Short circuit/overload at an output module
In the case of a short circuit or overload:
•
the digital output will be switched off,
•
the red LED will light up,
•
the short circuit error bit of the diagnostic
word will be set at logic 1,
•
the error code "short circuit/overload" will be
entered in the two status bits.
In order to activate the output again, proceed as
follows.
The output can then be reset at "logic 1".
If the short circuit still exists, the output will be
switched off again.
Step
Explanation
Eliminate short circuit or overload
Set output at 0 (RESET)
•
Manual (control)
•
Automatically in the program
The error bit in the diagnostic word of the
terminal is reset at logic 0.
Fig. 6/23: Eliminating short circuit/overload
VIFB9 - 02
6. Diagnostics/error treatment
9609
6-29
Summary of Contents for IIFB9-02 Series
Page 1: ......
Page 3: ...Order no 151767 Title MANUAL Designation P BE VIFB9 02 GB VIFB9 02 II 9609...
Page 5: ...VIFB9 02 IV 9609...
Page 6: ...1 USER INSTRUCTIONS VIFB9 02 1 User instructions 9609 1 1...
Page 7: ...Contents IMPORTANT USER INSTRUCTIONS 1 3 VIFB9 02 1 User instructions 1 2 9609...
Page 11: ...VIFB9 02 1 User instructions 1 6 9609...
Page 12: ...2 SYSTEM STRUCTURE VIFB9 02 2 System structure 9609 2 1...
Page 20: ...3 TECHNICAL DESCRIPTION VIFB9 02 3 Technical description 9609 3 1...
Page 38: ...4 INSTALLATION VIFB9 02 4 Installation 9609 4 1...
Page 79: ...VIFB9 02 4 Installation 4 42 9609...
Page 80: ...5 COMMISSIONING VIFB9 02 5 Commissioning 9609 5 1...
Page 128: ...6 DIAGNOSTICS AND ERROR TREATMENT VIFB9 02 6 Diagnostics error treatment 9609 6 1...
Page 131: ...VIFB9 02 6 Diagnostics error treatment 6 4 9609...
Page 157: ...VIFB9 02 6 Diagnostics error treatment 6 30 9609...
Page 158: ...INDEX VIFB9 02 Appendix A 9609 A 1...
Page 159: ...VIFB9 02 Appendix A A 2 9609...