44
1.2.2 aVr Desired Voltage
Setpoints > Control > aVr Desired Voltage
Setpoint name
Min
Value
Max
Value
Units
Description
Maximum Generator Voltage
Output Bias Percentage
0
100
%
The Maximum Generator Output voltage Bias Percent is the
maximum value above and below the Nominal Voltage that the
control will send a request for when adjusting the voltage from
the control screen
Generator Nominal Output
Voltage
100
50000
V
The Generator Nominal Output Voltage is the desired output
voltage of the generating set. This value is set to match the
generator rated voltage.
1.2.3 Governor Desired engine Speed
Setpoints > Control > Governor Desired engine Speed
Setpoint name
Min
Value
Max
Value
Units
Description
Maximum Engine Speed Range
0
2000
rpm
The Maximum Engine Speed Range is the maximum value
above and below the Nominal Engine Speed that PowerWizard
will send a request for when adjusting the speed from the
control screen
Generator Nominal Output
Frequency
40
500
Hz
This value is set to match the generator rated frequency
1.3 engine Monitor / Protect
1.3.1 Battery Voltage Monitor
Setpoints > engine Monitor / Protect > Battery Voltage Monitor
Setpoint name
Min
Value
Max Value
Units
High Battery Voltage Warning Event Threshold
12
50
VDC
High Battery Voltage Warning Event Notification Delay Time
0.0
240
sec
High Battery Voltage Shutdown Event Threshold
12
50
VDC
High Battery Voltage Shutdown Event Notification Delay Time
0.0
240
sec
Low Battery Voltage Warning Event Threshold
0.0
25.0
VDC
Low Battery Voltage Warning Event Notification Delay Time
0.0
240
sec
Low Battery Charging System Voltage Warning Event Threshold
0.0
30
VDC
Low Battery Charging System Voltage Warning Event Notification Delay Time
0.0
240
sec
Low Cranking Voltage Warning Event Threshold
0.0
30.0
VDC
Low Cranking Voltage Warning Event Notification Delay Time
0.0
240
sec
1.3.2 Crank / Start Counter
Setpoints > engine Monitor / Protect > Crank / Start Counter
Setpoint name
Min
Value
Max
Value
Units
factory
Default
Description
Customer Security Password Level to
Reset Crank / Start Counters
0
4
n/a
3
Password level required in order to reset the
Crank / Start Counters