TST
Startup
FU3E
FEIG ELECTRONIC GmbH
Page 24 of 29
FU3E_Inbetriebnahme_7_GB.doc
Parameters not set
F.090
Controller not parameterized
•
The basic parameters (P.205, P.100 to P.103) for the TST
FU3E controller have not yet been set.
Safety chain faults
F.201
Internal E-Stop „push-button“
tripped
or Watchdog (computer
monitor)
•
E-Stop chain was interrupted starting at input „internal E-
Stop“ without parameterizing mode having been selected
•
Internal parameter or EEPROM checks defective, pressing
the STOP key provides additional information about the
cause
F.211
External E-Stop 1 tripped
•
E-Stop chain was interrupted starting at Input 1
F.212
External E-Stop 2 tripped
•
E-Stop chain was interrupted starting at Input 2
Faults in the safety chain
F.360
Short circuit detected on edge
input
•
Short circuit detected on edges with normally closed
contact
F.361
Number of edge trips for
closing has reached set limit
•
Parameterized, maximum number of safety edge trips
during a door cycle was exceeded
F.362
Redundancy error with short
circuit
•
One of the processing channels for short circuit detection
does not react identically with the second channel.
Æ
Controller board defective
F.363
Interruption on edge input
•
Connection cable defective or not connected
•
Termination resistor incorrect or missing
•
Jumper J600 incorrectly set
F.364
Safety edge testing failed
•
Safety edge was not activated as expected when
requesting a test.
•
The time between request for testing and actual testing not
in agreement
F.365
Redundancy error with
interruption
•
One of the processing channels for interruption detection
does not react identically with the second channel.
Æ
Controller board defective
•
Dynamic optical system connected but not set in Parameter
P.460
F.366
Too high a pulse frequency
for optical safety edge
•
Defective optical safety edge
Defective input for internal safety edge
F.369
Internal safety edge
incorrectly parameterized
•
An internal safety edge is connected but deactivated
F.373
Fault in the safety edge
(message comes from
module)
•
Cable break to safety edge, no edge connected, edge
termination resistor incorrect or defective
•
Jumper for termination resistor definition in wrong position.
•
Safety edge processing selected with Parameter
P.470
, but
module not plugged in or wrong module.
F.374
Safety bar testing failed
•
Pre-limit switch for safety edge incorrectly set or defective
•
Processing module defective
•
Safety edge defective
F.379
Safety edge detection
defective (coding pin or
parameter setting)
•
No module plugged in but was reported as present by a
parameter
•
The controller was started up with another module than the
one currently plugged in