background image

7

SERVICE

OPERATION

I

& SAFETY PRECAUTIONS

I

ELECTRICAL REQUIREMENTS 

& SAFETY PRECAUTIONS

INSTALLATION

TROUBLESHOOTING

SERVICE

TROUBLESHOOTING

ELECTRONIC CONTROLS

WARRANTY

MAINTENANCE

OPERATION

INSTALLATION

WINDOW INSTALLATON

INSTALLATION

THRU-WALL INSTALLATION

INSTALLATION

AIRFLOW / FILTER

A

B

C

D

E

F

C

D

E

F

Power Control

Temperature/Timer Display

Temperature/Timer Controls

Mode Control

Fan Speed Control

Timer On/Off

A

B

Power Control

The Power Control turns the unit on and off.

Set Temperature/ Timer Display

Shows the set temperature when the unit is in operation and hours when the timer is

being set. THE TEMPERATURE DISPLAY ONLY SHOWS THE SET TEMPERATURE, NOT THE
ACTUAL ROOM TEMPERATURE.

Temperature/ Timer Hour Controls

These buttons are used to raise or lower the set temperature in increments of 1° from 66°

to 88°. By depressing both buttons at once, the display will toggle between Celsius and
Fahrenheit. When the timer is being set, these buttons are used to change the hour setting
in increments of 1 from 00 to 24.

Mode Control

A green light will indicate which mode is currently being utilized.

Cool Mode – The unit will circulate and cool the air.

Heat Mode (Heat Models Only)– The unit will circulate and heat the air.

Heater Safety Feature- When heater is powered off, low fan will automatically stay on
and run for 60 seconds to ensure the removal of residual heat, meanwhile, the Low Fan
LED blinks until the low fan stops.

Fan Mode – The unit will only circulate the air.

Energy Saver Mode – The fan will switch from the set fan speed to LOW whenever the

compressor turns off in response to the thermostat. When the compressor cycles back on,
the unit will return to the original fan setting. 

Fan Speed Control

High, Medium*, Low and Auto  *MEDIUM FAN NOT available on HEAT models.

The settings are adjusted with the Fan Speed Control, each time the button is depressed

it changes the setting. A green light will indicate which setting is currently being used.

When the AUTO feature is selected while the air conditioner is in the COOL or HEAT mode,

the fan speeds will change automatically as the temperature in the room changes.

COOL Mode

• 7° or more above the set temperature will use HI fan.

• 4° or less above the set temperature will use LO fan.

HEAT Mode (Heat models only)

• 9° or more below the set temperature will use HI fan.

• 4° or less below the set temperature will use LO fan.

Timer Control

The timer can be set to either turn the unit on or off

To turn the unit ON using the Timer:

Depress the timer key when the power is off,

the display will read 00. Adjust to the desired number of hours before TURN ON using the
up/down arrows.The display will show the time by hours left until TURN ON. To Turn the
timer off, depress the timer key. A green light next to the Timer Control indicates that the
timer is set.

To turn the unit OFF using the Timer:

Depress the timer key when the power is on,

the display will read 00. Adjust to the desired number of hours before TURN OFF using the
up/down arrows. The display will automatically return to the set temperature after 10
seconds.To display the amount of time left until TURN OFF, depress the timer button once.
To turn the TIMER OFF, depress the timer button twice. A green light next to the Timer
Control indicates that the timer is set. 

The functions work the same as your air conditioner’s touch controls.

Air Conditioner Remote Control 

AAA

IEC R03

1.5V

+

-

AAA

IEC R03

1.5V

CAUTION

Heat/Cool models or units with
electric heat are designed to be used
only as a supplemental heat source.
They should be used in addition to
regular heating systems and never as
the primary source of heat.

CAUTION

• Use only AAA or IEC R03 1.5V batteries.
• Remove the batteries if the remote controller is not used for a month or

longer.

• Do not attempt to recharge the supplied batteries
• All batteries should be replaced at the same time.
• Do not dispose of the batteries in a fire as they may explode.
• Do not mix old and new batteries.
• Do not install the batteries with the polarity (+/–) reversed.
• Keep batteries and other things that could be swallowed away from

young children. Contact a doctor immediately if an object is swallowed.

Built-in three minute timing delay.

If this electronic unit will not respond
to touch pad or remote control
commands, it is necessary to unplug
the unit from the electrical outlet for
five seconds and then plug the unit
back in.

Auto restart feature:
In the event of a power failure, this
feature allows the unit to resume
operation once power has been
restored, retaining the most recent
settings. Upon restoration of power,
the timer mode may need to be reset
if being utilized.

Summary of Contents for A7D18E2B

Page 1: ...e la grille d corative avant pr s du tableau de commande Communiquer ces num ros lors de toute correspondance ou appel au service apr s vente ayant trait au climatiseur ENGLISH Important Safety Instru...

Page 2: ......

Page 3: ...rdinances Use copper conductors of correct wire gauge and protector size only Do not alter cord or plug end Do not remove warning label on cord Important Grounding Requirements Air conditioner has a t...

Page 4: ...des of the cabinet and the window stopmolding This size unit requires two leveling brackets Fig 3b Decorative Front Removal 1 Remove the phillips screws on both sides of the cabinet Fig 4 3 Gently pul...

Page 5: ...y downward on the outside as shown by 1 2 a bubble off on a carpenter s level This outward pitch prevents water from entering the room Installation Other Than Flush Mount In order to install the unit...

Page 6: ...indow sill position 2 Slide the filler panel out from the air conditioner cabinet until the filler panel flange contacts the window stop molding position 3 Fig 14 4 Attach the filler panel to the face...

Page 7: ...e cabinet Measure height from top of cabinet to bottom of bar Add this measurement to the thickness of wood used to build the frame This will determine the size of wall opening needed Minimum 1 thick...

Page 8: ...nsate drain The fitting should be protruding approximately 1 2 above the bottom pan when fully threaded into the condensate drain Fig 21 3 If an open drain source is used to dispose of condensate plas...

Page 9: ...et temperature will use LO fan HEAT Mode Heat models only 9 or more below the set temperature will use HI fan 4 or less below the set temperature will use LO fan Timer Control The timer can be set to...

Page 10: ...moisture removal system Window vibration poor installation Improper installation Unit removing large quantity of moisture from humid room Push plug firmly into wall outlet Replace fuse with time delay...

Page 11: ...R USE OR PURPOSE ARE LIMITED IN DURATION TO FIVE YEARS FROM THE DATE OF ORIGINAL PURCHASE IN NO EVENT SHALL FEDDERS NORTH AMERICA BE LIABLE FOR INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES EVEN IF ADV...

Page 12: ...agar el aparato No bloquee la circulaci n del aire hacia las rejillas de ventilaci n exteriores del gabinete No obstruya el flujo del aire hacia el interior con persianas cortinas o muebles o hacia el...

Page 13: ...ambos lados del gabinet 2 Quite las dos perillas de control control mec nico solamente 3 Tire suavemente hacia adelante mientras sostiene los dos lados del frente decorativo C mo retirar el chasis Qui...

Page 14: ...erior usando la indicaci n de un nivel de carpintero Dicha inclinaci n evitar que el agua entre en la habitaci n Instalaci n diferente al montaje a ras Para instalar la unidad de modo que se proyecte...

Page 15: ...Deslizar el panel de relleno sac ndolo del gabinete del acondicionador de aire hasta que el reborde del panel de relleno haga contacto con la moldura de tope de la ventana posici n 3 Fig 13 4 Unir el...

Page 16: ...de la madera usada para construir el marco Esto determinar el tama o necesario de la cavidad en la pared El marco debe construirse usando madera de por lo menos 1 de espesor Cuando se determine el gro...

Page 17: ...1 2 sobre la bandeja inferior cuando est completamente enroscado en el drenaje de condensaci n Fig 21 3 Si se utiliza una fuente de drenaje abierta para eliminar el producto de la condensaci n podr ha...

Page 18: ...l modo Cool El ventilador cambiar de la velocidad de ajuste a velocidad baja cuando el compresor sea apagado por el termostato Cuando el compresor se activa nuevamente el ventilador volver al ajuste o...

Page 19: ...ndicionador de aire Para PONER EN MARCHA autom ticamente el acondicionador de aire usando el modo Timer 1 Oprima el bot n Timer cuando la alimentaci n el ctrica est desconectada El indicador mostrar 0...

Page 20: ...re est sucio Limpie el filtro Consulte la secci n frente decorativo el aire no puede pasar Limpieza del filtro de aire Para descongelar seleccione la posici n FAN ventilador El acondicionador de aire...

Page 21: ...FIN EN PARTICULAR DURANTE CINCO A OS A PARTIR DE LA FECHA DE COMPRA BAJO NINGUNA CIRCUNSTANCIA FEDDERS NORTH AMERICA SE HARA RESPONSABLE POR NINGUN DA O DIRECTO INDIRECTO O CONSECUENCIAL SIN IMPORTAR...

Page 22: ...it d alimentation Si la plaque signal tique du climatiseur indique qu il doit tre aliment sous 230 volts il faut que l appareil soit prot g par son propre fusible ou disjoncteur et aucun autre apparei...

Page 23: ...s solidement des surfaces fermes en bois ma onnerie ou m tal D pose du panneau frontal d coratif 1 Retirer les vis de chaque c t du bo tier 2 Retirer les deux boutons de commande Mod les m canique uni...

Page 24: ...n d calage d une demi bulle sur un niveau bulle Cette inclinaison vers l ext rieur emp che l eau de p n trer dans la pi ce Installation autre qu un montage encastr Pour poser l appareil dans des condi...

Page 25: ...travers le trou de la glissi re dans la fen tre int rieure 7 Couper le joint en mati re plastique mousse la longueur appropri e et l ins rer entre la fen tre ext rieure et la fen tre int rieure Insta...

Page 26: ...de l ouverture n cessaire dans le mur Pour la r alisation de l encadrement utiliser du bois pais d au moins 2 5 mm 1 po Pour d terminer la largeur finale de l encadrement tenir compte du fait que les...

Page 27: ...d charge du condensat un tube en plastique ou en caoutchouc peut relier directement le raccord de tuyau la source ouverte d vacuation Si une source ferm e d vacuation plomberie structurale interne es...

Page 28: ...uelle que soit la vitesse de rotation initialement s lectionn e Lors de la remise en marche du compresseur sur commande du thermostat le ventilateur adopte de nouveau la vitesse de rotation initialeme...

Page 29: ...erie 1 Appuyer sur le bouton de la minuterie alors que l appareil N est PAS ALIMENT L afficheur pr sentera 00 Effectuer avec les touches fl ch es le r glage de la valeur affich e pour indiquer le nomb...

Page 30: ...ement Le thermostat est r gl sur une temp rature R gler le thermostat sur un niveau de l arri re du panneau decoratif frontal trop lev e temp rature inf rieure Le climatiseur refroidit mais la L appar...

Page 31: ...RS NORTH AMERICA NE SAURAIT EN AUCUN CAS TRE TENU RESPONSABLE POUR LES DOMMAGES INDIRECTS SECONDAIRES OU ACCESSOIRES SANS GARD LA CAUSE M ME AU CAS O FEDDERS NORTH AMERICA AURAIT T PR VENU DE LA POSSI...

Page 32: ...atures and specifications subject to change without notice Las caracter sticas y especificaciones est n sujetas a cambio sin previo aviso Les caract ristiques et sp cifications sont sujettes modificat...

Reviews: