BlueHelix HiTech RRT C
342
EN
cod. 3541V300 - Rev. 00 - 02/2021
Water inlet filter cleaning
•Disconnect the power supply and close the gas cock ahead of the valve.
•Isolate the boiler by operating the DHW inlet and system shut-off valves.
•Clean the water inlet filter.
fig. 56
fig. 57
3.4 Troubleshooting
Diagnostics
LCD display Off
If, even after touching the buttons, the display does not come on, check that the card is electrically
powered. Using a digital multimeter, check for presence of power.
In case of no voltage, check the wiring.
If the voltage is sufficient ( Range 195 – 253 Vac), check the fuse
(3.15AL@230VAC)
. The fuse
is on the card. To access it, see fig. 28.
LCD display On
In case of operation problems or faults, the display shows the fault identification code.
There are faults that cause permanent shutdowns (indicated with the letter "
A
"); to restore opera-
tion just press the button
for 1 second and confirm with the button
, or RESET via the re-
mote timer control (optional) if installed. If the boiler does not restart, the fault must be eliminated.
Other faults cause temporary shutdowns (indicated with the letter “
F
”) which are automatically re-
set as soon as the value returns within the boiler's normal working range.
Summary of Contents for BlueHelix HiTech RRT C
Page 45: ...BlueHelix HiTech RRT C 45 IT cod 3541V300 Rev 00 02 2021 fig 48 fig 49 fig 50 5 6 6 ...
Page 104: ...BlueHelix HiTech RRT C 104 ES cod 3541V300 Rev 00 02 2021 fig 48 fig 49 fig 50 5 6 6 ...
Page 163: ...BlueHelix HiTech RRT C 163 RO cod 3541V300 Rev 00 02 2021 fig 48 fig 49 fig 50 5 6 6 ...
Page 221: ...BlueHelix HiTech RRT C 221 PL cod 3541V300 Rev 00 02 2021 wygląd 48 wygląd 49 wygląd 50 5 6 6 ...
Page 280: ...BlueHelix HiTech RRT C 280 EL cod 3541V300 Rev 00 02 2021 İȚț 48 İȚț 49 İȚț 50 5 6 6 ...
Page 339: ...BlueHelix HiTech RRT C 339 EN cod 3541V300 Rev 00 02 2021 fig 48 fig 49 fig 50 5 6 6 ...
Page 354: ......
Page 355: ......