3.1.3 Diagnosis of node-specific LEDs
The table below contains possible node-specific LED
displays of the operating status of the CP node.
1. Error displays of operating status (red), fault (green);
( = lights up; = LED flashes; = out)
LEDs
Operating status
Error treatment
red
green
Line x
Normal, but valves do not switch
Check the ...
•
operating voltage of
the valves (tolerance range
20.4 V .. 26.4 V)
•
compressed air supply
red
green
Operating voltage not applied
Check the ...
•
operating voltage (pin 1 on
node)
red
green
Line x
No communication with
RIO network
Check the ...
•
configuration of the RIO
slaves, or correct the
•
address
•
baud rate
•
RIO cable
red
green
(fast)
- Controller has issued a RESET
command or
- controller not in operating
status RUN or
- incorrect address setting or
- PLC configuration or
line assignment different
•
Check program
•
Set operating status RUN
•
Correct address
•
Check PLC configuration or
line assignment;
•
Operating voltage on the node:
OFF, then ON.
red
green
(briefly out)
Hardware fault
Servicing required
3. Diagnosis
CP FB8 9809a
3-5
Summary of Contents for Compact Performance Series
Page 2: ......
Page 12: ...Contents and general safety instructions X CP FB8 9809a...
Page 13: ...Chapter 1 Installation 1 Installation CP FB8 E 9809a 1 1...
Page 28: ...1 Installation 1 16 CP FB8 E 9809a...
Page 29: ...Chapter 2 Commissioning 2 Commissioning CP FB8 9809a 2 1...
Page 43: ...Chapter 3 Diagnosis 3 Diagnosis CP FB8 9809a 3 1...
Page 51: ...Appendix A Technical appendix A Technical appendix CP FB8 9809a A 1...