FEMA ELECTRÓNICA - Page 8

Input Menu

The input menu selects the input signal range. Options avail-

able are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T, 

E, S, R, N, C, L and X.

Note - Thermocouple X is a linear signal at 10uV/ºC.

The instrument manages up to 4 alarms. Each alarm is 

controlled by the condition “display higher (or lower) than 

the  configured  setpoint”.  The  front  leds  are  controlled  by 

the activation / deactivation of the related alarm. The relays 

installed on Option1 and/or Option2 are controlled by Alarm1 

and Alarm2.

Active (Act) -

 Value “On/Off”. Defines if the instrument has to 

manage this alarm or not. Select “Off” for alarm not managed. 

Type (tyPE) 

- Value “Max/Min”. Defines the behavior of the 

alarm as maximum or minimum alarm. The alarms config

-

ured as maximum are activated when the display value is 

equal or higher than the setpoint. The alarms configured as 

maximum are deactivated when the display is lower than 

the setpoint. The alarms configured as minimum have the 

inverse behavior.

Setpoint (SEt) - 

Value from “9999” to “-1999”. Alarm set point.

Hysteresis (hySt) -

 Value from “0” to “9999”. Points of hyster-

esis. The hysteresis applies on the deactivation of the alarm.

Delay (dEL) -

 Value from “0.0” to “99.9” seconds. Delay to be 

applied to the relay activation and deactivation. Relays are 

activated and deactivated  X seconds after the activation / 

deactivation of the alarm. The delay affects only to the relays. 

The delay does not affect to the front leds.

Setpoint2 (SEt2) - 

Value from  “-1999” to “9999”. Second 

setpoint. The second setpoint allows for the creation of acti-

vation windows. If the alarm is configured as maximum with 

setpoint 1000 and setpoint2 is configured at 1500, the alarm 

will be activated between 1000 and 1500 and the alarm will 

be deactivated when display is <1000 and  >1500. Setpoint2 

is affected on the same way as the setpoint with hysteresis 

and delays.

Display Menu

Functions on this menu allow for configuration of the visu

-

alization.

Steps (StEP) -

  Display changes on predefined steps. Values 

are 1, 2, 5, 10, 20 and 50. The display is made in steps of X 

counts. For example, select a step of 20 will make the display 

to change in steps of 20 (1420, 1440, 1460, ...).

Maximum (MAX) -

 Memory of maximum display. Indicates 

the maximum value of display since the last reset of the 

memory. Memory is reset on the following cases : manual 

reset from the Configuration Menu (Maximum), change on 

the input signal (Input), modification on the scaling (Scaling), 

change on the decimal point (dP), modification of the linear

-

ization segments, or instrument power-down.

Minimum  (MIn) -

 Memory of minimum display. Indicates the 

minimum value of display since the last reset of the memory. 

Memory is reset on the following cases : manual reset from 

the  Configuration  Menu  (minimum),  change  on  the  input 

signal (Input), modification on the scaling (Scaling), change 

on the decimal point (dP), modification of the linearization 

segments, or instrument power-down.

AlarmX Menu

Temperature Configuration Menu

The temperature configuration menu sets the function param

-

eters for Pt100/RTD and thermocouple sensors.

Degrees (dEG) - 

Value “ºC/ºF”. Select the temperature to be 

displayed in celsius or fahrenheit degrees.

Pt100/RTD resolution (P.rES) -

 Value “1º/0.1º”. Resolution 

for the Pt100/RTD. Select to display with degree or tenth of 

degree resolution.

Offset (oFFS) -

 Value from “-1999” to “9999” counts. Offset 

to be added to the reading. Both for Pt100/RTD and ther-

mocouples.

Thermocouple Cold Junction Compensation (t.cJc) - 

Val-

ue “On/Off”. Select “On” for automatic CJC compensation in 

the instrument. Select “Off” to disable the CJC compensation.

On break (on.bk) - 

Value “to_h/to_l”. Select “To L” to make 

the reading go to minimum, in case of probe broken. Select 

“To H” to make the reading go to maximum in case of probe 

broken.

Alpha (ALPh) - 

Value “385/390”. Select “385” or “390” ac-

cording to your PT100/RTD sensor.

Summary of Contents for S40-T

Page 1: ...th internal CJC selectable enabled or disabled Selectable behavior in case of sensor break to_high or to_low Reduced housing 72x36mm DIN standard Display in 4 digits and negative sign Maximum and mini...

Page 2: ...on the specified protection level Disconnect the instrument from power before starting any maintenance and or installation action Risk of electrical shock Instrument terminals can be connected to dan...

Page 3: ...he power line a protection fuse acting as disconnection element easily accessible to the operator and identified as a protection device Power H fuse 250mA time lag Power L fuse 400mA time lag 6 7 8 9...

Page 4: ...able 3 Offset drift see table 3 Span drift see table 3 Note span drift includes also the offset drift CJC automatic On Off selectable CJC accuracy 1 0 C CJC thermal drift 0 04 C On sensor break to_hig...

Page 5: ...nu or leaves the Informa tion Menu Operating the Information Menu 36 8 32 5 Mechanical Dimensions mm 72 18 80 69 Panel cut out Configuration Conf Information on the configured input sensor and the deg...

Page 6: ...the menu Allows selec tion of the current option displayed During a value selection menu for example a setpoint value validates the value on display Button UP Moves vertically on the menu Displays the...

Page 7: ...tion See menu for Alarm1 See menu for Alarm1 See menu for Alarm1 Alarm1 Setpoint Hysteresis Delay Active On Inactive Off Max Maximum Min Minimum Alarm management Alarm as max Alarm as min Counts Secon...

Page 8: ...fected on the same way as the setpoint with hysteresis and delays Display Menu Functions on this menu allow for configuration of the visu alization Steps StEP Display changes on predefined steps Value...

Page 9: ...message h udr Hardware underrange The thermocouple signal is lower than minimum readable signal 30mV h oVr Hardware overrange The thermocouple signal is higher than maximum readable signal 80mV d udr...

Page 10: ...ber 2011 Daniel Junc Quality Manager All instruments are warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse acc...

Page 11: ...User s Manual S40 T FEMA ELECTR NICA Page 11 T H I S P A G E B L A N K...