Terminal CPX-P

Key features

Variants for controlling the CPX-P terminal (with bus node, without preprocessing)

Bus node

Different bus nodes are used to

integrate the terminal in the control

systems of various manufacturers.

The CPX-P terminal can therefore be

operated on commonly used fieldbus

systems:

PROFIBUS DP

PROFINET

DeviceNet

Integration in universal networks

based on Ethernet opens up new

possibilities. Faster data transmis­

sion, real-time capability and above

all additional IT services such as file

transfer, web server, web monitor as

integrated website in the CPX-P

terminal, text message/e-mail alerts,

etc. open up a wide range of

synergies.

These include standardised and

universal communication technology

across all areas, including operating

level, management level and field

level in the production environment,

with protection to IP65.

The following protocols are supported:

EtherNet/IP

Modbus/TCP

PROFINET

Bus node

Industrial Ethernet bus node

PLC

Fieldbus

Web

IT services:

E-mail

File transfer

PLC

Industrial Ethernet

Communication with higher-order

controller via fieldbus

No preprocessing

Fieldbus protocol dependent on

CPX bus node used

Up to 90 I/Os, depending on the

bus node used

Connection to a higher-order

controller directly via EtherNet/IP,

Modbus/TCP or PROFINET

No preprocessing

Monitoring via Ethernet and web

applications

Up to 300 I/Os

-H-

Note

Every electrical connection can be

combined with an appropriate

number of I/O modules and/or

pneumatic components, depending

on its address capacity.

Likewise, every pneumatic variant of

the CPX-P terminal can be operated

with every electrical connection

variant.

Summary of Contents for CPX-P

Page 1: ...Modular electrical terminal CPX P...

Page 2: ...outputs 2 4 way Analogue inputs and outputs with HART protocol Input modules for connecting NAMUR sensors IP65 or IP20 Wall or H rail mounting also on mobile units Conversions extensions are possible...

Page 3: ...versal communication technology across all areas including operating level management level and field level in the production environment with protection to IP65 The following protocols are supported...

Page 4: ...cks M12 4 pin Screw terminal and spring loaded terminal CPX modules for NAMUR sensors intrinsically safe circuits for ATEX applications PLC Fieldbus 1 2 3 4 5 6 6 1 Higher order controller 2 Non ATEX...

Page 5: ...ssembled according to your order specifications and individually tested The finished valve terminal consists of the electrical peripherals including the desired actuation and the selected components f...

Page 6: ...fieldbus parameters via DIL switch Display of fieldbus and peripheral equipment status via LED Remote unit CPX CEC Connection via Ethernet TCP IP or Sub D programming interface Setting of operating m...

Page 7: ...for the entire system Additional power supply for outputs Connection accessories for 7 8 Individual linking with M6 screws individually expandable Digital inputs for connecting the sensors Digital out...

Page 8: ...P20 Spring loaded terminal Screening concept Optional screening plate for con nection block with M12 connection technology Direct machine mounting connection block to IP65 IP67 M12 5POL Digital electr...

Page 9: ...interlinking block Individual linking 86 System linking Different voltage values for supplying the modules Serial communication between the modules System supply 7 8 5 pin In addition to system linki...

Page 10: ...linking blocks Combination of connection blocks and electronics modules for inputs and outputs Digital electronics modules For inputs For outputs For NAMUR sensors CPX 8DE CPX 8NDE CPX 16DE CPX 4DA CP...

Page 11: ...livers pre assembled M8 M12 connecting cables NEBU modular system on request Tailored to the application Perfect fit Saves installation Combination of connection block and electrical connection techno...

Page 12: ...ectable connection technology 1 CPX AB 8 M8X2 4POL Socket M8 4 pin 2 NEBU M8G4 Modular system for choice of connecting cables Socket M8 3 pin Socket M8 4 pin Socket M12 5 pin Open cable end 3 NEDY L2R...

Page 13: ...Plug connector connecting cable Selectable connection technology 1 CPX P AB 4XM12 4POL 8DE N IS Socket M12 4 pin 3 NECU M S A12G4 IS Plug M12 4 pin 3 NECU S M12G4 IS Plug M12 4 pin 2 NEDU M12D4 M12T4...

Page 14: ...sign per connection Version R with quick lock techno logy and metal thread for screening With two channels per connection the corresponding input signals can be easily connected via a T adapter and co...

Page 15: ...ystem for all types of sensor actuator distributor 2x socket M8 3 pin 2x socket M8 4 pin 2x socket M12 5 pin 2x socket type A 2x socket type B 2x socket type C 2x socket plug pattern H 2x socket plug...

Page 16: ...tion block Connection technology Plug connector connecting cable Selectable connection technology 1 CPX AB 8 KL 4POL Spring loaded terminals 32 pin 2 AK 8KL cover Electrical connection Connection bloc...

Page 17: ...Plug connector connecting cable Selectable connection technology 1 CPX AB 1 SUB BU 25POL Socket Sub D 25 pin 2 SD SUB D ST25 Crimp contacts Electrical connection Connection block with quick connector...

Page 18: ...for the underlying modules in combination with a suitable mounting plate provided by the user Protection against electrostatic discharge through the use of electrically conductive materials and the op...

Page 19: ...lot nut with screws for joining the hood sections 5 Rail 6 Mounting bracket Technical data Weight Hood approx 500 g per 100 mm of length Mounting rail approx 550 g per 1 000 mm of length Side pieces a...

Page 20: ...ill need the following mounting kit CPX CPA BG NRH This facilitates mounting of the CPX P terminal on H rails to EN 60715 An additional mounting kit is required for combination with valve terminals Wa...

Page 21: ...ply for electronics plus sensors valves plus actuators Connection technology 7 8 Interlinking blocks Interlinking blocks represent the backbone of the CPX P terminal with all supply lines They provide...

Page 22: ...nnected to output modules of the CPX P terminal Without power supply CPX M GE EV With additional power supply for outputs CPX M GE EV Z 7 8 5POL CPX M GE EV Z 7 8 5POL VL Connection technology 7 8 5 p...

Page 23: ...puts and valves Open load detection for a missing solenoid coil Storage of the last 40 causes of errors with error start and error end The diagnostic messages can be read out via the bus interface in...

Page 24: ...nges to the application are often required during commissioning The parameterisable characteristics of the CPX P modules mean that functions can be very easily changed by means of configuration softwa...

Page 25: ...gured as counter 80 16 CPX P 8DE N IS 16 8 CPX P 8DE N IS inputs configured as counter 80 16 CPX 8DE 8 CPX 8NDE 8 CPX 16DE 16 CPX 4DA 4 CPX 8DA 8 CPX 4AE U I 4 x 16 CPX 2AA U I 2 x 16 CPX 4AE 4AA H V...

Page 26: ...62818 Max no of modules1 Control block 1 Bus node 1 I O modules 9 Pneumatic interface 1 Max address capacity Inputs byte 64 Outputs byte 64 Internal cycle time ms 1 Configuration support Fieldbus spec...

Page 27: ...ectronics only ms 10 Power supply connection 7 8 5 pin Fuse concept Per module with electronic fuses Tests Vibration test to DIN IEC 68 With wall mounting Severity level 2 With H rail mounting Severit...

Page 28: ...Certificates If the component is subject to restrictions on usage in residential office or commercial environments or small businesses further measures to reduce the emitted interference may be necess...

Page 29: ...wer supply for outputs 7 8 5 pin 550210 CPX M GE EV Z 7 8 5POL 7 8 5 pin for ATEX environment 8022158 CPX M GE EV Z 7 8 5POL VL Mounting accessories Screws for mounting the bus node connection block o...

Page 30: ...g attachments for connecting several hood sections in series 200 mm 572258 CAFC X1 GAL 200 300 mm 572259 CAFC X1 GAL 300 User documentation CPX P System Manual German 526445 P BE CPX SYS DE English 52...

Page 31: ...on commissioning and diagnostics of the MPA S pneumatic components Electronic components P BE CPX SYS System description installation and commissioning Overview of the design components and mode of op...

Page 32: ...el oriented errors Condition monitoring preselection loading of counters activation of the channels to be monitored Display of the last 40 error occurrences with timestamp Identification of sporadic c...

Page 33: ...agnostics Fast access to the diagnostic history and the modules with diagnostic messaging Display of the last 40 diagnostic messages with timestamp Display of the current diagnostic message for a modu...

Page 34: ...th wall mounting Severity level 2 With H rail mounting Severity level 1 Materials Reinforced PA Dimensions W x H x D mm 81 x 137 x 28 Product weight g 150 Operating and environmental conditions Ambien...

Page 35: ...3 Ordering data Designation Part No Type Operator unit Provides data polling configuration and diagnostic functions for CPX P terminals 529043 CPX MMI 1 Connecting cable Connecting cable M12 M12 spec...

Page 36: ...ctly as a CPX FMT project Undocumented changes can subsequently be identified using the online offline comparison function On site tests such as the actuation of valves or the emulation of sensor feed...

Page 37: ...rop feature You can insert and move modules 1 Module numbers from the graphic system overview 2 Catalogue for selecting required modules Module overview for a selected module Displays important module...

Page 38: ...inal CPX P Technical data CPX Maintenance Tool Dimensions Download CAD data www festo com Adapter 1 Mini B 5P USB port 2 Plug M12x1 5 pin Ordering data Designation Part No Type CPX P Maintenance Tool...

Page 39: ...in the input table of the controller In addition to cyclic data transmis sion acyclic communication is sup ported through explicit messaging which enables detailed device diagnostics and parameterisat...

Page 40: ...channel oriented diagnostics by means of manufacturer specific diagnostic object Parameterisation Module and system parameterisation via configuration interface in plain text EDS Online in run or prog...

Page 41: ...g Incoming 1 Blank Screened Connection to housing 2 Red 24 V DC bus 24 V DC supply for CAN interface 3 Black 0 V bus 0 V CAN interface 4 White CAN_H Received transmitted data high 5 Blue CAN_L Receive...

Page 42: ...BA 2 M12 5POL Socket for Micro Style connection M12 18324 FBSD GD 9 5POL Plug for Micro Style connection M12 175380 FBS M12 5GS PG9 Open Style bus connection for 5 pin terminal strip 525634 FBA 1 SL 5...

Page 43: ...n Part No Type User documentation User documentation for bus node CPX FB11 German 526421 P BE CPX FB11 DE English 526422 P BE CPX FB11 EN Spanish 526423 P BE CPX FB11 ES French 526424 P BE CPX FB11 FR...

Page 44: ...to EN 50170 Volume 2 for cyclic I O exchange parameterisation and diagnostic functions DPV0 In addition to DPV0 acyclic commu nication to the advanced specification DPV1 is supported DPV1 provides ac...

Page 45: ...t up parameterisation via configuration interface in plain text GSD Acyclic parameterisation via DPV1 Additional functions Storage of the last 40 errors with timestamp access via DPV1 8 bit system sta...

Page 46: ...trol signal 5 DGND Data reference potential M5V 6 VP Supply voltage P5V 7 n c Not connected 8 RxD TxD N Received transmitted data N 9 n c Not connected Hous ing Screened Connection to housing Bus conn...

Page 47: ...PX AB 2 M12 RK DP Socket M12x1 5 pin straight for self assembly of a connecting cable compatible with FBA 2 M12 5POL RK and CPX AB 2 M12 RK DP 1067905 NECU M B12G5 C2 PB Plug M12x1 5 pin straight for...

Page 48: ...n Part No Type User documentation User documentation for bus node CPX FB13 German 526427 P BE CPX FB13 DE English 526428 P BE CPX FB13 EN Spanish 526429 P BE CPX FB13 ES French 526430 P BE CPX FB13 FR...

Page 49: ...stic information configuration information etc can be transferred The Ethernet bandwidth is sufficient to transfer both data types real time and non real time in parallel The bus node features LEDs fo...

Page 50: ...nal functions Start up parameterisation in plain text via fieldbus Fast startup FSU Channel oriented diagnostics via fieldbus Acyclic data access via fieldbus System status can be represented using pr...

Page 51: ...1 Bus specific status LEDs 2 CPX P specific status LEDs 3 Fieldbus connection 4 pin socket M12 D coded 4 Transparent cover for DIL switch and memory card Pin allocation for the fieldbus interface Pin...

Page 52: ...er for DIL switch and memory card 548757 CPX AK P Function block Memory card for PROFINET bus node 2 MB 568647 CPX SK 2 Screws Screws for attaching an inscription label holder to the bus node 12 piece...

Page 53: ...pply for electronics mA Typically 75 Nominal operating voltage V DC 24 reverse polarity protected Permissible voltage fluctuations 25 Power failure buffering ms 20 Residual ripple Vss 0 4 Electrical i...

Page 54: ...module CPX P 8DE N IS has additional safety measures for pos sible faults such as non resettable fuses to ensure safe operation as per the ignition protection type If the module is operated within th...

Page 55: ...CPX P 8DE N CPX P 8DE N IS CPX P AB 4XM12 4POL 565706 n CPX P AB 2XKL 8POL 565704 n CPX P AB 4XM12 4POL 8DE N IS 565705 n CPX P AB 2XKL 8POL 8DE N IS 565703 n Pin allocation Connection block outputs C...

Page 56: ...NECU L3G8 C1 IS1 Screw terminal Black 565710 NECU L3G8 C2 Gentian blue 565709 NECU L3G8 C2 IS1 Plug M12 4 pin Spring loaded terminal For cable 4 8 mm 575719 NECU M S A12G4 IS1 Screw terminal For cabl...

Page 57: ...8DE CPX 8NDE Number of inputs 8 8 Max residual current of inputs per module A 1 0 7 Fuse protection Internal electronic fuse per module Intrinsic current consumption at operating voltage mA Typically...

Page 58: ...OL 549367 n n Pin allocation Connection block inputs CPX 8DE and CPX 8NDE CPX AB 8 M8 3POL X1 1 24 VSEN x X1 3 0 VSEN x X1 4 Input x X5 1 24 VSEN x 4 X5 3 0 VSEN x 4 X5 4 Input x 4 X2 1 24 VSEN x 1 X2...

Page 59: ...24 VSEN x 3 X4 1 0 VSEN x 3 X4 2 Input x 3 X4 3 FE X8 0 24 VSEN x 7 X8 1 0 VSEN x 7 X8 2 Input x 7 X8 3 FE CPX AB 1 SUB BU 25POL 1 Input x 2 Input x 1 3 Input x 2 4 Input x 3 5 24 VSEN x 1 6 0 VSEN x...

Page 60: ...L Distributor Modular system for all types of sensor actuator distributor NEDY Internet nedy 1x plug connector M12 4 pin 2x socket M8 3 pin 8005311 NEDY L2R1 V1 M8G3 N M12G4 2x socket M12 5 pin 800531...

Page 61: ...KL 4POL IP65 IP67 8 cable throughfeeds M9 1 cable throughfeed for multi pin plug 538219 AK 8KL Fittings kit 538220 VG K M9 Screening plate Screening plate for M12 connections 526184 CPX AB S 4 M12 Use...

Page 62: ...al current of inputs per module A 1 8 Intrinsic current consumption at operating voltage mA Typically 15 Fuse protection Internal electronic fuse for each module Nominal operating voltage V DC 24 Oper...

Page 63: ...2 4POL 541256 n CPX AB 8 KL 4POL 195708 n CPX AB 1 SUB BU 25POL 525676 n Pin allocation Connection block inputs CPX 16DE CPX AB 8 M8x2 4POL X1 1 24 VSEN X1 2 Input x 1 X1 3 0 VSEN X1 4 Input x X5 1 24...

Page 64: ...0 VSEN X6 2 Input x 5 X6 3 FE X3 0 Input x 10 X3 1 24 VSEN X3 2 Input x 2 X3 3 FE X7 0 Input x 14 X7 1 0 VSEN X7 2 Input x 6 X7 3 FE X4 0 Input x 11 X4 1 24 VSEN X4 2 Input x 3 X4 3 FE X8 0 Input x 1...

Page 65: ...8 S Sub D plug 25 pin 527522 SD SUB D ST25 Connecting cable For push in T connector 1x socket M8 3 pin 1x plug connector M8 3 pin 0 5 m 541346 NEBU M8G3 K 0 5 M8G3 1 0 m 541347 NEBU M8G3 K 1 M8G3 2 5...

Page 66: ...ction and diagnostics through integrated electronic fuse protection General technical data Type CPX 4AE U I Voltage input Current input Number of analogue inputs 4 Max power supply per module A 0 7 Fu...

Page 67: ...oothing Signal range per channel Wire break monitoring per channel Behaviour after short circuit Behaviour after overload at input Sensor supply active Protection class to EN 60529 Depending on connec...

Page 68: ...CPX AB 4 M12X2 5POL R1 and CPX M AB 4 M12X2 5POL X1 1 24 VSEN X1 2 Input 0 X1 3 0 VSEN X1 4 Input 0 X1 5 FE2 X3 1 24 VSEN X3 2 Input 2 X3 3 0 VSEN X3 4 Input 2 X3 5 FE2 X2 1 24 VSEN X2 2 Input 1 X2 3...

Page 69: ...tion block inputs CPX 4AE U I CPX AB 1 SUB BU 25POL 1 Input 0 2 Input 0 3 Input 1 4 Input 1 5 n c 6 n c 7 n c 8 n c 9 24 VSEN 10 24 VSEN 11 0 VSEN 12 0 VSEN 13 Screening1 14 Input 2 15 Input 2 16 Inpu...

Page 70: ...AB 4 M12X2 5POL Plug Plug M12 5 pin PG7 for cable 4 6 mm 175487 SEA M12 5GS PG7 Sub D plug 25 pin 527522 SD SUB D ST25 Connecting cable Modular system for connecting cables NEBU Internet nebu Cover H...

Page 71: ...load 4 channels can be connected in parallel 0 5 12 W lamp load 8 channels can be connected in parallel Fuse protection short circuit Internal electronic fuse for each channel Module current consumpt...

Page 72: ...L 4POL 195708 n n CPX AB 1 SUB BU 25POL 525676 n n CPX AB 4 HAR 4POL 525636 n n CPX M AB 4 M12X2 5POL 549367 n n Pin allocation Connection block outputs CPX 4DA CPX 8DA CPX AB 8 M8 3POL X1 1 n c X1 3...

Page 73: ...x 1 X1 3 0 VOUT X1 4 Output x X1 5 FE X3 1 n c X3 2 Output x 3 X3 3 0 VOUT X3 4 Output x 2 X3 5 FE X1 1 n c X1 2 Output x 1 X1 3 0 VOUT X1 4 Output x X1 5 FE X3 1 n c X3 2 Output x 5 X3 3 0 VOUT X3 4...

Page 74: ...3 Output x 2 4 Output x 3 5 n c 6 0 VOUT 7 n c 8 0 VOUT 9 n c 10 n c 11 0 VOUT 12 0 VOUT 13 FE 14 Output x 4 15 Output x 5 16 Output x 6 17 Output x 7 18 n c 19 n c 20 n c 21 n c 22 0 VOUT 23 0 VOUT...

Page 75: ...Y L2R1 V1 M8G3 N M8G4 1x plug M12 4 pin 2x socket M12 5 pin 8005311 NEDY L2R1 V1 M8G3 N M12G4 2x socket M8 3 pin 8005310 NEDY L2R1 V1 M12G5 N M12G4 Plug M8 3 pin Solderable 18696 SEA GS M8 Screw in 19...

Page 76: ...KL Fittings kit for hood AK 8KL 538220 VG K M9 Cover cap for sealing unused connections 10 pieces For M8 connections 177672 ISK M8 For M12 connections 165592 ISK M12 Screening plate Screening plate fo...

Page 77: ...c fuse protection General technical data Type CPX 2AA U I Voltage output Current output Number of analogue outputs 2 Max actuator supply per module A 2 8 Fuse protection Internal electronic fuse for a...

Page 78: ...ort circuit monitoring actuator supply Short circuit monitoring analogue output Behaviour after short circuit actuator supply Data format Lower limit value full scale value Upper limit value full scal...

Page 79: ...X1 3 FE X5 0 24 VOUT X5 1 0 VOUT X5 2 Output GND X5 3 FE X2 0 n c X2 1 n c X2 2 Output U0 X2 3 FE X6 0 n c X6 1 n c X6 2 Output U1 X6 3 FE X3 0 24 VOUT X3 1 0 VOUT X3 2 Output GDN X3 3 FE X7 0 24 VOUT...

Page 80: ...G7 for cable 4 6 mm 175487 SEA M12 5GS PG7 Sub D plug 25 pin 527522 SD SUB D ST25 Connecting cable Modular system for all types of sensor actuator distributor NEDY Internet nedy Modular system for con...

Page 81: ...fuse protection General technical data Type code CPX 4AE 4AA H Protocol HART Number of selectable analogue inputs outputs 4 Sensor type 0 20 mA 4 20 mA 4 20 mA with HART Operating voltage Nominal val...

Page 82: ...Housing PA reinforced PC Note on materials RoHS compliant Operating and environmental conditions Ambient temperature C 5 50 Storage temperature C 20 70 Relative humidity 95 non condensing Corrosion r...

Page 83: ...rror Combinations of bus nodes control blocks with HART input output module Bus node control block Part No Protocol HART input output module CPX 4EA 4AA H CPX FB13 195740 PROFIBUS n CPX FB33 548755 PR...

Page 84: ...X4 2 0 V X4 3 Input x 3 X4 4 0 V X2 1 Output I1 X2 2 0 V X2 3 X2 4 0 V X4 1 Output I3 X4 2 0 V X4 3 X4 4 0 V CPX P AB 2XKL 8POL X1 1 24 VSEN x X1 2 0 V X1 3 Input x X1 4 0 V X2 1 24 VSEN x 2 X2 2 0 V...

Page 85: ...cting cross section 0 2 2 5 mm2 565710 NECU L3G8 C2 Plug M12x1 4 pin straight A coded Insulation displacement connector Connecting cross section 0 25 0 5 mm2 525928 SEA GS HAR 4POL Screw terminal Conn...

Page 86: ...minal 24 V DC supply voltage for inputs 24 V DC supply voltage for valves 24 V DC supply voltage for outputs General technical data Nominal operating voltage V DC 24 Protection class to EN 60529 Depen...

Page 87: ...ck 5 pin 550208 CPX M GE EV S 7 8 5POL For ATEX environment 8022165 CPX M GE EV S 7 8 5POL VL 7 8 connection sockets Power supply socket 5 pin 543107 NECU G78G5 C2 Angled socket 5 pin open cable end 5...

Page 88: ...rs and actuators individually Applications All voltages are fed through to the next module by means of interlinking blocks The connected electronics module for inputs outputs or bus node taps off the...

Page 89: ...g data Designation Part No Type Interlinking block without supply Metal interlinking block 550206 CPX M GE EV Mounting accessories Screws for mounting the bus node connection block on an interlinking...

Page 90: ...off specific areas of the sensors and actuators individually Applications 24 V DC supply voltage for outputs General technical data Nominal operating voltage V DC 24 Protection class to EN 60529 Depe...

Page 91: ...al interlinking block 5 pin 550210 CPX M GE EV Z 7 8 5POL 5 pin For ATEX environment 8022158 CPX M GE EV Z 7 8 5POL VL 7 8 connection sockets Power supply socket 5 pin 543107 NECU G78G5 C2 Angled sock...

Page 92: ...s module of the valve terminal MPA S can be parameterised for example status of the solenoid coils in the event of fieldbus communication being interrupted fail safe individual channel diagnostics can...

Page 93: ...ings Ordering data Designation Part No Type Pneumatic interface Ducted exhaust air internal pilot air 552286 VMPA FB EPLM G Ducted exhaust air external pilot air 552285 VMPA FB EPLM E Flat plate silen...

Page 94: ...onnection block CPX AB 8 KL 4POL 6 Connection block CPX AB 1 SUB BU 25POL 7 Connection block CPX P AB 4 2XKL 8POL 8 Connection block CPX P AB 4XM12 4POL 9 Right hand end plate aJ Mounting bracket for...

Page 95: ...y plate aC Pressure sensor aD Proportional pressure regulator n Number of sub bases in a grid of 4 MPA1 or 2 MPA2 valves m Number of CPX P modules Type B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 C...

Page 96: ...nal D coded For Ethernet 543109 NECU M S D12G4 C2 ET For cable 2 5 2 9 mm 570955 NECU S M12G4 P1 Q6 IS1 192008 SEA 4GS 7 2 5 For cable 2x3 mm or 2x5 mm 570956 NECU S M12G4 D IS1 For 2x cable 3 5 mm 18...

Page 97: ...dy Modular system for connecting cables NEBU Internet nebu Push in T connector 1x plug M8 4 pin 2x socket M8 3 pin 8005312 NEDY L2R1 V1 M8G3 N M8G4 1x plug M12 4 pin 2x socket M8 3 pin 8005311 NEDY L2...

Page 98: ...200 300 mm 572259 CAFC X1 GAL 300 Screws Screws for mounting the bus node connection block on an interlinking block Bus node plastic connection block 550219 CPX M M3x22 4x Bus node metal connection bl...

Page 99: ...tch and memory card 548757 CPX AK P Cover for RJ45 connection 534496 AK Rj45 Cover cap for sealing unused connections 10 pieces For M8 connections 177672 ISK M8 For M12 connections 165592 ISK M12 Codi...

Reviews: