Commissioning
Pin allocation of the pilot air switching valve
Pin allocation
M12 connection
1
+24 V SENS
2
not assigned
3
0 V SENS
4
SENS OUT
5
not assigned
Tab. 40: Pin allocation of the pilot air switching valve
7.2.4
Earthing the valve terminal
1
Fig. 39: Earth terminal
1
Earth terminal
–
Connect the earth terminal to the earth potential with low impedance (short cable with large
cross-section).
–
Further information
è
Description of the CPX system (CPX-SYS-...).
8
Commissioning
8.1
Commissioning of the Pneumatic Components
8.1.1
Testing pneumatic components
8.1.1.1
Determining the exhaust times of the pressure switches
In order to query the exhausted status at the correct time, determine the exhaust times of the pressure
switches.
The exhaust times depend on the following factors:
–
Application, including drives and consumers
–
Configuration of the valve terminal
If the application or the configuration of the valve terminal is changed, recalculate the exhaust times.