Festo VPPM-...-LK Series Operating Instructions Download Page 3

Valve parameter: ID

Parameter  no.

1

Description

Provides valve identification for I-Port

Values

In-line valve

Flanged valve

0x01:

1/8" 10 bar

0x31:

F6 10 bar

0x02:

1/8" 6 bar

0x32:

F6 6 bar

0x03:

1/8" 2 bar

0x33:

F6 2 bar

0x11:

1/4" 10 bar

0x41:

F8 10 bar

0x12:

1/4" 6 bar

0x42:

F8 6 bar

0x13:

1/4" 2 bar

0x43:

F8 2 bar

0x21:

1/2" 10 bar

0x22:

1/2" 6 bar

0x23:

1/2" 2 bar

Comment

Read only

Fig. 11

Note

When changing the unit for pressure specifications, the parameters for the limit
values and the input word (setpoint value) are not automatically converted.
 When changing the unit, also change the parameters for the upper/lower limit

value and the input word

 (

è

 

Fig. 17

)

.

Valve parameter: Unit for pressure indications

Parameter no.

2

Description

Defines the unit for pressure indications (limit values, pressure setpoint
specification and pressure actual value  specification).

Bit

Bit 1.0

Values

Bit

1 0 Setting

Resolution

0 0 mbar (preset)

1 mbar/bit

0 1 kPa

1 kPa/bit

1 0 psi

0.1 psi/bit

1 1 reserved

Comment

To avoid accidental pressure fluctuations, set the input word before conversion
of the unit to zero.

Fig. 12

Valve parameters: Setting of the control behaviour (presets), output data type
and measured value smoothing

Parameter no.

3

Description

Parameterised via this function number are:
– Control behaviour (presets): Defines the characteristic curve used for

controlling a setpoint pressure.

– Output data type: Offers 3 options for what is presented in the output word

(data format 

è

 

Fig. 16):

– Output of the current pressure value
– Output as comparator bit:

Bit 0 = 0: Pressure value is outside the control range
Bit 0 = 1: Pressure value is in the control range

– Combined output of current pressure value and comparator bit. Bit 0 is used

as the comparator bit, as above It is no longer used for representing
the pressure value.

– Measured value smoothing: Sets how strongly the measured values are

smoothed for limit monitoring. This can suppress possible malfunctions.

Bit

Bit 1, 0: Control behaviour (presets)
Bit 3, 2: Output data type
Bit 5, 4: Measured value  smoothing

Values

Bit

5

4

3

2

1

0

Control behaviour setting (presets):

x

x

x

x

0

0

Reserved

x

x

x

x

0

1

Fast

x

x

x

x

1

0

General (presetting)

x

x

x

x

1

1

Precise

Setting of output data type:

x

x

0

0

x

x

Reserved

x

x

0

1

x

x

Current pressure value in the output word
(presetting)

x

x

1

0

x

x

Comparator bit (bit 0 in the output word)

x

x

1

1

x

x

Current pressure value and comparator bit

Settings of measured value smoothing:

0

0

x

x

x

x

No measured value smoothing (presetting)

0

1

x

x

x

x

Smoothing over 2 values

1

0

x

x

x

x

Smoothing over 4 values

1

1

x

x

x

x

Smoothing over 8 values

Comment

Bold = presetting, x = value is unimportant for this setting

Fig. 13

Valve parameter: Condition counter solenoid coil

Parameter no.

 

8...11

 Condition counter limit

Manual

A limit value for a counter (condition counter) can be set for the internal
solenoid coil in the pilot control of the pressure regulator. A message is
displayed if the limit value is exceeded, which is sent to the IO-Link master.

Bytes

11 or 8: High byte or low byte of the limit value (32 bit values,  hexadecimal)

Values

FFFFFFFF

h

:

Condition counter activated, but limit value  inactive
(preset)

2DC6C0

h

:

(Example) Condition counter activated and limit value
3,000,000

d

 set.

0:

Condition counter inactive (counter and diagnostic message
deactivated, counter reset, counter actual value can be read
through 0x6B.)

Fig. 14

Valve parameter: lower / upper limit

Parameter no.

12…13

 Lower limit value

14…15

 Upper limit value

Description

The lower and upper limit values for the pressure and diagnostic messages are
set with these parameters. Undershooting or overshooting of limit values is only
signaled if the output word diagnostics is activated via the limit value
monitoring parameter (

è

 

Fig. 10).

Byte

12 or 14 low byte
13 or 15 high byte

Values

Presets
– Lower limit value = 0 (low byte = 0; high byte: 0)
– Upper limit value: Max. pressure value of the valve type (

è

 Fig. 17)

Remarks

The upper limit value must always be greater than the lower limit value.
The limit values are checked for validity during parameterisation. If invalid
parameters are present and the module parameter “Monitoring of
parametrisation errors” is active, a corresponding error is signaled
(

è

 Chapter 12).

Fig. 15

Process Data

Input word (setpoint value, 16 bit)

Output word (pressure value, 16 bit)
LSB (bit 0) can be used as a comparator bit with parameterisation of output data.

Fig. 16

Proportional
pressure regulator

Control
range

Range of values 

1)

input word (decimal)

Range of values 

1)

 

input word (hex)

VPPM-...-0L2H-LK-S1

0 … 2 bar

0 … 2000/290/200

0

h

 … 07D0

h

/0122

h

/00c8

h

VPPM-…-0L6H-LK-S1

0 … 6 bar

0 … 6000/870/600

0

h

 … 1770

h

/0366

h

//0258

h

VPPM-...-0L10H-LK-S1

0 … 10 bar

0 … 10000/1450/1000

0

h

 … 2710

h

/05AA

h

/03E8

h

1)

If mbar/psi/kPa is set as the pressure unit

Fig. 17

Recommended parameter sets VPPM size 

x

" (presets

 

è

 

Fig. 13)

Tube
length

 1)

Open
system

Output volumes in ml

0 … 100

100 … 1000

> 1000

0 m

3

3

2

1

1 m

3

3

2

2

3 m

3

3

3

2

 

5 m

3

3

3

2

1)

With tubing diameter 6 mm or 8 mm

Fig. 18

Recommended parameter sets VPPM 

¼

" and 

½

" (presets

 

è

 

Fig. 13)

Tube
length

 1) 2)

Open
system

Output volumes in ml

Size 

¼

"

0 … 500

500 … 2000

> 2000

Size 

½

"

0 … 2000

2000 … 10000

> 10000

0 m

3

1

2

3

1 m

3

1

2

3

3 m

3

2

3

3

 

5 m

3

3

3

3

1)

With tubing diameter 8 mm or 10 mm (1/4")

2)

With tubing diameter 12 mm or 16 mm (1/2")

Fig. 19

7

Operation

Note

When switching off the VPPM, first make sure that the setpoint value is set to 0,
then that the supply pressure and finally the supply voltage are switched off.

Summary of Contents for VPPM-...-LK Series

Page 1: ...ns Ensure that the compressed air is properly prepared è Technical data Pressurize your entire system slowly There will then be no uncontrolled movements Range of application and certifications In combination with the UL mark on the product the information included in this section is also applicable for compliance with the certification requirements of Underwriters Laboratories Inc UL for USA and ...

Page 2: ...mand to ISDU parameter 0x0048 COM3 03 COM2 02 For I Port the data rate is always set to COM3 Power supply with 24 V DC is provided through the IO Link master Pressurize the VPPM with an input pressure at least 1 bar higher than the max imum desired output pressure An outlet pressure p2 proportionate to it is then set The following outlet pressure is then assigned to the setpoint value signal Type ...

Page 3: ...tting x value is unimportant for this setting Fig 13 Valve parameter Condition counter solenoid coil Parameter no 8 11 Condition counter limit Manual A limit value for a counter condition counter can be set for the internal solenoid coil in the pilot control of the pressure regulator A message is displayed if the limit value is exceeded which is sent to the IO Link master Bytes 11 or 8 High byte o...

Page 4: ...t pressure Failure of data communication Replace data transmission line Fig 24 13 Technical data VPPM 2 bar 29 psi 6 bar 87 psi 10 bar 145 psi Design Proportional pressure regulator Mounting position Any preferably flat display components facing upwards Operating medium Compressed air in accordance with ISO 8573 1 2010 7 4 4 with use of ester oil compressed air in accordance with ISO 8573 1 2010 2...