CPX-FVDA-P...
Festo CPX-FVDA-P... 1011NH English
33
Technical data
CPX-FVDA-P
– Max. peak current per channel
[A]
5, for t < 50 ms
– Max. residual current per module
[A]
5
– Voltage drop per channel under
continuous load
[V]
max. 0.6
– Wire break detection (CH1, CH2)
Configurable, I
L
< approx. 50 mA
– Cable length (CH1, CH2)
[m]
max. 200
– Load capacitance to FE
[nF]
max. 100
– Load capacitance P-M
[µF]
max. 2.2
– Load inductance
[mH]
1000 at 150 mA, 100 at 600 mA;
for characteristic curve, see manual for
type P.BE-CPX-SYS-F-...
– Fuse protection (short circuit)
Internal electrical fuse per channel
– Switching logic at outputs
PM switching
Function characteristic values
– Module code
193d (C1h)
– Sub-module code
1d (01h)
Safety characteristic values
– Safety function
– Safe disconnection of output channels in
compliance with EN 61508 with SIL3
– Safe disconnection of output channels in
compliance with ISO 13849 with Cat. 3
and PL e
– Safe disconnection of output channels in
compliance with EN 62061 with SIL CL3
– Safety Integrity Level (SIL)
Safe disconnection/SIL 3
– Performance level (PL)
Safe disconnection / Kat. 3, PI e
– Disconnection scheme by channel
P and M switching
– Diagnosis of external channel faults
– Cyclic functional check
– Cyclic check for external feed
– Cyclic check for cross circuit