Testing
1. Switch on the compressed air supply.
2. Check the function and effectiveness of each
individual valve as follows. If the valve does
not function correctly see Fig. 4/11.
•
Manual override with automatic reset
Operating the manual override
Reaction of valve
or of processor
Press the plunger
of manual override
as far as it will go.
The valve or
the processor
●
switches
Hold the plunger of
manual override
pressed down.
●
remains switched
Remove the
screwdriver.
A spring returns the
plunger of manual
override to start
position.
●
returns to basic
setting
Fig. 4/9: Manual override with automatic reset
VIFB9 - 02 4. Installation
9609
4-13
Summary of Contents for IIFB9-02 Series
Page 1: ......
Page 3: ...Order no 151767 Title MANUAL Designation P BE VIFB9 02 GB VIFB9 02 II 9609...
Page 5: ...VIFB9 02 IV 9609...
Page 6: ...1 USER INSTRUCTIONS VIFB9 02 1 User instructions 9609 1 1...
Page 7: ...Contents IMPORTANT USER INSTRUCTIONS 1 3 VIFB9 02 1 User instructions 1 2 9609...
Page 11: ...VIFB9 02 1 User instructions 1 6 9609...
Page 12: ...2 SYSTEM STRUCTURE VIFB9 02 2 System structure 9609 2 1...
Page 20: ...3 TECHNICAL DESCRIPTION VIFB9 02 3 Technical description 9609 3 1...
Page 38: ...4 INSTALLATION VIFB9 02 4 Installation 9609 4 1...
Page 79: ...VIFB9 02 4 Installation 4 42 9609...
Page 80: ...5 COMMISSIONING VIFB9 02 5 Commissioning 9609 5 1...
Page 128: ...6 DIAGNOSTICS AND ERROR TREATMENT VIFB9 02 6 Diagnostics error treatment 9609 6 1...
Page 131: ...VIFB9 02 6 Diagnostics error treatment 6 4 9609...
Page 157: ...VIFB9 02 6 Diagnostics error treatment 6 30 9609...
Page 158: ...INDEX VIFB9 02 Appendix A 9609 A 1...
Page 159: ...VIFB9 02 Appendix A A 2 9609...