Select the I/O start addresses, e.g.: DI = 24,
DO = 24.
#
Configuration ( = equipment on terminal)
Enter:
•
for each group of 8 inputs:
8DI
•
for each group of 8 outputs:
8DO
The entry fields must be assigned in as-
cending order without gaps. No field may
be unused. Inputs must be entered before
outputs.
Example 1:
Valve sensor terminal with
10 valve locations,
Configuration:
8DI, 8DI, 8DI, 8DI, 8DO, 8DO, 8DO
The 2 status bits increase the number of in-
puts to 24 in this case
(22 2 status bits).
Example 2:
Valve terminal with 10 valve locations.
Configuration:
8DO, 8DO, 8DO
VIFB9 – 02
5. Commissioning
9609
5-13
Summary of Contents for IIFB9-02 Series
Page 1: ......
Page 3: ...Order no 151767 Title MANUAL Designation P BE VIFB9 02 GB VIFB9 02 II 9609...
Page 5: ...VIFB9 02 IV 9609...
Page 6: ...1 USER INSTRUCTIONS VIFB9 02 1 User instructions 9609 1 1...
Page 7: ...Contents IMPORTANT USER INSTRUCTIONS 1 3 VIFB9 02 1 User instructions 1 2 9609...
Page 11: ...VIFB9 02 1 User instructions 1 6 9609...
Page 12: ...2 SYSTEM STRUCTURE VIFB9 02 2 System structure 9609 2 1...
Page 20: ...3 TECHNICAL DESCRIPTION VIFB9 02 3 Technical description 9609 3 1...
Page 38: ...4 INSTALLATION VIFB9 02 4 Installation 9609 4 1...
Page 79: ...VIFB9 02 4 Installation 4 42 9609...
Page 80: ...5 COMMISSIONING VIFB9 02 5 Commissioning 9609 5 1...
Page 128: ...6 DIAGNOSTICS AND ERROR TREATMENT VIFB9 02 6 Diagnostics error treatment 9609 6 1...
Page 131: ...VIFB9 02 6 Diagnostics error treatment 6 4 9609...
Page 157: ...VIFB9 02 6 Diagnostics error treatment 6 30 9609...
Page 158: ...INDEX VIFB9 02 Appendix A 9609 A 1...
Page 159: ...VIFB9 02 Appendix A A 2 9609...