3. Output modules type CP−A04−M12−CL
3−11
Festo P.BE−CPEA−CL−E N en 0404NH
Status LED
Load supply (PL)
Short circuit or overload of the actuator supply is shown by
means of the status LED short circuit/overload
(see Tab.3/4).
LED PL
(green)
Sequence
Operating status
Fault treatment
LED lights up
ON
OFF
Load supply OK
None
LED flashes
ON
OFF
Undervoltage in actuator
supply (< 17 V)
·
Check the CP cable and the
operating voltage connection
on the CP master
LED is out
ON
OFF
Load supply missing
·
Check the CP cable and the
operating voltage connection
on the CP master
Tab.3/4:
Status LED load supply (PL)
Status LEDs
Status display of output
Next to the actuator connections there is a yellow LED for
every output. This shows the status of the signal at the
relevant output.
LED status
of output
Sequence
Status
LED lights up
ON
OFF
Output supplies 1−signal
LED is out
ON
OFF
Output supplies 0−signal
Tab.3/5:
Status LEDs for status display of output
Summary of Contents for CP-A04-M12-CL
Page 2: ......
Page 4: ...Contents and general instructions II Festo P BE CPEA CL EN en 0404NH...
Page 14: ...Contents and general instructions XII Festo P BE CPEA CL EN en 0404NH...
Page 15: ...System summary CP system 1 1 Festo P BE CPEA CL EN en 0404NH Chapter 1...
Page 28: ...1 System summary CP system 1 14 Festo P BE CPEA CL EN en 0404NH...
Page 29: ...Input modules type CP E08 M CL and CP E16 KL CL 2 1 Festo P BE CPEA CL EN en 0404NH Chapter 2...
Page 46: ...2 Input modules type CP E08 M CL and CP E16 KL CL 2 18 Festo P BE CPEA CL EN en 0404NH...
Page 47: ...Output modules type CP A04 M12 CL 3 1 Festo P BE CPEA CL EN en 0404NH Chapter 3...
Page 60: ...3 Output modules type CP A04 M12 CL 3 14 Festo P BE CPEA CL EN en 0404NH...
Page 61: ...Technical appendix A 1 Festo P BE CPEA CL EN en 0404NH Appendix A...
Page 81: ...Index B 1 Festo P BE CPEA CL EN en 0404NH Appendix B...
Page 82: ...B Index B 2 Festo P BE CPEA CL EN en 0404NH Contents B Index B 1 B 1 Index B 3...