TST
Assembly instructions
FUF2 / FU3F -A/-C/-F
FEIG ELECTRONIC GmbH
page 86 of 114
TST_FUxF-A-C-F_Montageanleitung_EN_15
No.
Description
Possible reason for error
F.364
Safety edge testing failed
• Safety edge was not activated as expected when requesting a test.
• The time between request for testing and actual testing not in agreement
• The pre
-limit switch is set incorrectly
F.366
Too high a pulse frequency for optical safety edge
• Faulty opt
ical safety edge
• Defective input for internal safety edge
F.369
Internal safety edge incorrectly parametrized
• An internal safety edge is connected but deactivated → set P.460 to the used
edge type
F.371
Number of trips of the Safety input E, normally this is
the integrated safety edge evaluation, has reached
set limit (configurable in P.47E)
• Parametrized, maximum number of trips of the safety input E during a door
cycle was exceeded → close the door in jog mode to reset
• Check the set
number of trips in P.47E
F.372
Redundancy error with short circuit
• One of the processing channels for short circuit detection does not react
identically with the second channel.
• Controller board defective
F.373
Fault in the safety edge (message comes from
module)
• Cable break to safety edge, no edge connected, edge termination resistor
incorrect or defective
• Jumper for termination resistor definition in wrong position.
• Safety edge processing selected with Parameter P.470, but module
not
plugged in or wrong module.
F.374
Safety edge testing failed
• Pre
-limit switch for safety edge incorrectly set or defective
• Processing module defective
• Safety edge defective
F.379
Safety edge detection defective (coding pin or
parameter setting)
• No module plugged in but was reported as present by a parameter
• The controller was started up with another module than the one currently
plugged in
F.37A
Redundancy error of the 8K2 slip door switch on the
internal safety edge evaluation unit channel 1
• One of the contacts of the redundant 8k2 slip door switch is defective
• The slip door was not fully opened or closed
F.380
Short circuit detected on safety input
• Short circuit detected on edges with normally closed
contact
F.383
Interruption on safety input
• Connection cable defective or not connected
• Termination resistor incorrect or missing
• Jumper incorrectly set
F.384
Safety input testing failed
• Safety edge was not activated as expected when requesting a test.
• The time between request for testing and actual testing not in agreement
F.385
Fault in pre-limit switch for safety edge
• Pre
-limit switch for turning off the safety edge or reversing after safety edge
tripping remains tripped even in the upper end position.
F.386
Too high a pulse frequency for optical edge
• Defective optical safety edge
• Defective input for internal safety edge