![Festo CPX-P User Manual Download Page 27](http://html1.mh-extra.com/html/festo/cpx-p/cpx-p_user-manual_2284200027.webp)
2018/04 – Subject to change
27
è
Internet: www.festo.com/catalogue/...
Terminal CPX-P
Technical data
General technical data
Module No.
562818
Parameterisation
Module-specific and entire system, for example:
Diagnostic behaviour
Condition monitoring
Profile of inputs
Fail-safe response of outputs and valves
Commissioning support
Forcing of inputs and outputs
Nominal operating voltage
[V DC]
24
Operating voltage range
[V DC]
18 … 30
Power supply
Interlinking block with system
supply for
electronics plus sensors
actuators plus valves
[A]
[A]
8
8
Additional power supply for
actuators
[A]
8
Current consumption
Depending on system configuration
Power failure bridging (bus electronics only)
[ms]
10
Power supply connection
7/8", 5-pin
Fuse concept
Per module with electronic fuses
Tests
Vibration test to DIN IEC 68
With wall mounting: Severity level 2
With H-rail mounting: Severity level 1
Shock test to DIN IEC 68
With wall mounting: Severity level 2
With H-rail mounting: Severity level 1
PWIS classification
PWIS-free (free of paint-wetting impairment substances)
Interference immunity
EN 61000-6-2 (industry)
Interference emission
EN 61000-6-4 (industry)
Isolation test for galvanically isolated circuits to IEC 1131 Part 2
[V DC]
500
Galvanic isolation of electrical voltages
[V DC]
80
Protection against direct and indirect contact
PELV (Protective Extra-Low Voltage)
Materials
End plates: Die-cast aluminium
Grid dimension
[mm]
50
Operating and environmental conditions
Module No.
562818
Ambient temperature
[°C]
–5 … +50
Storage temperature
[°C]
–20 … +70