Festo CPX-AX 1107d English
26
Input module CPX-4AE-U-I
(continuation)
Voltage inputs
Current inputs
– Potential connection to FE
– Sensor supply
– Output voltage
– Load capacity
– Fuse
– Behaviour after end of
overload
– Inverse polarity protection
24 V load input
– Inverse voltage resistance
High-impedance, capacitive
connection
One connection per sensor, same
supply potential at all connections,
generation from V
EL/SEN
DC 24 V ± 25 %
1.4 A (max. permanent current per
module)
Electronic, thermal
(Response current: 1.4 to 4.5 A)
Can be parametrised
(s. description P.BE-CPX-AX...)
Yes
Max. 30 V
– Electrical isolation
– Between channel and
24 V
SEN
– Between the channels
Yes (release electrical isolation by
using the internal sensor supply)
No
Summary of Contents for CPX-2AA Series
Page 16: ...Festo CPX AX 1107d Deutsch 16...
Page 30: ...Festo CPX AX 1107d English 30...
Page 44: ...Festo CPX AX 1107d Espa ol 44...
Page 58: ...Festo CPX AX 1107d Fran ais 58...
Page 72: ...Festo CPX AX 1107d Italiano 72...
Page 73: ...Festo CPX AX 1107d 73 1 CPX CPX CPX CPX CPX P BE CPX AX CPX P BE CPX SYS CPX CPX...
Page 74: ...Festo CPX AX 1107d 74 2 1 2 DIL 3 3 3 4 5 LED 6 0 9 1 1 Nm 1 2 3 4 5 6 LED LED LED...
Page 76: ...Festo CPX AX 1107d 76 3 2 2 1 6 1 2 2 2 1 3 2 3 0 9 1 1 Nm...
Page 78: ...Festo CPX AX 1107d 78 3 4 CPX P BE CPX AX 30 m FE FE FE FE FE...
Page 86: ...Festo CPX AX 1107d 86...