CMSX-...-C-U-F1-...
34
Festo – CMSX-...-C-U-F1-... – 1506a English
7.6.6
Menu configuration (2)
Display
Description
MENU 2 CONFIG
SIGNAL
Establishes the active setpoint value input and the type of setpoint value signal
0-10 V
Voltage input (pin 1, 2); 0 ... 10 V
4-20 mA
Current input (pin 3, 4); 4 ... 20 mA (presetting)
0-20 mA
Current input (pin 3, 4); 0 ... 20 mA
Open
1)
Specifies in which direction the process valve opens (semi-rotary drives only).
clockwis
Clockwise
anti-clk
Anti-clockwise (presetting)
DIRECT
Establishes the signal direction for increasing the setpoint position (SP) (
è
increase
Increasing setpoint value signal (presetting)
decrease
Decreasing setpoint signal
CHARACTE
Character of the setpoint value characteristics curve
linear
Linear characteristic curve (presetting); linear ratio between ana
logue setpoint value and setpoint position (
è
1 : 25
Equal-percentage characteristic curve (
è
1 : 33
1 : 50
user-def
User-defined setpoint value characteristic curve (
è
D-OUT-1
D-OUT-2
Establishes the behaviour of the two status outputs (D-OUT-1, D-OUT-2).
power-H
High level if load voltage supply is present for outputs
power-L
Low level if load voltage supply is present for outputs (presetting)
limit1-H
High level, if end position 1 is reached
limit1-L
Low level, if end position is 1 reached
limit2-H
High level, if end position 2 is reached
limit2-L
Low level, if end position 2 is reached
limits-H
High level, if end position 1 or end position 2 is reached
limits-L
Low level, if end position 1 or end position 2 is reached
stop-H
High level, if CMSX is in the operating status “Actuat stopped”
stop-L
Low level, if CMSX is in the operating status “Actuat stopped”
D-IN
Establishes the reaction to a signal at the digital input D-IN. The controller is then
inactive. Either both of the working ports of the device are pressurized in order to
stop or one working port is pressurized and one is exhausted.
stop-H
In the case of High level, stop drive (presetting)
stop-L
In the case of Low level, stop drive
lmt1-H
In the case of High level, travel to stop 1
lmt1-L
In the case of Low level, travel to stop 1
lmt2-H
In the case of High level, travel to stop 2
lmt1-L
In the case of Low level, travel to stop 2
1)
Submenu only available for CMSX-S-... (rotary)
Tab. 16
Menu configuration (2)