
the PowerWizard can be used to energize the fuel lift pump in order to prime the engine.
In order to prime the generating set:
1.
MAIN MENU > CONTROL > ENGINE FUEL PRIMING
To prime the set press the right cursor key, this will initiate a 180 second priming cycle.
2.
To exit the priming cycle press the left cursor key.
3.
note
:
The generating set may only be primed when stopped and there are no active or present shutdown conditions.
•