- 21 -
6.5 Notes on the connections
The panel power cable, type FG7 RN-F 3G1,5,
is already connected as standard to the termi-
nal block. In the event of replacement, make
sure an appropriate cable is used, according to
the legislation in force. The power supply to the
burner is taken directly from the terminal block,
single-phase and with a maximum current
input of 3A. The power supply to the system
water pump is taken directly from the terminal
block, single-phase and with a maximum cur-
rent input of 3A. If the current input of the bur-
ner or the pump is higher than envisaged, or
the power supply is three-phase, power relays
must be connected to the outputs on the termi-
nal block. The remote start enabling signal
allows the boiler to be operated from a distan-
ce. This is jumpered when not used. The exter-
nal boiler safety enabling signal represents a
further contact that is used to stop the burner.
This is jumpered when not used. The room
thermostat contact only controls the water
pump. This is jumpered when not used.
7. PRINCIPLE DIAGRAM - SYSTEM FOR
CENTRAL HEATING AND THE PRODUCTION
DI DOMESTIC HOT WATER
(Fig. 18)
The choice and installation of the components
making up the system is left to the expertise of
the installer, who must operate in a workmanlike
manner and according to the legislation in force.
The systems loaded with antifreeze require the
use of water disconnecting devices. It should be
stressed that the diagram in Fig. 18 is a princi-
ple diagram. In the case of different systems,
please contact our After-Sales Service, which
will provide you all the details required.
Key
A
Central heating flow outlet
B
Central heating return inlet
1
Heat generator
2
Burner complete with shutdown
and control valves
3
Storage heater
4
System manifolds
5
On-off valves
6
Circulating pump
7
Non-return valves
8
System expansion vessel
9
Automatic vent valve
10
Safety valve
11
Softener filter
12
System fill
13
Fuel on-off valve
14
Gas pressure stabiliser
15
Manual on-off valve
16
Gas filter
17
Vibration-damping joint
18
Pump
19
Pressure gauge
20
Safety thermostat
21
Control thermostat
22
Three-way cock
23
Pressure switch with manual reset
24
Flow switch
25
Control thermostat
26
Thermostat with manual reset
27
Temperature test socket
28
Temperature control valve
8. COMMISSIONING
8.1 Preliminary checks
Once having completed the water, electrical and
fuel connections to the boiler, before starting,
check that:
- The expansion vessel and the safety valve (if
required) are connected correctly and cannot
be shut-off.
- The bulbs of the thermostats and the thermo-
meter are secured inside the corresponding
sheaths.
- The turbulators are positioned in all the flues.
- The system is filled with water and completely
vented of air.
- The pump or the pumps are working properly.
- The water, electrical, safety device and fuel
connections have been performed in com-
pliance with the national and local legislation
in force.
- The burner is installed according to the
instructions contained in the manual provided
by the manufacturer.
- The mains voltage and frequency are compati-
ble with the rating of the burner and the boi-
ler’s electrical equipment.
- The system is able to absorb the quantity of
heat that will be produced.
- The recirculating pump is installed, as descri-
bed in par. 5.5.5.
8.2 Starting for the first time
After the positive outcome of the checks descri-
bed in the previous paragraph, the burner can
be ignited for the first time; this operation must
be performed by a technician who has been
authorised by the Manufacturer of the burner.
The technician has full responsibility as regards
the field of calibration, within the declared and
Key to the symbols/components on the wiring diagram
Water outlet temperature
Boiler status/Water temperature instrument
System water pump
Remote start enabling signal
External safety enabling signal
Room thermostat
Boiler ON switch
Burner switch
Pump switch
Test button
1
st
burner stage thermostat
2
nd
burner stage thermostat
Boiler safety thermostat
GB
Summary of Contents for PREXTHERM RSH 1100
Page 1: ...PREXTHERM RSH Caldaie ad Altissimo Rendimento Very high efficiency boilers...
Page 2: ......
Page 110: ...6 4 17 110 Fig 17 1 2 1 2 2...
Page 112: ...160 8 3 112 9 O C BAH E 9 1 9 2 300 9 3 9 4 19 1 2 3 4 5 6 9 5 1 30 2 3 9 6 9 7...
Page 113: ...113 RU...
Page 115: ...Fig 5 Fig 4...
Page 116: ...Fig 7 Fig 8 3 5D D Fig 6...
Page 117: ...Fig 9 1 2 3 4 5 6 7 Fig 10...
Page 118: ...Fig 12 L A Fig 11...
Page 120: ...Fig 15 C B A C Fig 16 5 4 3 2 1 14 13 12 6 7 8 1011 9 Fig 18...
Page 121: ...Fig 19...
Page 122: ...Fig 20 Fig 21...
Page 123: ......