Ferroli PEGASUS 119 LN 2S Instructions For Use, Installation And Maintenance Download Page 28

PEGASUS LN 2S

28

EN

EN

1. GENERAL WARNINGS

Carefully read and follow the instructions contained in this instruction booklet.

After boiler installation, inform the user regarding its operation and give him this
manual, which is an integral and essential part of the product and must be kept with
care for future reference.

Installation and maintenance must be carried out by professionally qualified person-
nel, in compliance with the current regulations and according to the manufacturer's
instructions. Do not carry out any operation on the sealed control parts.

Incorrect installation or inadequate maintenance can result in damage or injury. The
Manufacturer declines any liability for damage due to errors in installation and use,
or failure to follow the instructions.

Before carrying out any cleaning or maintenance operation, disconnect the unit from
the electrical power supply using the switch and/or the special cut-off devices.

In case of a fault and/or poor operation, deactivate the unit and do not try to repair
it or directly intervene. Contact professionally qualified personnel. Any repair/re-
placement of the products must only be carried out by qualified personnel using orig-
inal replacement parts. Failure to comply with the above could affect the safety of
the unit.

This unit must only be used for its intended purpose. Any other use is deemed im-
proper and therefore hazardous.

The packing materials are potentially hazardous and must not be left within the
reach of children.

The unit must not be used by people (including children) with limited physical, sen-
sory or mental abilities or without experience and knowledge of it, unless instructed
or supervised in its use by someone responsible for their safety.

The unit and its accessories must be appropriately disposed of, in compliance with
the current regulations.

The images given in this manual are a simplified representation of the product. In
this representation there may be slight and insignificant differences with respect to
the product supplied.

2. OPERATING INSTRUCTIONS
2.1 Introduction

Dear Customer,
Thank you for choosing 

PEGASUS LN 2S

, a floor-standing boiler 

FERROLI

 featuring

advanced design, cutting-edge technology, high reliability and quality construction.
Please read this manual carefully and keep it for future reference.
PEGASUS LN 2S is a high-efficiency heat generator with 

low NOx emissions

 for central

heating, running on natural gas or liquefied gas, equipped with an advanced electronic
control system.
The boiler shell consists of cast iron elements whose particular shape guarantees high
exchange efficiency in all operating conditions and an open-flue burner equipped with
electronic ignition and ionisation flame control.
Partial (1st stage) or total (1st + 2nd stage) burner ignition enables the unit to supply two
separate outputs according to system requirements.
The boiler also has an automatic boiler air vent valve, a 2-stage control thermostat and
a safety thermostat.
Thanks to the electronic ignition and flame control system, unit operation is for the most
part automatic.
The user only has to set the system temperature by means of the control thermostat.

2.2 Control panel

To access the control panel, lift the front door.

fig. 1 - Control panel

Key

1

Prearrangement for thermostatic controller

2

Boiler pressure/temperature gauge

3

Manual reset safety thermostat cover

4

Cap

5

Flame control reset button with 1st stage shutdown indicator

6

Flame control reset button with 2nd stage shutdown indicator

7

2-stage boiler control thermostat

8

0 - 1 - TEST switch

2.3 Turning on and off
Lighting

Open the gas cock ahead of the boiler.

Turn on or insert any switch or plug ahead of the boiler.

Turn the boiler switch “8” to 1 (fig. 1).

Turn the knob "7" to the required temperature and that of a possible room thermostat
to the required temperature value. The burner will light and the boiler begins to func-
tion automatically, controlled by its adjustment and safety devices.

If the boiler is equipped with an electronic thermostatic controller fitted in position 1
of fig. 1, the user must also take into account the manufacturer's instructions.

A

If, after correctly carrying out the lighting procedures, the burners do not light
and buttons-shutdown indicator "5 - 6" come on, wait about 15 seconds then
press the above-mentioned buttons. The flame controllers reset in this way will
repeat the lighting cycle. If the burners do not light after several attempts, con-
sult the faults section.

A

In case of a power failure while the boiler is working, the burners will go out and
relight automatically when the power is restored.

Turning off

Close the gas cock ahead of the boiler, turn knob "8" to 0 and disconnect the power.

B

To avoid damage caused by freezing during long shutdowns in winter, it is ad-
visable to drain all water from the boiler and system; or add a suitable antifreeze
to the heating system.
The boiler switch 8 has 3 positions “0-1-TEST”; the first two have the on-off
function, the third (unstable) must only be used for service and maintenance
purposes.

2.4 Adjustments
System temperature adjustment

Turn the knob 7 of fig. 1 clockwise to increase the heating water temperature, or anti-
clockwise to decrease it. The temperature can be varied from a minimum of 30°C to a
maximum of 90°C. However, it is advisable not to operate the boiler below 45°C.

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the required temperature in the rooms. By command of
the room thermostat, the boiler lights and brings the system water to the temperature set
by boiler adjustment thermostat 7 of fig. 1. The generator turns off when the required
temperature in the rooms is reached.
If the room thermostat is not installed the boiler will keep the system at the temperature
set by the boiler control thermostat.

Water system pressure adjustment

The filling pressure with system cold, read on the boiler water gauge detail 2 of fig. 1,
must be approx. 1.0 bar. If, during operation, the system pressure falls (due to the evap-
oration of gases dissolved in the water) to values below the minimum described above,
the user must bring it to the initial value by operating the filling cock. At the end of the
operation always close the filling cock.

2.5 Faults

Given below are the faults that can be caused by simple user-solvable problems.

A

Before calling the after-sales service, check that the problem is not due to no
gas or power.

1

2

3

4

6

7

8

5

Symbol

Faults

Cure

Boiler shutdown by the flame control-
ler

Check if the gas cocks ahead of the boiler and on the 
meter are open.
Press the illuminated indicator-button.
In case of repeated boiler shutdowns, contact the nearest 
service centre.

Boiler shutdown due to insufficient 
system pressure (only if a pressure 
switch is installed in the system)

Fill the system to 1-1.5 bar cold by means of the system 
filling cock.
Close the cock after use.

Boiler shutdown due to water over-
temperature

Unscrew the safety thermostat cover and press the but-
ton below.
In case of repeated shutdowns, contact the nearest serv-
ice centre.

cod. 3540T612  -  Rev. 01 - 02/2015

Summary of Contents for PEGASUS 119 LN 2S

Page 1: ...LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INSTAL...

Page 2: ...nte riarmo centralina controllo fiamma con spia di blocco 2 stadio 7 Termostato di regolazione caldaia a 2 stadi 8 Interruttore 0 1 TEST 2 3 Accensione e spegnimento Accensione Aprire il rubinetto del...

Page 3: ...i spessore provocano a causa della loro bassa conduttivit termica un notevole surriscaldamento delle pareti della caldaia con conse guenti gravi inconvenienti indispensabile il trattamento dell acqua...

Page 4: ...dio Collegare un manometro alla presa di pressione A fig 5 posta a valle delle valvole gas 1 stadio Ruotare la manopola del termostato caldaia al massimo Togliere il tappo di protezione 1 fig 6 delle...

Page 5: ...alla caldaia mentre quest ultima in funzione i bruciatori si spegneranno e si riaccenderanno au tomaticamente al ripristino della tensione di rete Verifiche durante il funzionamento Assicurarsi della...

Page 6: ...odi unicamente con spazzola non metallica o con aria compressa mai con dei prodotti chimici A fine intervento rimontare il tutto in ordine inverso fig 9 Smontaggio e pulizia bruciatori Gruppo bruciato...

Page 7: ...fiamme troppo alte troppo basse o troppo gialle Filtro della valvola gas sporco Controllare la pressione di alimentazione del gas Ugelli gas sporchi Controllare che la caldaia non sia sporca Controll...

Page 8: ...30 50 230 50 230 50 230 50 Indice di protezione elettrica IP X0D X0D X0D X0D MODELLO 187 221 255 289 Potenze Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Portata Termica Potere calorifico Inferiore Hi kW 2...

Page 9: ...tato di sicurezza 72 Termostato ambiente non fornito 82 Elettrodo dl rilevazione 83a Centralina elettronica di comando 1 stadio 83b Centralina elettronica di comando 2 stadio 98 Interruttore 114 Press...

Page 10: ...Garanzia La presente garanzia convenzionale valida per gli apparecchi Z d K d D E s Z E Z E Y d s FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933...

Page 11: ...caldera Conectar el interruptor el ctrico situado antes de la caldera o enchufar el aparato Poner el interruptor de la caldera 8 en la posici n 1 fig 1 Poner el mando 7 en correspondencia de la temper...

Page 12: ...conductividad t rmica muy baja y por consiguiente las paredes de la caldera se calientan en exceso Si la instalaci n es muy grande con una gran cantidad de agua o debe rellenarse a me nudo es indispe...

Page 13: ...los reguladores de presi n presentes en las v lvulas gas 1 Etapa Conectar un man metro a la toma de presi n A fig 5 situada despu s de las v lvulas gas 1 etapa Disponer el mando del termostato caldera...

Page 14: ...a nicamente para fines de servicio y mantenimiento A Si se interrumpe el suministro el ctrico mientras la caldera est en marcha los quemadores se apagan y se vuelven a encender autom ticamente cuando...

Page 15: ...adores y electrodos nicamente con un cepillo no met lico o con aire compri mido nunca con productos qu micos Al terminar la intervenci n montar todos los elementos efectuando las operaciones an terior...

Page 16: ...est cerrado El quemador quema mal llamas dema siado altas bajas o amarillas filtro de la v lvula del gas sucio Controlar la presi n de alimentaci n del gas Inyectores del gas sucios Controlar que la c...

Page 17: ...z 230 50 230 50 230 50 230 50 ndice de protecci n el ctrica IP X0D X0D X0D X0D MODELO 187 221 255 289 Potencias Pm x Pm n Pm x Pm n Pm x Pm n Pm x Pm n Potencia t rmica poder calor fico inferior Hi kW...

Page 18: ...5 289 49 Termostato de seguridad 72 Termostato de ambiente no suministrado 82 Electrodo de detecci n 83a Centralita electr nica de mando 1 etapa 83b Centralita electr nica de mando 2 etapa 98 Interrup...

Page 19: ...la cumplimentaci n de la totalidad de los datos en el Certi cado de Funcionamiento La cumplimenta ci n del certi cado deber realizarse inmediatamente a la P M y consignar la fecha correctamente envi...

Page 20: ...resetleme d mesi 7 2 kademeli kombi kontrol termostat 8 0 1 TEST d mesi 2 3 A ma ve kapatma Ate leme Kombi zerindeki gaz valf n a n z Kombiye monteli sivici a n z veya fi ini tak n z Kombinin sivicin...

Page 21: ...ciddi sorunlar n karabilece inin unutulmamas gerekir ok b y k sistemlerde ok b y k miktarda su i eren sistemler veya sistemde suyun ok s k bir ekilde yeniden ikmal edildi i durumlarda suyu i lemden g...

Page 22: ...verilmi olan teknik veriler tablosundaki de erlere riayet ederek ate leme u lar ndaki bas nc kontrol etmek ve belki ayarlamak gerekecektir Bas nc n ayarlanmas i in yap lacak i lemler kombi al yor ike...

Page 23: ...5 saniye bekleyiniz ve yukar da belirtilen basmal d meye tekrar bas n z Reset kontrol r ate leme devrini tekrar edecektir kinci bir demeden sonra da e er br l rler yanmaz ise paragraf 3 4 Sorunlar n g...

Page 24: ...tronik alev kontrol rlerini gaz valf na sabitleyen iki adet viday s k n z k s m A ek 9 ve bunlar gaz valflar ndan kart n z k s m B ek 9 Konnekt rleri gaz valflar na sabitleyen vidalar s k n z ve bunla...

Page 25: ...ve iyonizasyon elektrotlar n n ba lant lar n kontrol ediniz Elektronik alev kontrol r ndeki ba lant lar kontrol ediniz FAZ ve N TR k sm n ters d nmemi oldu undan ve topraklama kontaklar n n sa l kl o...

Page 26: ...bar 37 37 37 37 Br l r bas nc G31 mbar 35 35 35 35 35 35 35 35 k G31 Kg s 10 26 5 86 11 6 5 86 13 2 7 33 14 64 7 33 NOx Emisyon S n f 5 70 mg kWh Is tma Maksimum al ma s cakl C 100 100 100 100 Is tmad...

Page 27: ...alf sadece u versiyonlarda 153 170 187 221 255 289 49 Emniyet termostat 72 Oda termostat cihazla birlikte verilmez 82 Tespit elektrotu 83a 1 Kademe elektronik kumanda santrali 83b 2 Kademe elektronik...

Page 28: ...e control reset button with 2nd stage shutdown indicator 7 2 stage boiler control thermostat 8 0 1 TEST switch 2 3 Turning on and off Lighting Open the gas cock ahead of the boiler Turn on or insert a...

Page 29: ...prob lems Water treatment is indispensable in case of very large systems containing large amounts of water or with frequent introduction of replenishing water in the system If par tial or total empty...

Page 30: ...ves 1st stage Connect a manometer to pressure point A fig 5 located below the 1st stage gas valve Turn the boiler thermostat knob to maximum Remove the protection cap 1 fig 6 of the gas valves and adj...

Page 31: ...ce and maintenance purposes A In case of a power failure while the boiler is working the burners will go out and relight automatically when the power is restored Checks during operation Make sure the...

Page 32: ...hamber door Check and clean the burners Only use a non metallic brush or compressed air to clean the burners never use chemical products Afterwards refit everything in reverse order to removal fig 9 B...

Page 33: ...The burner burns poorly flames too high too low or too yellow Gas valve filter dirty Check the gas supply pressure Gas nozzles dirty Make sure the boiler is not dirty Make sure the ventilation in the...

Page 34: ...50 230 50 230 50 230 50 Electrical protection rating IP X0D X0D X0D X0D MODEL 187 221 255 289 Powers Pmax Pmin Pmax Pmin Pmax Pmin Pmax Pmin Heating Capacity Net Heat Value Hi kW 206 112 243 131 280...

Page 35: ...187 221 255 289 49 Safety thermostat 72 Room thermostat not supplied 82 Detection electrode 83a 1st stage electronic controller 83b 2nd stage electronic controller 98 Switch 114 Water pressure switch...

Page 36: ...ement de la centrale de contr le de flamme avec vo yant de blocage 2 tage 7 Thermostat de r glage de la chaudi re 2 tages 8 Interrupteur 0 1 TEST 2 3 Allumage et extinction Allumage Ouvrir le robinet...

Page 37: ...agressives Il convient de rappeler que des incrustations m me de l paisseur de quel ques millim tres entra nent cause de leur basse conductivit thermique une sur chauffe consid rable des parois de la...

Page 38: ...pression se font en usine Lors du premier allumage en pr sence de variations de pression de ligne contr ler et r gler la pression aux gicleurs en respectant les valeurs de la table des donn es tech n...

Page 39: ...que les conditions normales de fon ctionnement ont t r tablies l unit de contr le r p tera le cycle d allumage Si m me apr s la seconde tentative les br leurs ne s allument pas consulter le paragraph...

Page 40: ...e des gaz en amont de la chaudi re D visser les 2 vis de fixation de la centrale lectronique de contr le de flamme la vanne de gaz rep A fig 9 et la d senfiler de la vanne de gaz rep B fig 9 D visser...

Page 41: ...e Contr ler les branchements lectriques aux lectrodes d allumage et d ionisa tion Contr ler les branchements lectriques au module lectronique de contr le de flamme V rifier que PHASE et NEUTRE ne soie...

Page 42: ...5 35 35 35 35 35 35 35 D bit G31 kg h 10 26 5 86 11 6 5 86 13 2 7 33 14 64 7 33 Classe d mission NOx 5 70 mg kWh Chauffage Temp rature maximum de r gime C 100 100 100 100 Pression maxi d utilisation c...

Page 43: ...e gaz uniquement versions 153 170 187 221 255 289 49 Thermostat de s curit 72 Thermostat d ambiance non fourni 82 lectrode de d tection 83a Module lectronique de commande 1 tage 83b Module lectronique...

Page 44: ...U RU 1 2 2 1 PEGASUS LN 2S FERROLI PEGASUS LN 2S NOx 1 1 2 2 2 1 1 2 3 4 5 1 6 2 7 2 8 0 1 2 3 8 1 1 7 11 A 5 6 15 A 8 0 B 8 3 0 1 TEST 2 4 17 30 90 45 7 1 12 1 0 2 5 A 1 2 3 4 6 7 8 5 1 1 5 cod 3540T...

Page 45: ...220 50 42 2 2 1 PEGASUS 136 LN 2S 1020 250 53 45 2 2 1 PEGASUS 153 LN 2S 1100 250 58 43 2 2 1 1 2 PEGASUS 170 LN 2S 1190 300 60 46 2 2 1 1 2 PEGASUS 187 LN 2S 1270 300 58 44 2 2 1 1 2 PEGASUS 221 LN...

Page 46: ...G20 G31 G20 G31 G20 G31 G20 PEGASUS 119 LN 2S 37 20 35 15 35 15 2 15 3 40 PEGASUS 136 LN 2S 37 20 35 15 35 15 2 15 3 40 PEGASUS 153 LN 2S 37 20 35 15 35 15 2 15 3 40 PEGASUS 170 LN 2S 37 20 35 15 35...

Page 47: ...A B 1 A B C 2 4 2 B 8 1 1 7 1 50 C B 15 3 4 8 3 0 1 TEST A cap 5 8 1 0 7 1 0 B 4 3 B 10 1 sez 5 3 PEGASUS LN 2S 110 C 10 C Per sbloccare il li mitatore di temperatura si dov svitare il coperchietto 3...

Page 48: ...PEGASUS LN 2S 48 RU 8 1 2 3 4 5 6 10 15 7 8 A A 9 B 9 C 9 D 9 9 10 1 2 3 4 5 6 7 8 11 7 5 11 1 2 3 4 5 3 3 4 mm 5 4 8 3 2 1 4 5 cod 3540T612 Rev 01 02 2015...

Page 49: ...119 LN 2S 930 133 220 50 42 1050 2 2 1 PEGASUS 136 LN 2S 1020 148 250 53 45 1050 2 2 1 PEGASUS 153 LN 2S 1100 148 250 58 43 1050 2 2 1 1 2 PEGASUS 170 LN 2S 1190 173 300 60 46 1050 2 2 1 1 2 PEGASUS...

Page 50: ...IP X0D X0D X0D X0D 187 221 255 289 P P P P P P P P Hi 206 112 243 131 280 149 317 168 187 102 221 119 255 136 289 153 P P P P P P P P G20 G25 2 x 0 32 2 2 x 0 32 2 2 x 0 32 2 2 x 0 32 2 G31 2 x 0 24...

Page 51: ...PEGASUS LN 2S 51 RU 5 5 14 24 32 44 44a 153 170 187 221 255 289 49 72 82 83a 1 83b 2 98 114 116 129 159 170 1 171 2 15 cod 3540T612 Rev 01 02 2015...

Page 52: ...2 2 i i i i i 1 1 i 2 3 i i 4 5 i i 1 i 6 i i 2 i 7 i 8 0 1 TEST 2 3 i i i 8 1 1 i 7 i i i i i i 1 1 i i i A i i i 5 6 i 15 i i i i i A i 8 0 i i B i i i i 8 3 i 0 1 TEST i i i i i i i i i 2 4 7 1 i i...

Page 53: ...i i i i i i i i i i i i i i i i i i i i i i i B 3 5 i i i i 230 50 B i i i i i i i i i i i i i i sez 5 5 i i i i i i 3 i 3 i i i i I I i i i i i i i A C D E a1 i i a2 i i a3 i PEGASUS 119 LN 2S 930 22...

Page 54: ...30 i i i i i 2 3 i i i i A B C i A B G31 G20 G31 G20 G31 G20 G31 G20 PEGASUS 119 LN 2S 37 20 35 15 35 15 2 15 3 40 PEGASUS 136 LN 2S 37 20 35 15 35 15 2 15 3 40 PEGASUS 153 LN 2S 37 20 35 15 35 15 2...

Page 55: ...i V Honeywell VR 4601 CB i i A B 1 i A B C 2 i 4 2 B i i i i i i i i i i i i i i i i i i i i i i i i 8 1 1 i 7 1 50 C i i i i B i i i 15 i i i 3 4 i 8 3 i 0 1 TEST i i i i i i i i i A cap 5 8 1 0 i 7...

Page 56: ...i i i i i i 8 1 i i 2 i i i i 3 i i i i 4 5 6 10 15 7 8 A i i i i i i i i i A 9 B 9 i i i i i i i i i i i i i i i C 9 D 9 i i i i i i i i i i i i i i i i i i 9 i i 10 i 1 2 i 3 i 4 5 6 i 7 8 i 1 2 3 3...

Page 57: ...i i i i 11 1 2 i i 3 4 i 5 I i 4 4 A i i i i i i i 3 2 1 4 5 i i i i i i i i i i 10 i i i i i i i i i i i i i 10 i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i i...