background image

Proportional pressure regulator valve
VPPM-…-LK-…

Festo AG & Co. KG

Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com

Operating instructions
(Translation of the original instructions)

8086184
2018-03b
[8086186]

For all available product documentation 

è

 www.festo.com/pk

Proportional pressure regulator valve

English

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

IO-Link

®

 is a registered trademark of the trademark holder in certain countries.

1

Application and function

The VPPM is intended for controlling a pressure
proportional to a specified setpoint value (input
word). A built-in pressure sensor records the
pressure at the working port and compares this
value with the setpoint value. If there are devi­
ations between the actual value and the set­
point value, the control valve is actuated until
the outlet pressure reaches the setpoint value.

Fig. 1

2

Characteristics in the type code

Type code

1

2

3

5

6

4

7

VPPM

- 6L -

-

-

-

-

-

L

1

G18

0L6H

LK

S1

Item

Characteristics

Significance

1

Nominal width in [mm]

6, 8, 12

Valve type

F (flange), L (sleeve)

2

Dynamic response class

L (Low)

3

Valve function

1 (3-way pressure regulator, normally
closed)

4

Pneumatic connection

– Flange/sub-base

F6 (NW 6 mm), F8 (NW 8 mm)

– ISO thread

G18 (

x

"), G14 (

¼

"), G12 (

½

")

5

Control ranges

– Lower pressure value

0L (0 bar)

– Upper pressure value

2H (2 bar), 6H (6 bar), 10H (10 bar)

6

– Setpoint specification

IO-Link-specific

7

Accuracy

S1 (1 %)

Fig. 2

3

Requirements for product use

 Installation and commissioning is to be carried out only by qualified personnel,

in accordance with the documentation.

 Take into consideration the ambient conditions at the location of use.
 All applicable national and international regulations must be complied with.

 Use the product in its original status, without any unauthorised product

modifications.

 Ensure that the compressed air is properly prepared (

è

 Technical data).

  Pressurize your entire system slowly. There will then be no uncontrolled

movements.

Range of application and certifications

In combination with the UL mark on the product, the information included in this
section is also applicable for compliance with the certification requirements of
Underwriters Laboratories Inc. (UL) for USA and Canada.

UL approval information

Product category code

QUYX, QUYX7 

File number

E322346

Standards taken into account

UL 61010­1, CAN/CSA­C22.2 No. 61010­1

UL identification

Fig. 3

The product must be powered by a power source that fulfills the requirements of
an energy-limited circuit in accordance with IEC/EN/UL/CSA 61010-1 or a power
source with limited power (LPS)in accordance with IEC/EN/UL/CSA 60950-1 or
IEC/EN/UL/CSA 62368-1 or a Class 2 circuit in accordance with NEC or CEC.

3.1 Connections and mounting holes (in-line valve)

1

2

3

5

4

3

1

Electr. connecting plug (5-pin)

2

Air (2), pressure output

3

Through holes for mounting. For
size 

½

" in the manifold block

4

Compressed air (1), supply port

5

Exhaust (3)

Fig. 4

4

Installation

4.1 Mechanical

 Make sure there is sufficient space for the connecting cable and tubing connec­

tions. In this way you will prevent the cable and tubes from being bent.

 Place the VPPM as close to the consumer as possible. This leads to improved

control precision and shorter response times.

Wall mounting

 Fasten the in-line valve of size 

x

" and 

¼

"

at the intended position with two M4 screws.
If necessary, use bracket type VAME-P1-A
(

è

 Fig. 5) to do this. When using the bracket,

the VPPM may only be loaded statically.

 Fasten the in-line valve of size 

½

" at the

intended position with two M5 screws
(tightening torque 2.0 Nm).

 Mount the flange valve of size 

x

" and 

¼

"

onto the manifold rail VEABM-P1-SF-G18…
(tightening torque approx. 1.5 Nm). Fasten
the manifold rail at the intended position
with two M6 screws.

Fig. 5

Summary of Contents for VPPM-...-LK Series

Page 1: ...ns Ensure that the compressed air is properly prepared è Technical data Pressurize your entire system slowly There will then be no uncontrolled movements Range of application and certifications In combination with the UL mark on the product the information included in this section is also applicable for compliance with the certification requirements of Underwriters Laboratories Inc UL for USA and ...

Page 2: ...mand to ISDU parameter 0x0048 COM3 03 COM2 02 For I Port the data rate is always set to COM3 Power supply with 24 V DC is provided through the IO Link master Pressurize the VPPM with an input pressure at least 1 bar higher than the max imum desired output pressure An outlet pressure p2 proportionate to it is then set The following outlet pressure is then assigned to the setpoint value signal Type ...

Page 3: ...tting x value is unimportant for this setting Fig 13 Valve parameter Condition counter solenoid coil Parameter no 8 11 Condition counter limit Manual A limit value for a counter condition counter can be set for the internal solenoid coil in the pilot control of the pressure regulator A message is displayed if the limit value is exceeded which is sent to the IO Link master Bytes 11 or 8 High byte o...

Page 4: ...t pressure Failure of data communication Replace data transmission line Fig 24 13 Technical data VPPM 2 bar 29 psi 6 bar 87 psi 10 bar 145 psi Design Proportional pressure regulator Mounting position Any preferably flat display components facing upwards Operating medium Compressed air in accordance with ISO 8573 1 2010 7 4 4 with use of ester oil compressed air in accordance with ISO 8573 1 2010 2...

Reviews: