The remote control (RTA11-M) allows manual adjustment
of the heating curve (±15 K). The remote control is optional
and it is not included in the full kit.
The heating circuit can be switched off manually, if the re-
mote control is set to the position “heating circuit off“.
Heating circuit switched-off means that the heating circuit
pump is switched off and the mixer closed.
Flow temperature is boosted to maximum for rapid heating
when the remote control it is set to “rapid heating“.
Manual correction (remote control)
arrangement/heat.circuits/heating circuit/
expert/man. corr.
selection: “Yes“, “No“
factory setting: “No“
Adjustment channel for allocating the remote control sen-
sor. The factory setting is sensor 10.
Sensor remote control
arrangement/heat.circuits/heating circuit/
expert/sen. remote
adjustment range: 1 ... 14
factory setting: 10
With this option it is possible to determine whether the
heating circuit pump remains switched-on or should be
switched off when the adjusted maximum flow temperature
is reached.
Pump HCmax
arrangement/heat.circuits/heating circuit/
expert/Pump hcmax
selection: “Yes“, “No“
factory setting: “No“
When this option is activated, the heating circuit opens
(mixer opens) and the heating circuit pump is switched-on
(provided that the chimney sweeper function is active, see
4.4). The protective function of the heating pump maximum
limitation will still be active.
Chimney sweeper
arrangement/heat.circuits/heating circuit/
expert/chimney
selection: “Yes“, “No“
factory setting: “No“
An additional external heating circuit module can be ac-
tivated (HKM) if a further compensated heating circuit is
required.
Heating module
arrangement/heat.circuits/options/HC module
selection: No / HCM1 / HCM2
factory setting: “No“
The displays and functions are similar to that of the internal
heating circuit (see also manual HKM2). The parameter
“heating circuit relay allocation“ is not available.
arrangement/heat.circuits/HC module...
External heating module:
arrangement/heat.circuits/heating circuit/
expert/sen.outdoor
adjustment range: 1 ... 21
factory setting: 11
change to: 16
If the external heating circuit module HKM2 is additionally
used, only 1 outdoor temperature sensor is required.In
order to ensure that both heating circuits control using the
same outdoor temperature, adjust to sensor 16 and connect
the external sensor to the HKM module.